APC BC300 manual UPS Stop/Start, UPS Stop for stand-by, UPS Start from stand-by

Page 5

UPS Stop/Start

2.0 UPS Stop/Start

WARNING!

AC voltage generated either from batteries or utility may be present at UPS output. Always disconnect AC input supply source, switch off UPS, AND switch off DC.

TEST BEFORE YOU TOUCH!

Some UPS systems have a factory-set auto-start feature, which automatically switches on the UPS whenever utility supply is switched on (AC line). See the “Parameter Settings” section in this User Guide for instructions on how to de-activate this function.

Only qualified electricians should start up or shut down APC BC300 Series UPS systems, and instructions in the Installation Guide should be followed. The UPS must be completely shut down before service or before the UPS is taken out of operation for more than 24 hours. Although you cannot completely start or shut down the unit, you can switch the UPS into stand-by mode and return it to normal operation by following the instructions below. (In stand- by mode, the UPS does not provide output voltage.)

2.1UPS Stop (for stand-by)

To put the unit into stand-by mode, press the red control button inside the unit’s front door.

2.2UPS Start (from stand-by)

To take the unit out of stand-by and switch it back to normal operation, press the

green control button inside the unit’s front door.

.

NOTICE!

Make sure the UPS operates in normal operation for at least 12 hours every three months to recharge the batteries.

 

990-1403

 

 

User Guide APC BC300 Series 40kW 208/450/480V UPS

5

Image 5
Contents Copyright 2002 APC Denmark ApS APC BC300 Series 40kW 208/450/480V User GuideThank You Safety Symbols used in this manualUser Guide APC BC300 Series 40kW 208/450/480V UPS Contents Display Unit IntroductionIntroduction UPS Stop/Start UPS Stop/StartUPS Stop for stand-by UPS Start from stand-byOperation OperationOperating Modes Sample Display Operation Mode DescriptionOperation Modes Using the keys Key Function Using the KeysDisplaying Measurements Operation Parameter Settings Parameter SettingsAPC Technical Support before changing this Parameter SettingsAlarms and Events Alarms and EventsSilencing the Audible Alarm Displaying the Alarm LogAlarm Description Action Message Alarm MessagesPossible Alarms Alarms and Events Alarms and Events Alarms and Events Alarms and Events 990-1403 Alarms and Events Alarms and Events Alarms and Events Displaying the Events Log Log Messages Mode DescriptionMaintenance and Testing Maintenance and TestingPreventive Maintenance Check Battery Monitor TestBattery Capacity Test Maintenance and Testing Start-up and Shutdown Procedure Start-up and Shutdown ProcedureStart-up from Maintenance Bypass Shutdown ProcedureIf you have shut the loads down Move on to step Specifications SpecificationsGeneral Specifications For Users in the United States OnlyFor Users in Canada Optional Service Programs Optional Hardware and Software FeaturesOptions OptionsOn-Site Service Preventive Maintenance VisitRemote Monitoring Service External Battery Installation ServiceLife Support Policy APC BC300 Series UPS Limited Factory WarrantyWarranty How to Contact APC How to Contact APCAPC Corporate Fairgrounds Road West Kingston, RIHow to Contact APC