Operation Procedures
Note: If the system does not contain a
Total Power Off procedure
Warning: Before electrical installation begins, verify that the UPS is in the Total Power Off mode by following this procedure.
UPS
ON TRIP OFF
XR Battery enclosures /
Set the SYSTEM ENABLE switch to the the OFF position.
Set the DC DISCONNECT switch on all XR Battery enclosures and on the back of the
Disconnect all battery units by removing them or pulling them out to the red disconnect line.
Caution: To ensure the enclosure does not tip, do not pull the battery units out beyond the red disconnect line unless you completely remove them from the enclosure.
8 | Symmetra PX 160 kW 400 V Operation |