4.0Specifications
4.2 Plus Series Specifications (w/ isolation transformer)
| MODEL NUMBER | UE1A1A006C6T | UE1A1A008C6T | UE1A1A010C6T |
|
|
|
|
|
| CAPACITY | 600 VA (0.42 kW) | 800 VA (0.56 kW) | 1000 VA (0.7 kW) |
|
|
|
|
|
Input | Input voltage | Single phase, 120 Vac, +10% to |
| |
|
|
|
|
|
| Input frequency | 45 to 65 Hz |
|
|
|
|
|
|
|
| Input capacity | 600 VA | 800 VA | 1000 VA |
|
|
|
|
|
| Input power factor | Approximate unity (0.95 to 1.0) |
| |
|
|
|
|
|
Battery | Battery rated voltage | 60 Vdc |
|
|
|
|
|
|
|
| Battery backup time when fully charged | 12 min. at full load (**) | 8 min. at full load (**) | 7 min. at full load (**) |
| with 0.7 power factor at 77° F (25° C) | 30 min. at half load (**) | 20 min. at half load (**) | 18 min. at half load (**) |
|
|
|
|
|
| Recharge time | Maximum 24 hrs to 100% (90% recharge after 8 hrs) (***) | ||
|
|
|
|
|
| Type of batteries | Sealed |
|
|
|
|
|
|
|
Output | Output voltage |
|
| |
|
|
|
| |
| Output voltage regulation | Within +/- 3%, steady state |
| |
|
|
| ||
| Outputfrequency(*****) | 50/60 Hz +/- 0.5% in | ||
|
|
| ||
| Output voltage waveform | |||
|
| distortion with linear load |
| |
|
|
|
|
|
| Common mode | Less than 0.5V peak |
|
|
|
|
|
|
|
| Normal mode | Less than 10V peak |
|
|
|
|
|
|
|
| Rated load power factor | 0.7 lagging (0.6 to 1.0) |
|
|
|
|
|
| |
| Voltage transient characteristic | +/- 8% under 100% load step change |
| |
| Rated output current (rms) | 5.0A | 6.7A | 8.3A |
| Maximum output current (peak) | 15.0A | 20.0A | 25.0A |
|
|
|
|
|
| Inverter overload capacity | 150% for 30 seconds |
|
|
|
|
|
|
|
| Crest factor | 3.0 |
|
|
|
|
| ||
Environment | Operating temperature | 32 to 104° F (0 to 40° C), optimal at 77° F (25° C) | ||
|
|
|
| |
| Storage temperature |
| ||
|
|
|
| |
| Operating humidity | 30 to 90%, no condensation |
| |
|
|
|
| |
| Altitude(****) | Less than 3000 ft (1000 m) above sea level |
| |
|
|
| ||
| External dimensions | 8.00W x 20.38D x 10.00H in (203W x 518D x 254H mm) | ||
| Net weight | 57.5 lb (26.1 kg) | 57.5 lb (26.1 kg) | 60.9 lb (27.6 kg) |
|
|
|
|
|
| Acoustical noise | 50 dB at max. output, measured 3.3 ft (1 m) from front panel | ||
|
|
|
|
|
| Efficiency | 83% | 83% | 85% |
|
|
|
|
|
Switches | Bypass switch | Automatic bypass is provided when the run switch is in the stop | ||
|
| position, if a fault occurs, or if an overload occurs (transfer time is | ||
|
| approximately 4 msec) |
|
|
|
|
|
|
|
Interfaces | IBM (TM) AS/400 |
|
|
|
| LAN Manager | See section 6.0 for details. |
| |
| Fault detect and input power loss |
|
|
|
| RS232 ASCII |
|
|
|
|
|
|
|
|
Options | Software for unattended |
|
|
|
| computer shutdown | Contact Toshiba for details on this option |
| |
|
|
|
| |
| External battery pack | Contact Toshiba for details on this option |
| |
|
|
|
|
|
(*) Output capacity reduced when input voltage is between
(**)Battery backup time may vary depending on the operating conditions including ambient temperature at the installation site.
(***) An initial charge time of 24 hrs. is necessary to obtain proper battery performance level before unit is used for battery backup.
(****) Above 3000 ft (1000 m), output capacity reduced. (*****) Output voltage and capacity derated for 50 Hz output.
4 - 3