Toshiba 1500 Operation Monitoring Visual Indicator Functions, Audible Alarm Functions

Page 20

TOSHIBA

5.0Operating the UPS

5.3Operation Monitoring

5.3.1Visual Indicator Functions

The following LED (light emitting diode) indicators are located on the front panel (see Section 9.2 "Panel Layout"). Refer to these lamps for visual information about the operating condition of the UPS (see Section 5.3.3 "Visual and Audible Indicator Function Chart").

1)AC Input: This green LED lights when normal ac input power is being supplied to the UPS unit.

2)On Line: This green LED lights when the inverter output voltage is normal.

3)Fault: This red LED lights when an abnormal operating condition is detected. Operation of the unit's inverter is inhibited until the fault has been corrected and the system reset (see Section 5.10 "System Reset").

5.3.2Audible Alarm Functions

The UPS is equipped with an audible alarm system which activates under various operating conditions. Sound patterns are used to indicate these conditions (see Section 5.3.3 "Visual and Audible Indicator Function Chart"). Alarms for the battery backup mode or low battery voltage will stop automatically when AC input voltage is restored. Alarms for a fault condition will continue to sound until the UPS has been reset (see Section 5.10 "System Reset").

5.3.3Visual and Audible Indicator Function Chart

Condition

Cause

 

 

Audible

Visual

UPS

 

 

 

Alarm

 

 

 

 

 

Indicators

Operation

 

 

 

 

Pattern

 

 

 

 

 

 

Overcurrent (OC)

Problem in chopper or

 

 

 

 

 

 

 

1) "Fault" LED

1) Auto

 

inverter circuit.

 

 

 

 

 

 

 

is ON

transfer

 

 

 

 

 

 

 

 

 

2) "On Line"

to bypass

 

 

 

 

 

 

 

 

 

DC Bus Overvoltage (DCOV)

DC Bus > 115% of rated.

 

 

 

 

 

 

ON

LED is OFF

2) Chopper

 

 

 

 

 

 

 

 

OFF

3) "AC Input"

stopped

Ouput Overvoltage (OV)

V out > 110% of rated.

 

 

 

 

 

 

 

 

2s

1.5s

LED is ON

3) Inverter

 

 

 

 

 

stopped

Undervoltage (UV)

V out < 85% of rated.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Overheat (OH)

Heatsink exceeds 90º C.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Overload (OL)

Output current and over-

 

 

 

 

 

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

load specifications have

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

been exceeded.

 

 

.5s

.5s

 

 

 

 

 

 

 

 

 

 

 

 

 

Battery problem

Problem in battery

 

 

 

 

 

 

ON

1) “Replace

1) Bypass or

 

 

 

 

 

 

OFF

 

circuit.

 

 

 

 

 

 

Battery”

On-Line

 

 

 

 

1s

2s

LED is ON

mode.

 

 

 

 

 

 

 

 

 

 

 

Normal battery backup

Loss of AC power

 

 

 

 

 

 

ON

1) "Fault" LED

1) Chopper

operation

 

 

 

 

 

 

 

OFF

is OFF

running

 

 

 

 

 

 

 

 

2) "On Line"

2) Inverter

 

 

 

 

5s

70s

LED is ON

running

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3) "AC Input"

 

 

 

 

 

 

 

 

 

ON

 

Low battery voltage

Battery voltage too low,

 

 

 

 

 

 

 

LED is OFF

 

 

 

 

 

 

 

OFF

 

 

 

Shutdown imminent.

 

 

 

 

 

 

 

 

 

 

 

1s

.5s

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5 - 3

Image 20
Contents Series Page Toshiba Contents Section Contents Contd Troubleshooting ProceduresPreventive Maintenance/Parts Replacement External Dimensions/Panel Layout/Shipping WeightsIntroduction General Safety Instructions Important Safety Instructions Model Capacity Manufacturer Type QuantityWhen working with batteries ViiInstructions Importantes Concernant LA Sécurité ViiiPower Backup Power ConditioningTheory of Operation Application and UseInspection of the new UPS equipment After UncratingStorage of UPS equipment AvoidInstallation Precautions General Prestart Precautions Operating Precautions CautionSpecifications Standard Series Specifications Model NumberSpecifications Standard Series Specifications Contd UE1A1A012C6 UE1A1A006C6T UE1A1A008C6T UE1A1A010C6T Operation Modes AC Input Mode normal operation Power flow in AC input modeBattery Backup Mode Power flow in battery backup modeSystem Protection Features Operation Modes Circuit-bypass modePower flow in circuit-bypass mode Operation Monitoring Visual Indicator Functions Audible Alarm FunctionsVisual and Audible Indicator Function Chart Condition Cause Indicators Operation PatternUPS On-Line Mode Display Front Panel LayoutBattery Recharging Rated battery voltagesBattery Backup Time Battery Low Voltage TolerancesBattery Check Function System ResetDB25 Connector Pinout Pin Symbol DescriptionDry Contact Interface RS-232C Serial Communication InterfaceUPS Shutdown via RS-232C Non-Fatal Fault Mode Non-Fatal Fault Mode Display ChartFatal Fault Mode Fatal Fault Mode Display ChartPreventive and Scheduled Maintenance/Parts Replacement Preventive MaintenanceFuse Rating Chart Fuse ratingExternal Dimensions/Shipping Weights/Panel Layout External DimensionsPounds Kilograms Panel Layout Shipping WeightsShipping Weight Toshiba International Corporation