American Power Conversion 240-320kW 400V manual Action, Display shows

Page 53

Options/Accessories

Action

1.Check that output switch (Q004) is in position “0”

2.Check that all output switches (Q002) are in position “0”

3.Turn input switches (Q001) to position “1”

4.Open the UPS front door and press the green “ON” push-botton

5.Press on the keyboard

6.Press or on the keyboard until

7.

Press

on the keyboard

8.

Press

on the keyboard

All systems will transfer to bypass operation

9.Check that all output switches (Q002) are in position “0”

10.Turn all output switches (Q002) to position ”1“

11.Turn the output switch (Q004) to position ”1“

12. Turn the bypass switch (Q003) to position “0”

Display shows

** System OFF **

Normal operation load power 0%

Bypass operation :NO

Bypass operation

:YES

Bypass operation

Lamp indication

on Service Bypass Panel

The green lamps (H002) above all the output switch handles (Q002) lights.

The green lamp

(H004) above the output switch (Q004) handle also lights.

The green lamps (H002) above all the output switch handles (Q002) light. The green lamp (H004) above the output switch (Q004) handle and the green lamp (H003) above the bypass switch light.

The green lamps (H002) and (H004) do not light any longer. (H003) will light until normal operation.

990-4045a

Installation Guide APC Silcon 240-320kW 400V UPS

53

Image 53
Contents APC Silcon 240-320kW 400V UPS Installation Guide Thank You Installation Guide APC Silcon 240-320kW 400V UPSSafety Symbols used in this manual Contents Warranty System Specifications10.0 How to Contact APC AppendixIntroduction IntroductionTools and Equipment ToolsUnpacking UnpackingInstallation InstallationRequirements on Site Height mm Width mm Depth mmFootprint 2 825mm Cabinet for Isolation Transformer or Switch Gear1 1600mm Cabinet for 240-320kW UPS 3 1600mm Cabinet for Isolation TransformerExternal Connection Connecting the UPSExternal Connection Right side viewFuses Output240kW 320kWSystem Integration Interface Connections Terminal Blocks X003/X004 Anxiliary Contacts Parallel BoardX005 Output Relays Parallel BoardExternal Connection External Control Cables Power CablesRelays Relay BoardRelay Board/Relay Functions Relay Message Alarm-trigging Events NumberSee .2 System configuration Communication Interface Board Connecting of APC Silcon Tripel Chassis APC Silcon Triple Chassis Safety WarningsProduct Description Monitoring PortInstalling Management Peripherals Optional Power InputLEDs If the LED is… Then the Silcon Triple Chassis…Order of Management Peripheral Cards Installing Management Peripheral CardsManagement Priority Position Peripheral Card Daisy-chaining the APC Silcon Triple ChassisManagement Peripheral Draw mA If Problems Persist TroubleshootingProblem Possible Cause Solution Product Specifications Monitoring Port Pin Assignments External Connection Environmental Power, Physical, and Environmental SpecificationsPhysical Important Safety Instructions APC Silcon Battery CabinetsSilcon Installation of BatteriesDiagram UPS with Battery Cabinet Battery Breaker Box/Fuse-box Ampere Connection Max Dimensions Weight Rating Cable Short Battery Breaker BoxCircuit Current kA 240 kW 320 kWAPC Battery Breaker Box Connection Diagram External Connection Programming Parameters Parameter Setting CommentsProgramming Parameters ParametersProgramming Keys Programming Example Switch to Bypass Operation System ConfigurationSystem Configuration Parameters password protected Programming Example Change Charge Voltage to Change parameters by pressing Programming Parameters for Advanced Parallel Operation Description of SettingsProgramming example Battery MonitorService Bypass Panel for Single Operation Options/AccessoriesOptions/Accessories Options/Accessories Display shows Operating The External Service Bypass SwitchLamp indication On Servive Bypass Panel Switching from External Bypass to Normal UPS OperationService Bypass Panel for Parallel Redundant Operation Two Parallel Systems with Service Bypass Panel Options/Accessories H002a Action Options/Accessories Display shows Lamp indication On Service Bypass PanelAction Following can be carried out on any UPS Isolating One UPS for Service/MaintenanceSwitching Back to Normal Parallel/Redundant Operation Intersystem Synchronization Unit ISU Intersystem Synchronization UnitIntersystem Synchronization Unit System ISU System Standard Short-haul RS232 Modem Async Remote DisplayExtension of Remote Display Communication Distance Host DTE Remote Display DTE Connections Without ConverterConnections With Converter Pin Connections for cable from host to ME800A-R2 HostRemote Display Cables Remote Display Power SupplyRemote Display Setting Communication FaultAlarms Remote Display UseIsolation Transformer Height mm Width mm Depth mm Weight kgExternal External PE Input Fuses Input Cable Connecting Isolation TransformerFM a 120 DIN gL typesOptions/Accessories Isolation External External PE Cable mm2 SignalInput Input Cable Output Temp Fuses* FM 150 185Options/Accessories Options/Accessories Options/Accessories Options/Accessories Options/Accessories System Specifications System SpecificationsTechnical Data Dimensions / WeightAPC Silcon Series Limited Factory Warranty WarrantyWarranty Appendix Installation Planning DataAppendix Appendix How to Contact APC How to Contact APCAPC Corporate Fairgrounds Road West Kingston, RI APC Denmark Silcon Allé DK-6000 Kolding