Page 22

 

 

 

Alarms and Events

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 5: Possible Alarms

 

 

 

 

 

 

 

TSM 3 temp.

Inverter module 3 has shut down

Find the vents for the UPS fans

 

 

shutdown

because the temperature on the

and check to see if the fans are

 

 

 

heat-sink is higher than the

operating. Do not try to open the

 

 

 

shutdown level. If bypass is within

unit, and do not insert anything

 

 

 

tolerance, the unit transfers to

into a fan vent. If the fans are not

 

 

 

static bypass operation.

operating, call APC Global

 

 

 

If not, the unit transfers to stand-

Service.

 

 

 

by and does not supply output

If the fans are operating, make

 

 

 

voltage.

sure the room temperature is

 

 

 

 

below 80° F (27° C). If not, cool

 

 

 

 

down the room. if the room was

 

 

 

 

already below this temperature,

 

 

 

 

call APC Global Service.

 

 

 

 

 

 

 

TSM 3 temp.

The temperature on the heat-sink

Find the vents for the UPS fans

 

 

warning

for inverter module 3 is higher than

and check to see if the fans are

 

 

 

the warning setting. The unit’s

operating. Do not try to open the

 

 

 

status does not change. However, if

unit, and do not insert anything

 

 

 

the temperature continues to rise,

into a fan vent. If the fans are not

 

 

 

the unit will sound a “TSM 3 temp.

operating, call APC Global

 

 

 

shutdown” alarm.

Service.

 

 

 

 

If the fans are operating, make

 

 

 

 

sure the room temperature is

 

 

 

 

below 80° F (27° C). If not, cool

 

 

 

 

down the room. if the room was

 

 

 

 

already below this temperature,

 

 

 

 

call APC Global Service.

 

 

 

 

 

 

990-1403

22

User Guide APC BC300 Series 40kW 208/450/480V UPS

Image 22
Contents APC BC300 Series 40kW 208/450/480V User Guide Copyright 2002 APC Denmark ApSUser Guide APC BC300 Series 40kW 208/450/480V UPS Safety Symbols used in this manualThank You Contents Introduction IntroductionDisplay Unit UPS Stop for stand-by UPS Stop/StartUPS Stop/Start UPS Start from stand-byOperation OperationOperation Modes Sample Display Operation Mode DescriptionOperating Modes Using the Keys Using the keys Key FunctionDisplaying Measurements Operation Parameter Settings Parameter SettingsParameter Settings APC Technical Support before changing thisSilencing the Audible Alarm Alarms and EventsAlarms and Events Displaying the Alarm LogPossible Alarms Alarm MessagesAlarm Description Action Message Alarms and Events Alarms and Events Alarms and Events Alarms and Events 990-1403 Alarms and Events Alarms and Events Alarms and Events Log Messages Mode Description Displaying the Events LogPreventive Maintenance Check Maintenance and TestingMaintenance and Testing Battery Monitor TestBattery Capacity Test Maintenance and Testing Start-up from Maintenance Bypass Start-up and Shutdown ProcedureStart-up and Shutdown Procedure Shutdown ProcedureIf you have shut the loads down Move on to step General Specifications SpecificationsSpecifications For Users in the United States OnlyFor Users in Canada Options Optional Hardware and Software FeaturesOptional Service Programs OptionsRemote Monitoring Service Preventive Maintenance VisitOn-Site Service External Battery Installation ServiceAPC BC300 Series UPS Limited Factory Warranty Life Support PolicyWarranty APC Corporate How to Contact APCHow to Contact APC Fairgrounds Road West Kingston, RIHow to Contact APC