ATTACH THE BEZEL TO THE UPS
HARDWIRING INSTRUCTIONS
•Wiring must be performed by a qualified electrician.
•Adhere to all national and local electrical codes.
•Install a utility circuit breaker for input wiring, (see tables below).
220/230/240 V MODELS
Input Connections |
|
|
|
|
|
|
| Output Connection (optional) |
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
| |||
| . |
|
|
| Wire to L1A, N1, and |
|
| . |
| ||||||
|
|
|
|
|
|
| |||||||||
|
|
|
|
|
|
| |||||||||
|
|
|
|
|
|
|
|
| |||||||
|
| . |
|
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
| |||||
System |
| Wiring | Number |
| Voltage |
| Current |
| External Input | Wire | |||||
|
|
| of |
|
|
|
|
| Full Load |
| Circuit Breaker | Size | |||
|
|
| Phases |
|
|
|
| (Nominal) |
| (Typical) | (Typical) | ||||
SURT8000 |
| Input | 1 |
|
|
| 220/230/240 V |
| 40 A |
| 50 A / | 10mm2 | |||
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
| Input | 3+ |
|
| 380/400/415 V |
| 15 | A / phase when |
| 50 A / | 10mm2 | |||
|
|
| Neutral |
|
|
|
| online |
|
|
| ||||
|
|
|
|
|
|
|
|
|
| 40 | A on L1 in bypass |
|
|
| |
|
| Output | 1 |
|
|
| 220/230/240 V |
| 40 | A |
| (not required) | 10mm2 | ||
|
|
|
|
|
|
|
|
|
|
|
|
| |||
SURT10000 |
| Input | 1 |
|
|
| 220/230/240 V |
| 50 A |
| 63 A / | 16mm2 | |||
|
| Input | 3+ |
|
| 380/400/415 V |
| 18 | A / phase when |
| 63 A / | 16mm2 | |||
|
|
| Neutral |
|
|
|
| online |
|
|
| ||||
|
|
|
|
|
|
|
|
|
| 50 | A on L1 in bypass |
|
|
| |
|
| Output | 1 |
|
|
| 220/230/240 V |
| 50 | A |
| (not required) | 16mm2 |
2