External Connection
4.9.1 Battery Breaker Box
UPS | Ampere | Connection | Max. | Dimensions | Weight |
| Rating | Cable | short- | HxWxD [mm] | [kg] |
| [A] | [mm2] | circuit |
|
|
|
|
| current [kA] |
|
|
|
|
|
|
|
|
240 kW | 400 | 2//95 | 40 | 1035x835x300 | 100 |
320 kW | 500 | 2//150 | 40 | 1035x835x300 | 100 |
|
|
|
|
|
|
32 | Installation Guide APC Silcon |