Toshiba 1500 SERIES Battery Backup Time, Battery Low Voltage Tolerances, Battery Check Function

Page 23

TOSHIBA

5.0Operating the UPS

5.7Battery Backup Time

The UPS unit's batteries provide about 5-12 minutes of back-up time depending on the capacity of the UPS. These times are valid when a unit is operating under full load. When the units are operating at half load, the batteries can power the load equipment about 3 times longer. The exact length of these times will depend on the UPS model used, condition of the batteries, amount of load, temperature and other variables. See battery backup time in the standard specifications Sections 4.1 through 4.2.

5.8Battery Low Voltage Tolerances

Excessive discharge will cause the UPS unit's battery voltage to drop. The chart shown below lists the voltage level at which each UPS unit's low-voltage alarm will sound and also at what level the low-voltage condition will cause the unit to automatically shut down.

UPS Capacity

600VA

800VA

1000VA

1200VA

600VA

800VA

1000VA

 

 

 

 

 

Plus

Plus

Plus

 

 

 

 

 

 

 

 

Nominal voltage

60.0

60.0

60.0

60.0

60.0

60.0

60.0

in Vdc

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Alarm voltage

52.8

52.8

52.8

52.8

52.8

52.8

52.8

in Vdc

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Shutdown voltage

48.0

48.0

48.0

48.0

48.0

48.0

48.0

 

 

 

 

 

 

 

 

5.9Battery Check Function

Part of the UPS start-up procedure is an automatic 'Battery Check' to see if a problem exists in the battery circuit. When the UPS is started it will begin operation in the bypass mode. An automatic voltage level test of the batteries is made while operating in the bypass mode for five seconds. A failure of this first test will activate visual and audible alarms (see section 5.3.3 "battery problem"). If this test is passed, then the UPS will auto- transfer from bypass mode to on line operating mode. A ten second automatic voltage check of the batteries is made after the UPS has auto-transferred from bypass to on line mode. Normal on line operation continues if the second test is passed. If the second test fails, then the "Fault" LED will flash and up to three additional automatic battery voltage checks are made at 3 hour intervals while the inverter continues to operate. If the batteries are found to be normal during one of these three tests then the "Fault" LED will stop flashing and normal inverter operation will continue. A failure of the third and final check will activate visual and audible alarms (see section 5.3.3 "battery problem") causing an auto-transfer back to bypass. If the batteries are indicated "bad" then

STOP the UPS and allow a 24 hour charge on the batteries before restarting.

5.10System Reset

The UPS is reset by moving the STOP/RUN switch from "run" to "stop" and then back to "run". Use the reset procedure to transfer from bypass back to inverter after a fault occurs. Some faults may only be cleared by shutting down the UPS, waiting for all LED's on the front panel to go off, and then restarting the UPS.

5 - 6

Image 23
Contents Series Page Toshiba Contents Section External Dimensions/Panel Layout/Shipping Weights Contents ContdTroubleshooting Procedures Preventive Maintenance/Parts ReplacementIntroduction General Safety Instructions Model Capacity Manufacturer Type Quantity Important Safety InstructionsVii When working with batteriesViii Instructions Importantes Concernant LA SécuritéApplication and Use Power BackupPower Conditioning Theory of OperationAvoid Inspection of the new UPS equipmentAfter Uncrating Storage of UPS equipmentInstallation Precautions General Operating Precautions Caution Prestart PrecautionsModel Number Specifications Standard Series SpecificationsUE1A1A012C6 Specifications Standard Series Specifications ContdUE1A1A006C6T UE1A1A008C6T UE1A1A010C6T Power flow in battery backup mode Operation Modes AC Input Mode normal operationPower flow in AC input mode Battery Backup ModeSystem Protection Features Operation Modes Circuit-bypass modePower flow in circuit-bypass mode Indicators Operation Pattern Operation Monitoring Visual Indicator Functions Audible Alarm Functions Visual and Audible Indicator Function Chart Condition CauseFront Panel Layout UPS On-Line Mode DisplayRated battery voltages Battery RechargingSystem Reset Battery Backup TimeBattery Low Voltage Tolerances Battery Check FunctionPin Symbol Description DB25 Connector PinoutDry Contact Interface RS-232C Serial Communication InterfaceUPS Shutdown via RS-232C Non-Fatal Fault Mode Display Chart Non-Fatal Fault ModeFatal Fault Mode Display Chart Fatal Fault ModePreventive Maintenance Preventive and Scheduled Maintenance/Parts ReplacementFuse rating Fuse Rating ChartExternal Dimensions External Dimensions/Shipping Weights/Panel LayoutPounds Kilograms Panel Layout Shipping WeightsShipping Weight Toshiba International Corporation