American Power Conversion 240-320kW 400V manual System Configuration Parameters password protected

Page 38

Programming Parameters

System Configuration Parameters (password protected)

Parameter

Setting*

Comments

 

 

 

Isolation Transformer Input

YES, NO

YES if optional input isolation transformer is available

 

 

 

IsolationTransformer

YES, NO

YES if optional output isolation transformer is available

Output

 

 

 

 

 

Delta Soft Start Time

1, 10, 20, 40 sec.

Input current switching in ramp function. Use higher

 

 

values for smaller/unstable diesel generators

 

 

 

External SSW present

YES, NO

YES for systems with external static bypass switch

 

 

 

Normal Charge Voltage

410-460V

Setting of float charge voltage at 20°C

 

438V

(Automatic compensation for temperature deviations)

 

 

 

Boost Charge Voltage

438-460V

Setting of boost charge voltage at 20°C

 

438V

(Automatic compensation for temperature deviations)

 

 

 

Low Battery warning

336-384V

Discharged Battery warning

 

336V

 

 

 

 

Low Battery shut-down

310-336V

Switches off system at min. permissible battery

 

326V

voltage

 

 

 

Synchronization

0.25, 0.5, 1, 2, 4

Syncronization speed.

 

Hz/sec.

 

 

 

 

High Battery Temperature

15-40°C

Alarm - Ambient temperature for battery too high

 

35°C

 

 

 

 

Common fault delay

0, 10, 20,

Delay before common fault alarm relay is activated

 

30 sec.

 

 

 

 

Reset operation mode lock

YES, NO

YES resets system locked in bypass or battery

 

 

operation mode caused by system failures (only

 

 

applicable for service personnel)

 

 

 

Expected back-up time

0.1-999.9

Expected UPS back-up time in minutes when running

(min.)

5.0

at 100% ohmic load. Time used by ABM**

 

 

 

Battery Capacity in (Ah)

0.1-999.9

Total Battery capacity in Ah.

 

7.0

Setting used by ABM**.

 

 

 

Highest Station Address

2-9

Highest station address in parallel system

 

 

 

Station Address

1-9

Station address in parallel system

 

 

 

APM Mode Active

Disabled

Use only in parallel systems.

(Advanced Power

Redundant +1

Disabled: Advanced power management off.

Management)

Parallel +1

Redundant +1: Redundant operation with one unit

 

 

being inactive in parallel system

 

 

Parallel +1: Redundant operation with all units in

 

 

operation.

 

 

 

APM Test Mode Active

YES, NO

YES, if APM test mode is active

 

 

 

Battery Connection

Common,

Common: if common battery is used in parallel system.

 

Separate

Separate: if separate battery is used

 

 

 

*Bold text refers to factory standard setting **Advanced Battery Monitor

990-4045a

38

Installation Guide APC Silcon 240-320kW 400V UPS

Image 38
Contents APC Silcon 240-320kW 400V UPS Installation Guide Thank You Installation Guide APC Silcon 240-320kW 400V UPSSafety Symbols used in this manual Contents 10.0 How to Contact APC System SpecificationsWarranty AppendixTools and Equipment IntroductionIntroduction ToolsUnpacking UnpackingRequirements on Site InstallationInstallation Height mm Width mm Depth mm1 1600mm Cabinet for 240-320kW UPS 2 825mm Cabinet for Isolation Transformer or Switch GearFootprint 3 1600mm Cabinet for Isolation TransformerExternal Connection Connecting the UPSExternal Connection Right side view240kW OutputFuses 320kWSystem Integration Interface Connections X005 Output Relays Parallel BoardTerminal Blocks X003/X004 Anxiliary Contacts Parallel BoardExternal Connection Power Cables External Control CablesRelay Board RelaysRelay Message Alarm-trigging Events Number Relay Board/Relay FunctionsSee .2 System configuration Communication Interface Board Connecting of APC Silcon Tripel Chassis Product Description Safety WarningsAPC Silcon Triple Chassis Monitoring PortLEDs Optional Power InputInstalling Management Peripherals If the LED is… Then the Silcon Triple Chassis…Management Priority Position Peripheral Card Installing Management Peripheral CardsOrder of Management Peripheral Cards Daisy-chaining the APC Silcon Triple ChassisManagement Peripheral Draw mA If Problems Persist TroubleshootingProblem Possible Cause Solution Product Specifications Monitoring Port Pin Assignments External Connection Environmental Power, Physical, and Environmental SpecificationsPhysical APC Silcon Battery Cabinets Important Safety InstructionsSilcon Installation of BatteriesDiagram UPS with Battery Cabinet Battery Breaker Box/Fuse-box Circuit Current kA 240 kW Battery Breaker BoxAmpere Connection Max Dimensions Weight Rating Cable Short 320 kWAPC Battery Breaker Box Connection Diagram External Connection Programming Parameters Parameter Setting CommentsProgramming Parameters ParametersProgramming Keys System Configuration Programming Example Switch to Bypass OperationSystem Configuration Parameters password protected Programming Example Change Charge Voltage to Change parameters by pressing Description of Settings Programming Parameters for Advanced Parallel OperationBattery Monitor Programming exampleService Bypass Panel for Single Operation Options/AccessoriesOptions/Accessories Options/Accessories Operating The External Service Bypass Switch Display showsSwitching from External Bypass to Normal UPS Operation Lamp indication On Servive Bypass PanelService Bypass Panel for Parallel Redundant Operation Two Parallel Systems with Service Bypass Panel Options/Accessories H002a Action Options/Accessories Display shows Lamp indication On Service Bypass PanelAction Isolating One UPS for Service/Maintenance Following can be carried out on any UPSSwitching Back to Normal Parallel/Redundant Operation Intersystem Synchronization Unit ISU Intersystem Synchronization UnitIntersystem Synchronization Unit System ISU System Standard Short-haul RS232 Modem Async Remote DisplayExtension of Remote Display Communication Distance Connections With Converter Connections Without ConverterHost DTE Remote Display DTE Pin Connections for cable from host to ME800A-R2 HostRemote Display Power Supply Remote Display CablesAlarms Communication FaultRemote Display Setting Remote Display UseHeight mm Width mm Depth mm Weight kg Isolation TransformerFM a Connecting Isolation TransformerExternal External PE Input Fuses Input Cable 120 DIN gL typesOptions/Accessories Input Input Cable Output Temp Fuses* FM Cable mm2 SignalIsolation External External PE 150 185Options/Accessories Options/Accessories Options/Accessories Options/Accessories Options/Accessories Technical Data System SpecificationsSystem Specifications Dimensions / WeightAPC Silcon Series Limited Factory Warranty WarrantyWarranty Appendix Installation Planning DataAppendix Appendix APC Corporate Fairgrounds Road West Kingston, RI How to Contact APCHow to Contact APC APC Denmark Silcon Allé DK-6000 Kolding