Before applying power to the supply, check the label on the heat sink to make certain that the supply's line voltage option agrees with the line voltage to be used. If the option does not correspond to your line voltage, refer to paragraph "LINE VOLTAGE OPTION CONVERSION" in the service section before applying power.
TURN -ON CHECKOUT PROCEDURE
a.Connect line cord to power source and turn LINE switch on.
b.Push +6V METER switch and, with no load con- nected, vary +6V VOLTAGE control over its range and check that the voltmeter responds to the control setting and the ammeter indicates zero.
c.Set the +6V VOLTAGE control to 6 volts and short the
+6V output terminal to COM (common) terminal
with an insulated test lead. The ammeter should indicate a
d.Push the +20V METER switch and turn Tracking Ratio control fully clockwise to the Fixed position. With no load connected, vary ±20V VOLTAGE control
over its range and check that the voltmeter responds to the control setting and the ammeter indi- cates zero.
e.Set the ±20V VOLTAGE control to 20 volts and
short the +20V output terminal to the COM terminal
with an insulated test lead. The ammeter should indicate a
f.Repeat steps (d) and (e) for
g.Adjust the +20V output to 20 volts. Then push
If this brief checkout procedure or later use of the supply reveals a possible malfunction, see the service information section for detailed test, troubleshooting, and adjustment pro- cedures.
OPERATION
This power supply can be operated individually or in parallel or series with another supply (see Parallel and Series Opera- tion paragraphs). All output terminals are isolated from ground. The ±20V and +6V outputs use a single common out- put terminal. This common (COM) terminal or any one of the other output terminals may be grounded to the chassis at the front panel ground terminal ( in Figure 2), or all outputs may be left floating. Loads can be connected separately between each of the 0 to ±20V output terminals and the COM terminal, or between the
tor the 0 to 40V output voltage, add the voltmeter readings of the +20V and
Tracking Ratio Control
With the Tracking Ratio control in the Fixed position, the volt- age of the
Turn the Tracking Ratio control counter clockwise out of the Fixed position to set the voltage of the
Overload Protection Circuits
+6V Current Foldback. The overload and
During the actual operation of the ±20V and +6V outputs, if a load change causes the current limit to be exceeded, the OL LED is lighted. If overload conditions occur, the ±20V supplies will protect the load by limiting the current to 0.55 A and the +6V supply will protect the load by reducing both voltage and current simultaneously along the foldback locus as shown in Figure 4. The ±20V and +6V supplies are self restoring; that is, when the overload is removed or corrected, the output voltage is automatically restored to the previously set value.
Operation Beyond Rated Output
The supply may be able to provide voltages and currents greater than its rated maximum outputs if the line voltage is at or above its nominal value. Operation can be extended up to 5% over the rated output without damage to the supply, but performance can not be guaranteed to meet specifications in