APC BC300 manual Battery Capacity Test

Page 25

Maintenance and Testing

To perform a battery monitor test:

1.Press to display the user parameters.

2.Press or to scroll through parameters until the display shows “Battery monitor test.”

3.Press to start the battery monitor test. The display shows “Batt. operation time > xxx min.”

(“xxx” = the minutes of runtime remaining. This number will fluctuate during the test.)

4.When the test is complete, the display will show “Normal operation load power xx%” if the batteries are in acceptable condition. If the test has determined that the condition of the batteries is unacceptable, the unit will display either a “Battery monitor warning” or “Battery monitor alarm.” See the “Alarm Messages” section for a detailed description of these alarms.

6.3Battery Capacity Test

NOTICE!

If you are using UPS contacts for a communication link, take the necessary precautions so this test will not cause a premature shutdown. See your software documentation for more information.

The battery capacity test discharges the batteries to the “Low DC warning” level and displays the estimated runtime. This estimate is only correct for the unit’s condition at the time of the battery capacity test. If the load changes and you would like to display the estimated runtime, you must perform this test again. After a battery capacity test, the unit must charge the batteries for at least eight hours before full battery capacity and full runtime have been restored.

To perform a battery capacity test, follow these steps:

1.Press to display the user parameters.

2.Press or to scroll through the parameters until the display shows this: Battery capacity test: xxx

(“xxx” = the backup time from the last test). If the test has never been performed before or if the test has been aborted, the display will show “???.”

3.Press to abort the test or to continue. The display shows “Batt. operation time xxx min.”

4.If you wish to abort the test while it is in progress, follow these steps:

990-1403

User Guide APC BC300 Series 40kW 208/450/480V UPS

25

Image 25
Contents Copyright 2002 APC Denmark ApS APC BC300 Series 40kW 208/450/480V User GuideUser Guide APC BC300 Series 40kW 208/450/480V UPS Safety Symbols used in this manualThank You Contents Introduction IntroductionDisplay Unit UPS Stop/Start UPS Stop/StartUPS Stop for stand-by UPS Start from stand-byOperation OperationOperation Modes Sample Display Operation Mode DescriptionOperating Modes Using the keys Key Function Using the KeysDisplaying Measurements Operation Parameter Settings Parameter SettingsAPC Technical Support before changing this Parameter SettingsAlarms and Events Alarms and EventsSilencing the Audible Alarm Displaying the Alarm LogPossible Alarms Alarm MessagesAlarm Description Action Message Alarms and Events Alarms and Events Alarms and Events Alarms and Events 990-1403 Alarms and Events Alarms and Events Alarms and Events Displaying the Events Log Log Messages Mode DescriptionMaintenance and Testing Maintenance and TestingPreventive Maintenance Check Battery Monitor TestBattery Capacity Test Maintenance and Testing Start-up and Shutdown Procedure Start-up and Shutdown ProcedureStart-up from Maintenance Bypass Shutdown ProcedureIf you have shut the loads down Move on to step Specifications SpecificationsGeneral Specifications For Users in the United States OnlyFor Users in Canada Optional Service Programs Optional Hardware and Software FeaturesOptions OptionsOn-Site Service Preventive Maintenance VisitRemote Monitoring Service External Battery Installation ServiceLife Support Policy APC BC300 Series UPS Limited Factory WarrantyWarranty How to Contact APC How to Contact APCAPC Corporate Fairgrounds Road West Kingston, RIHow to Contact APC