APC SY160K160H, PDUM160H-B, SYCFXR9 manual PDU fault list

Page 32

PDU fault list

Display Message

Meaning

Corrective Action

 

 

 

Maintenance Bypass Alarm

The system is in maintenance

No corrective action necessary.

 

bypass: the Q2 switch is open

 

 

and the Q3 switch is closed.

 

 

 

 

Output V <Ln-N>

Phase-to-neutral output voltage

Evaluate the threshold setting. If necessary,

Voltage Under Limit

for phase <L-N> has dropped

adjust it for your situation.

 

below the configured limit.

 

 

 

 

Output V <Ln-N>

Phase-to-neutral output voltage

Evaluate the threshold setting. If necessary,

Voltage Over Limit

for phase <L-N> exceeded the

adjust it for your situation.

 

configured limit.

 

 

 

 

Output I L<n>

Current of output phase <n>

Evaluate the threshold setting. If necessary,

Current Over Limit

exceeded the configured limit.

adjust it for your situation.

 

 

 

Output I L<n>

Current of output phase<n>

Evaluate the threshold setting. If necessary,

Current Under Limit

dropped below the configured

adjust it for your situation.

 

limit.

 

 

 

 

Output FDev

Frequency of the output current

Evaluate the threshold setting. If necessary,

Freq Out of Range

is above or below the range that

adjust it for your situation.

 

is configured as acceptable.

 

 

 

 

<User Contact Name>

A user-configured contact

Determined why the alarm has occurred. This

Alarm Active

connected to the system is

is a user-specific alarm setting.

 

reporting an alarm condition.

 

 

 

 

No UPS Input

The Q1 circuit breaker is open,

Close the Q1 switch to re-connect the UPS to

Breaker Q1 Open

and the UPS is disconnected

utility/mains power.

 

from the input voltage.

 

 

 

 

No Panel Feed

The Q2 & Q3 circuit breakers

For safety reasons, ensure the switches were

Breakers Q2 & Q3 Open

are open, and the system is not

not closed for maintenance purposes. If not,

 

supporting connected

close Q2 for UPS operation, and Q3 for

 

equipment.

maintenance bypass.

Atypical Bypass Mode

The system state as set by the

Alarm

Q1, Q2, & Q3 breakers is in a

 

non-typical bypass mode.

Option 1: Resume normal UPS operation.

Option 2: Go to maintenance bypass.

26

Symmetra PX 160 kW 400 V Operation

990-3015-001

Image 32
Contents Operation Page Companion manuals Updates to this manualAbout this Manual Page Contents Maintenance Safety Page Interface area OverviewUser Interface Display interface UPS Menu treePage Operation Operation ModesOperation Procedures Total Power Off procedureHow to turn the load on/off using the display interface How to put the UPS in maintenance bypass operationYES, Turn UPS Off How to return to normal operation How to view the Status screens How to view the Log screenConfiguration System SettingsHow to change the date and time How to change the settingsPage Maintenance Parts ReplacementHow to determine if you need a replacement part How to return parts to APCReplacement parts Part APC Part NoHow to remove a power module How to install a power moduleHow to replace a power management peripheral How to replace an intelligence module MIM/RIMHow to replace a battery module How to replace a power distribution modulePage Troubleshooting UPS AlarmsTroubleshooting UPS Alarms Specified range Display Message Meaning Corrective Action Modular Distribution fault list PDU fault list Page Page Page 04/2007 APC Worldwide Customer Support990-3015-001