APC BC300 manual Operation Modes, Operating Modes, Sample Display Operation Mode Description

Page 7

Operation

3.1Operation Modes

The display automatically indicates which mode the unit is operating in. See Table 1 below for sample display messages and an explanation of each.

 

Table 1: Operating Modes

 

 

Sample Display

Operation Mode Description

Mode

 

 

 

Normal Operation

The UPS is in the normal operation mode. During normal operation,

load power ##%

utility (AC line) passes through the UPS and to the load. The inverter

 

regulates the output and charges the batteries. The UPS measures

 

all three phases, and the display reads out the% load of the highest

 

loaded phase.

 

 

Battery Operation

When AC input is out of tolerance (outside programmed limits), the

time ## minutes

UPS is running in battery mode. The main static switch is open, and

 

the inverter is powered from the batteries. The power is then fed to

 

the loads. If the batteries are depleted, the unit will switch to stand-

 

by mode (see below) and wait for utility to return in tolerance. If auto-

 

start is programmed to “ON,” the unit will automatically start about

 

30 seconds after utility has returned. If auto-start is programmed to

 

“OFF,” you must start the unit manually by pressing the green

 

button inside the front door. (See the “Parameter Settings” section in

 

this User Guide.)

 

 

Bypass Operation

The AC input passes unregulated through the bypass static switch,

 

through the main transformer, and to the loads. The UPS’ inverter is

 

in stand-by and is synchronized to the utility, ready to transfer the

 

unit to battery operation if utility voltage is out of tolerance.

 

 

Economy Mode

The unit has been programmed to operate in economy mode. The AC

 

power flows in bypass, and the UPS will periodically transfer to

 

normal operation to charge the batteries (at 7-day intervals by UPS

 

default). The inverter is in stand-by and is synchronized to utility,

 

ready to transfer to battery operation if utility voltage is out of

 

tolerance. The output voltage is not regulated in this mode, but

 

efficiency increases. Call APC Technical Support or your nearest

 

APC office for more information on programming your APC BC300

 

Series UPS for Economy Mode.

 

 

** Stand-by **

Both static switches are open. The unit is not supplying output

 

voltage.

 

 

 

990-1403

 

 

User Guide APC BC300 Series 40kW 208/450/480V UPS

7

Image 7
Contents Copyright 2002 APC Denmark ApS APC BC300 Series 40kW 208/450/480V User GuideUser Guide APC BC300 Series 40kW 208/450/480V UPS Safety Symbols used in this manualThank You Contents Introduction IntroductionDisplay Unit UPS Start from stand-by UPS Stop/StartUPS Stop/Start UPS Stop for stand-byOperation OperationOperation Modes Sample Display Operation Mode DescriptionOperating Modes Using the keys Key Function Using the KeysDisplaying Measurements Operation Parameter Settings Parameter SettingsAPC Technical Support before changing this Parameter SettingsDisplaying the Alarm Log Alarms and EventsAlarms and Events Silencing the Audible AlarmPossible Alarms Alarm MessagesAlarm Description Action Message Alarms and Events Alarms and Events Alarms and Events Alarms and Events 990-1403 Alarms and Events Alarms and Events Alarms and Events Displaying the Events Log Log Messages Mode DescriptionBattery Monitor Test Maintenance and TestingMaintenance and Testing Preventive Maintenance CheckBattery Capacity Test Maintenance and Testing Shutdown Procedure Start-up and Shutdown ProcedureStart-up and Shutdown Procedure Start-up from Maintenance BypassIf you have shut the loads down Move on to step For Users in the United States Only SpecificationsSpecifications General SpecificationsFor Users in Canada Options Optional Hardware and Software FeaturesOptional Service Programs OptionsExternal Battery Installation Service Preventive Maintenance VisitOn-Site Service Remote Monitoring ServiceLife Support Policy APC BC300 Series UPS Limited Factory WarrantyWarranty Fairgrounds Road West Kingston, RI How to Contact APCHow to Contact APC APC CorporateHow to Contact APC