Siemens 090-010 manual Assigning authorizations, Start button security

Page 115

Industry Sector, IA&DT

Create an adjuster with the name "SCHMIDT" and the password "KLAUS".

Create a developer with the name "HUBER" and the password "FRANZ".

13.3 Assigning authorizations

Only users with operator control authorization are permitted to operate the start button and select a color mixture from the recipes.

Only adjusters are authorized to switch the operating mode to manual operation of the plant. Only developers are permitted to change or enter new recipe data records.

No access protection is required for all other functions, such as screen changes.

Start button security

Open the root screen and select the "START" button.

Under Security, select the "Operator control" authorization.

Set the check mark for Allow operator control.

SCE Training Curriculum

Page 115 of 118

To be used only at Educational and R&D Facilities

TIA Portal Module 090-010, Edition 03/2013

 

Unrestricted / © Siemens AG 2013. All Rights Reserved

SCE_EN_090-010_R1209_ WinCC Advanced with Runtime and TP700 Comfort Panel

Image 115
Contents SCE Training Curriculum for Suitable SCE Trainer Packages for these training curriculums Seite 10.4 Training objective PrefaceRequirements Hardware and software needed Professional V11 TIA Portal V11 programming software Simatic S7-300 automation systemOperator control and monitoring with WinCC PC for configuration TP700 as HMI device Project description Hardware configurationPlant description Task ConfigurationIndustry Sector, IA&DT Loading and re-saving a project template Click ’Open the project view‘ Industry Sector, IA&DT Industry Sector, IA&DT Industry Sector, IA&DT Industry Sector, IA&DT Industry Sector, IA&DT Set the check marks for Alarms Then, click Next After that, click Next Assign the names Root screen, Tank 1, Tank 2, TankSelect the system screens Then, click Next Industry Sector, IA&DT WinCC interface now opens with the root screen WinCC user interface Menu bar and buttons Project treeTools Working areaDetails view Properties windowLayout Device configuration of the TP700 Comfort Panel Setting the IP address Setting the panel as Profinet IO device Tank 2, Tank Configuring screensRoot screen TankPermanent overview area Root screenIndustry Sector, IA&DT Root screen display area Configuring screen changes Industry Sector, IA&DT Drag a graphic view to the working area of the root screen Inserting a graphic viewIndustry Sector, IA&DT Industry Sector, IA&DT Industry Sector, IA&DT Remember to save the project Tank 1 screen Industry Sector, IA&DT Industry Sector, IA&DT Tank 2 screen Tank 3 screen Testing configuration in Runtime Test the function of the buttons in all screens Loader buttons Settings on the TP700 Comfort Touch PanelSetting the date and time Setting transfer properties Assigning Profinet device names RebootTransfer mode Configuring a connection Layers Display and operating objectsBasic objects Industry Sector, IA&DT Simatic S5 Enhanced objectsConfiguring the bar view Industry Sector, IA&DT Industry Sector, IA&DT Industry Sector, IA&DT Industry Sector, IA&DT Configuring sliders Industry Sector, IA&DT Remember to save the project Configuring buttons Industry Sector, IA&DT For Single bit, select the bit position Under Animations, select the Control enableIndustry Sector, IA&DT Displaying the valve function in color Industry Sector, IA&DT Remember to save the project Testing Tank 1 in Runtime Industry Sector, IA&DT View of Tank 2 screen View of Tank 3 screen Industry Sector, IA&DT Creating a graphics list Configuring the mixer motorInserting a graphic I/O field Creating a text list Inserting a symbolic I/O field Industry Sector, IA&DT Configuring manual mode for the drain valve of the reservoir Button should be operable only in manual mode Switching the operating mode Industry Sector, IA&DT Configuring fill quantities Industry Sector, IA&DT Configuring the Start button Industry Sector, IA&DT Industry Sector, IA&DT Configuring the mixer movement Industry Sector, IA&DT Industry Sector, IA&DT Industry Sector, IA&DT Configuring text fields Configuring objects in the permanent windowConfiguring output fields Set the properties Industry Sector, IA&DT Analog alarms Configuring alarmsSpecifying the delay time Alarm window Testing alarm configuration in Runtime Adding recipes Configuring recipesSpecifying data records Configuring the Recipe input screenCreating Recipe input and Select recipe screens Industry Sector, IA&DT Configuring the Select recipe screen Configuring buttons for screen change Industry Sector, IA&DT Selecting a recipe in Runtime Entering new recipes in Runtime Setting up user groups Configuring user administrationCreating users Start button security Assigning authorizationsSecurity in recipe input Security of data record selectionOperation mode Security in operating mode selectionTesting user administration in Runtime