APC SYCFXR9 manual How to replace a battery module, How to replace a power distribution module

Page 25

Maintenance: Parts Replacement

How to replace a battery module

Use two people to lift components weighing between 18–32 kg/40–70 lb.

Holding the handle, gently lift the battery unit and pull it halfway out. A lock mechanism prevents it from being pulled all the way out.

Release the lock by pushing the battery unit upwards and pull the battery unit all the way out while supporting it

Take the replacement battery unit and push it into the system.

Note: Allow for a 24-hour recharging period of the batteries after system start-up/battery replacement for battery monitoring data to become fully reliable.

How to replace a power distribution module

Disconnect the power cable from the power distribution module from the extension cable.

Open the locking latch on the module and gently pull it out of the enclosure.

Reverse the procedure to install the new module.

990-3015-001

Symmetra PX 160 kW 400 V Operation

19

Image 25
Contents Operation Page About this Manual Updates to this manualCompanion manuals Page Contents Maintenance Safety Page User Interface OverviewInterface area Display interface Menu tree UPSPage Operation Modes OperationTotal Power Off procedure Operation ProceduresHow to put the UPS in maintenance bypass operation How to turn the load on/off using the display interfaceYES, Turn UPS Off How to return to normal operation How to view the Log screen How to view the Status screensSystem Settings ConfigurationHow to change the date and time How to change the settingsPage Parts Replacement MaintenanceHow to determine if you need a replacement part How to return parts to APCPart APC Part No Replacement partsHow to install a power module How to remove a power moduleHow to replace an intelligence module MIM/RIM How to replace a power management peripheralHow to replace a power distribution module How to replace a battery modulePage UPS Alarms TroubleshootingTroubleshooting UPS Alarms Specified range Display Message Meaning Corrective Action Modular Distribution fault list PDU fault list Page Page Page 990-3015-001 APC Worldwide Customer Support04/2007