8.0Preventive and Scheduled Maintenance/Parts Replacement

8.1Preventive Maintenance

Toshiba's 1500 and 1500 Plus Series of uninterruptible power systems have been designed to provide years of trouble-free operation requiring a minimum of preventive maintenance.

The best preventive measure that the UPS user can take is to keep the area around the unit, particularly the air inlet vents, clean and free of moisture and dust accumulations. If the atmosphere of the installation site is very dusty, use a vacuum cleaner to periodically remove dust accumulations from the system. Schedule authorized service centers to perform internal parts inspections annually.

CAUTION

WARNING

Before performing any maintenance, the technician should be familiar with and follow the important safety instructions located on pages vi and vii.

Proper maintenance of the battery system of this unit by a qualified service technician is essential to the safety and reliability of your UPS system. Refer to service manual.

8.2Parts Replacement

The following list shows intervals for periodic maintenance and replacement of certain UPS parts.

1)Batteries: VRLA batteries are maintenance free with respect to electrolyte only. The charging voltage, temperature, performance and connection resistance must be monitored periodically. Necessary corrective actions must be made in order to assure safe reliable power is supplied by the UPS. The aforementioned items affect the life of batteries, so replacement should be done once every 3 to 5 years at a minimum. All of the batteries must be replaced at the same time.

Quarterly maintenance

a)Visual checks

1)Leakage

2)Corrosion on positive terminal

b)Check battery temperature at the negative terminal.

c)Measure and record the system float charging voltage.

d)Measure and record the individual units float charging voltage.

Semi-Annual maintenance

a)Repeat the quarterly checks.

b)Perform a 10 second high rate (e.g. 100 amp) load test on the individual batteries.

c)Optionally test for the purpose of trending the battery over time.

d)Re-torque all inter-battery connecting hardware (if applicable).

e)Perform inter-battery connector resistance checks.

2)Aluminum electrolytic capacitors: Replace once every 5 years.

3)Fuses: Replace once every 7 years (see output fuse rating chart on the following page).

4)Cooling fan: Replace once every 3 years.

8 - 1

Image 28
Contents Series Page Toshiba Contents Section Contents Contd Troubleshooting ProceduresPreventive Maintenance/Parts Replacement External Dimensions/Panel Layout/Shipping WeightsIntroduction General Safety Instructions Important Safety Instructions Model Capacity Manufacturer Type QuantityWhen working with batteries ViiInstructions Importantes Concernant LA Sécurité ViiiPower Backup Power ConditioningTheory of Operation Application and UseInspection of the new UPS equipment After UncratingStorage of UPS equipment AvoidInstallation Precautions General Prestart Precautions Operating Precautions CautionSpecifications Standard Series Specifications Model NumberSpecifications Standard Series Specifications Contd UE1A1A012C6UE1A1A006C6T UE1A1A008C6T UE1A1A010C6T Operation Modes AC Input Mode normal operation Power flow in AC input modeBattery Backup Mode Power flow in battery backup modePower flow in circuit-bypass mode Operation Modes Circuit-bypass modeSystem Protection Features Operation Monitoring Visual Indicator Functions Audible Alarm FunctionsVisual and Audible Indicator Function Chart Condition Cause Indicators Operation PatternUPS On-Line Mode Display Front Panel LayoutBattery Recharging Rated battery voltagesBattery Backup Time Battery Low Voltage TolerancesBattery Check Function System ResetDB25 Connector Pinout Pin Symbol DescriptionUPS Shutdown via RS-232C RS-232C Serial Communication InterfaceDry Contact Interface Non-Fatal Fault Mode Non-Fatal Fault Mode Display ChartFatal Fault Mode Fatal Fault Mode Display ChartPreventive and Scheduled Maintenance/Parts Replacement Preventive MaintenanceFuse Rating Chart Fuse ratingExternal Dimensions/Shipping Weights/Panel Layout External DimensionsShipping Weight Panel Layout Shipping WeightsPounds Kilograms Toshiba International Corporation