| Alarms and Events |
|
|
|
|
|
|
|
|
|
|
|
|
| Table 5: Possible Alarms |
| |
|
|
|
|
|
| TSM 3 temp. | Inverter module 3 has shut down | Find the vents for the UPS fans |
|
| shutdown | because the temperature on the | and check to see if the fans are |
|
|
| operating. Do not try to open the |
| |
|
| shutdown level. If bypass is within | unit, and do not insert anything |
|
|
| tolerance, the unit transfers to | into a fan vent. If the fans are not |
|
|
| static bypass operation. | operating, call APC Global |
|
|
| If not, the unit transfers to stand- | Service. |
|
|
| by and does not supply output | If the fans are operating, make |
|
|
| voltage. | sure the room temperature is |
|
|
|
| below 80° F (27° C). If not, cool |
|
|
|
| down the room. if the room was |
|
|
|
| already below this temperature, |
|
|
|
| call APC Global Service. |
|
|
|
|
|
|
| TSM 3 temp. | The temperature on the | Find the vents for the UPS fans |
|
| warning | for inverter module 3 is higher than | and check to see if the fans are |
|
|
| the warning setting. The unit’s | operating. Do not try to open the |
|
|
| status does not change. However, if | unit, and do not insert anything |
|
|
| the temperature continues to rise, | into a fan vent. If the fans are not |
|
|
| the unit will sound a “TSM 3 temp. | operating, call APC Global |
|
|
| shutdown” alarm. | Service. |
|
|
|
| If the fans are operating, make |
|
|
|
| sure the room temperature is |
|
|
|
| below 80° F (27° C). If not, cool |
|
|
|
| down the room. if the room was |
|
|
|
| already below this temperature, |
|
|
|
| call APC Global Service. |
|
|
|
|
|
|
22 | User Guide APC BC300 Series 40kW 208/450/480V UPS |