Alarms and Events
Table 5: Possible Alarms
Charge reg. | Failure in charge regulation. The | Call APC Global Service. |
error (reg. = | unit transfers to battery until the |
|
regulator) | “Low DC shutdown” alarm occurs; |
|
| then, it transfers to |
|
| does not supply output voltage. |
|
|
|
|
External service | The external service bypass switch | Call APC Global Service. |
switch activated | is in the line position. The unit is in |
|
|
| |
| output voltage. However, the loads |
|
| may be receiving power from the |
|
| external manual bypass. |
|
|
|
|
Fan fault | If the fan monitoring option is | Call APC Global Service. |
| installed, this alarm sounds if one |
|
| or more of the fans are slowing |
|
| down. The unit’s status does not |
|
| change, but the problem may cause |
|
| other |
|
| that could change the unit’s status. |
|
|
|
|
Fatal Error | Components on the main controller | Call APC Global Service. |
RAM1 data | board have failed. |
|
error |
|
|
|
|
|
Fault in int. | There is a fault in the internal | Call APC Global Service. |
power supply | power supply unit (PSU). The UPS |
|
| transfers to |
|
| supply output voltage. |
|
|
|
|
High Battery | The ambient battery temperature | Make sure the room temperature |
Temperature | is higher than the set alarm level. | does not exceed 80° F (27° C). If |
| The unit’s status does not change, | so, cool down the room. If the |
| but battery life could be affected. | temperature was below 80° F (27° |
| This alarm is often caused by high | C) at the time of the alarm, find |
| room temperature. | the exhaust vents for the UPS |
|
| fans and check to see if the fans |
|
| are operating. Do not try to open |
|
| the unit, and do not insert |
|
| anything into a fan vent. If the |
|
| fans are not operating, call APC |
|
| Global Service. |
|
|
|
High DC | The monitored battery voltage is | Call APC Global Service. |
Warning | higher than the unit’s shutdown |
|
| setting. |
|
|
|
|
High DC | The monitored battery voltage is | Call APC Global Service. |
Shutdown | higher than the unit’s shutdown |
|
| setting. The unit will switch to |
|
| battery power to reduce DC bus |
|
| voltage. |
|
|
|
|
| |
|
|
User Guide APC BC300 Series 40kW 208/450/480V UPS | 15 |