Toshiba 1500 SERIES operation manual DB25 Connector Pinout, Pin Symbol Description

Page 24

TOSHIBA

6.0UPS Control Interface

6.1DB25 Connector Pinout

RS-232C serial communication and Dry Contacts are both standard features available through a DB25 female connector located on the back panel of the UPS (see Section 9.1). The RS-232C serial communication interface allows control of the UPS from a personal computer running special Toshiba software. The computer is connected to the UPS through a serial RS-232C communication port. The Dry Contact interface is available as open or closed contacts. An adapter is available from Toshiba for splitting the RS-232C and Dry Contact interfaces into two separate DB9 connectors. Contact Toshiba for more information on this option. The following chart shows the pin assignments for the DB25 connector.

RS-232C Serial Interface

Dry Contacts

Pin

Symbol

Description

1

0V

Supply used by Slide-In Options cards (-)

2

+9V

Supply used by Slide-In Options cards (+)

3

RXD_UPS

UPS receive line

4

TXD_UPS

UPS transmit line

5

TXD_AUX

Auxiliary transmit line

6

RXD_AUX

Auxiliary receive line

7

 

(not used)

8

SNMPSIG1

SNMP option card function

9

RS_Common

Common line for RS-232C communication

10

SNMPSIG2

SNMP option card function

11

DTR

UPS data terminal ready

12

DSR

UPS data set ready

13

RTS

UPS request to send

14

CTS

UPS clear to send

15

 

(not used)

16

Dry_Common

Common line for Dry Contact signals

17

Backup_O

Open during Battery Backup

18

Backup_C

Closed during Battery Backup

19

Low_Battery

Closed during Low Battery

20

Inverter

Closed during On-Line mode

21

Bypass

Closed during Bypass mode

22

Fault

Closed during Fault

23

 

(not used)

24

SD_Signal

Shutdown command signal line

25

SD_Common

Shutdown command common line

 

 

 

6 - 1

Image 24
Contents Series Page Toshiba Contents Section Contents Contd Troubleshooting ProceduresPreventive Maintenance/Parts Replacement External Dimensions/Panel Layout/Shipping WeightsIntroduction General Safety Instructions Important Safety Instructions Model Capacity Manufacturer Type QuantityWhen working with batteries ViiInstructions Importantes Concernant LA Sécurité ViiiPower Backup Power ConditioningTheory of Operation Application and UseInspection of the new UPS equipment After UncratingStorage of UPS equipment AvoidInstallation Precautions General Prestart Precautions Operating Precautions CautionSpecifications Standard Series Specifications Model NumberSpecifications Standard Series Specifications Contd UE1A1A012C6UE1A1A006C6T UE1A1A008C6T UE1A1A010C6T Operation Modes AC Input Mode normal operation Power flow in AC input modeBattery Backup Mode Power flow in battery backup modeOperation Modes Circuit-bypass mode Power flow in circuit-bypass modeSystem Protection Features Operation Monitoring Visual Indicator Functions Audible Alarm FunctionsVisual and Audible Indicator Function Chart Condition Cause Indicators Operation PatternUPS On-Line Mode Display Front Panel LayoutBattery Recharging Rated battery voltagesBattery Backup Time Battery Low Voltage TolerancesBattery Check Function System ResetDB25 Connector Pinout Pin Symbol DescriptionRS-232C Serial Communication Interface UPS Shutdown via RS-232CDry Contact Interface Non-Fatal Fault Mode Non-Fatal Fault Mode Display ChartFatal Fault Mode Fatal Fault Mode Display ChartPreventive and Scheduled Maintenance/Parts Replacement Preventive MaintenanceFuse Rating Chart Fuse ratingExternal Dimensions/Shipping Weights/Panel Layout External DimensionsPanel Layout Shipping Weights Shipping WeightPounds Kilograms Toshiba International Corporation