TOSHIBA
4.0Specifications
4.1 Standard Series Specifications (Cont'd)
| MODEL NUMBER | UE1A1A012C6 |
|
|
|
| CAPACITY | 1200 VA (0.84 kW) |
|
|
|
Input | Input voltage | Single phase, 120 Vac, +10% to |
|
|
|
| Input frequency | 45 to 65 Hz |
|
|
|
| Input capacity | 1200 VA |
|
|
|
| Input power factor | Approximate unity (0.95 to 1.0) |
|
|
|
Battery | Battery rated voltage | 60 Vdc |
|
|
|
| Battery backup time when fully charged | 5 min. at full load (**) |
| with 0.7 power factor at77° F (25° C) | 12 min. at half load (**) |
|
|
|
| Recharge time | Maximum 24 hrs to 100% (90% recharge after 8 hrs) (***) |
|
|
|
| Type of batteries | Sealed |
|
|
|
Output | Output voltage | |
|
|
|
| Output voltage regulation | Within +/- 3%, steady state |
|
|
|
| Output frequency | 50/60 Hz +/- 0.5% in |
|
|
|
| Output voltage waveform | |
|
| distortion with linear load |
| Rated load power factor | 0.7 lagging (0.6 to 1.0) |
|
|
|
| Voltage transient characteristic | +/- 8% under 100% load step change |
| Rated output current (rms) | 10.0A |
|
|
|
| Maximum output current (peak) | 30.0A |
|
|
|
| Inverter overload capacity | 150% for 30 seconds |
|
|
|
| Crest factor | 3.0 |
|
|
|
Environment | Operating temperature | 32 to 104° F (0 to 40° C), optimal at 77° F (25° C) |
| Storage temperature | |
|
|
|
| Operating humidity | 30 to 90%, no condensation |
|
|
|
| Altitude(****) | Less than 3000 ft (1000 m) above sea level |
|
|
|
| External dimensions | 8.00W x 20.38D x 10.00H in (203W x 518D x 254H mm) |
| Net weight | 43.7 lb (19.8 kg) |
|
|
|
| Acoustical noise | 50 dB at max. output, measured 3.3 ft (1 m) from front panel |
|
|
|
| Efficiency | 87% |
|
|
|
Switches | Bypass switch | Automatic bypass is provided when the run switch is in the stop |
|
| position, if a fault occurs, or if an overload occurs (transfer time is |
|
| approximately 4 mS) |
|
|
|
Interfaces | IBM (TM) AS/400 |
|
| LAN Manager | See section 6.0 for details. |
| Fault detect and input power loss |
|
| RS232 ASCII |
|
Options | Software for unattended |
|
| computer shutdown | Contact Toshiba for details on this option |
| External battery pack | Contact Toshiba for details on this option |
|
|
|
(*) Output capacity reduced when input voltage is between
(**)Battery backup time may vary depending on the operating conditions including ambient temperature at the installation site.
(***) An initial charge time of 24 hrs. is necessary to obtain proper battery performance level before unit is used for battery backup.
(****) Above 3000 ft (1000 m), output capacity reduced.
4 - 2