6.2.4 Isolating One UPS for Service/Maintenance

In a redundant system, one UPS may be isolated for service/maintenance without affecting other UPSs.

1.Check that remaining UPS(s) is capable of carrying the load in the event that one UPS is isolated

2.Switch off system to be isolated for maintenance purposes by pushing green “ON” and red “OFF” buttons simultaneously

3.To disconnect battery, mains and output, open battery MCCB/fuse and set input switch (Q001) and output switch (Q002) to position “0”

With Q002 in position “0”, UPS will be operational and may be tested as a single system without affecting other parallel UPS(s).

990-4045a

54

Installation Guide APC Silcon 240-320kW 400V UPS

Image 54
Contents APC Silcon 240-320kW 400V UPS Installation Guide Installation Guide APC Silcon 240-320kW 400V UPS Safety Symbols used in this manualThank You Contents 10.0 How to Contact APC System SpecificationsWarranty AppendixTools and Equipment IntroductionIntroduction ToolsUnpacking UnpackingRequirements on Site InstallationInstallation Height mm Width mm Depth mm1 1600mm Cabinet for 240-320kW UPS 2 825mm Cabinet for Isolation Transformer or Switch GearFootprint 3 1600mm Cabinet for Isolation TransformerExternal Connection Connecting the UPSExternal Connection Right side view240kW OutputFuses 320kWSystem Integration Interface Connections X005 Output Relays Parallel BoardTerminal Blocks X003/X004 Anxiliary Contacts Parallel BoardExternal Connection Power Cables External Control CablesRelay Board RelaysRelay Message Alarm-trigging Events Number Relay Board/Relay FunctionsSee .2 System configuration Communication Interface Board Connecting of APC Silcon Tripel Chassis Product Description Safety WarningsAPC Silcon Triple Chassis Monitoring PortLEDs Optional Power InputInstalling Management Peripherals If the LED is… Then the Silcon Triple Chassis…Management Priority Position Peripheral Card Installing Management Peripheral CardsOrder of Management Peripheral Cards Daisy-chaining the APC Silcon Triple ChassisManagement Peripheral Draw mA Troubleshooting Problem Possible Cause SolutionIf Problems Persist Product Specifications Monitoring Port Pin Assignments External Connection Power, Physical, and Environmental Specifications PhysicalEnvironmental APC Silcon Battery Cabinets Important Safety InstructionsInstallation of Batteries Diagram UPS with Battery CabinetSilcon Battery Breaker Box/Fuse-box Circuit Current kA 240 kW Battery Breaker BoxAmpere Connection Max Dimensions Weight Rating Cable Short 320 kWAPC Battery Breaker Box Connection Diagram External Connection Programming Parameters Parameter Setting CommentsProgramming Parameters ParametersProgramming Keys System Configuration Programming Example Switch to Bypass OperationSystem Configuration Parameters password protected Programming Example Change Charge Voltage to Change parameters by pressing Description of Settings Programming Parameters for Advanced Parallel OperationBattery Monitor Programming exampleOptions/Accessories Options/AccessoriesService Bypass Panel for Single Operation Options/Accessories Operating The External Service Bypass Switch Display showsSwitching from External Bypass to Normal UPS Operation Lamp indication On Servive Bypass PanelService Bypass Panel for Parallel Redundant Operation Two Parallel Systems with Service Bypass Panel Options/Accessories H002a Action Options/Accessories Lamp indication On Service Bypass Panel ActionDisplay shows Isolating One UPS for Service/Maintenance Following can be carried out on any UPSSwitching Back to Normal Parallel/Redundant Operation Intersystem Synchronization Unit Intersystem Synchronization Unit System ISU SystemIntersystem Synchronization Unit ISU Remote Display Extension of Remote Display Communication DistanceStandard Short-haul RS232 Modem Async Connections With Converter Connections Without ConverterHost DTE Remote Display DTE Pin Connections for cable from host to ME800A-R2 HostRemote Display Power Supply Remote Display CablesAlarms Communication FaultRemote Display Setting Remote Display UseHeight mm Width mm Depth mm Weight kg Isolation TransformerFM a Connecting Isolation TransformerExternal External PE Input Fuses Input Cable 120 DIN gL typesOptions/Accessories Input Input Cable Output Temp Fuses* FM Cable mm2 SignalIsolation External External PE 150 185Options/Accessories Options/Accessories Options/Accessories Options/Accessories Options/Accessories Technical Data System SpecificationsSystem Specifications Dimensions / WeightWarranty WarrantyAPC Silcon Series Limited Factory Warranty Installation Planning Data AppendixAppendix Appendix APC Corporate Fairgrounds Road West Kingston, RI How to Contact APCHow to Contact APC APC Denmark Silcon Allé DK-6000 Kolding