Operation: Operation Procedures
Press ESC to go back to the UPS Control screen and select UPS into Bypass.
Note: The H2 LED next to the Q2 switch will illuminate, indicating that it is safe to operate the Q2 switch.
Set the Q2 switch on the
Note: The H3 LED next to the Q3 switch will illuminate, indicating that it is safe to operate the Q3 switch.
Set the Q3 switch on the
The UPS is now in normal operation. Verify that the Load Powered LED is lit and the system is not displaying any alarms.
How to view the Status screens
Use the main menu screen to access information for each component of the system. A status screen is available for each component, this example uses the UPS.
|
|
|
|
|
|
|
| UPS | Alarms |
|
|
| ||
|
|
| Power Dist | Log |
|
|
| Switch Gear | Admin |
|
|
| Environment | Help |
|
|
|
|
|
|
|
|
|
|
Symmetra PX 160 kW
On Line
Press
Press
Press
UPS Control
UPS Status
UPS Tests & Diags
UPS Configuration
Use the UP and DOWN arrow keys to navigate through the Status screens.
No UPS Alarms
How to view the Log screen
UPS Alarms
Power Dist Log
Switch Gear Admin
Environment Help
Log Item > 1 of 2
Press | | Press |
| View New Log | Items |
| View Entire Log | |
| Clear Entire | Log |
Use the UP and DOWN arrow keys to navigate through the Log screens.
<Description>
03/14/07 10:37:02
12 | Symmetra PX 160 kW 400 V Operation |