Toshiba 1500 SERIES operation manual Non-Fatal Fault Mode Display Chart

Page 26

TOSHIBA

7.0Troubleshooting Procedures

Faults are those abnormal conditions that can occur and cause the unit to shutdown normal operation. The faults are detected by the protection circuitry (see System Protection Features Section 5.2) in the unit. The UPS “Fault” lamp will light red. "Troubleshooting" involves monitoring the bar graph lamps on the front panel and then interpreting the readout by using the fault mode display charts.

7.1Non-Fatal Fault Mode

Non-fatal faults may or may not cause the unit to shut down. These faults normally will cause the UPS to transfer to bypass mode. Use "System Restart" procedures (see Section 5.10) to transfer the UPS back to “On Line” mode. Use the following chart to decode the display. All non-fatal faults will cause the red “Fault” LED to flash.

Non-Fatal Fault Mode Display Chart

Fault

Display status

Probable cause

Corrective action

 

 

 

Remove cause of

Output low

 

Inverter fault or short

short circuit. If none is

voltage

 

circuit in UPS output

found, contact your

 

 

 

Toshiba service

 

 

 

representative.

Output

 

Resonance with load

Remove load

overvoltage

 

equipment

equipment one piece

 

 

 

at a time.

DC

 

Chopper fault

Contact your Toshiba

undervoltage

 

 

service representative.

 

 

 

Check for airflow

Cooling fin

 

Cooling fan outage or

restriction. If none is

overheating

 

closed cooling airflow

found, contact your

 

 

path

Toshiba service

 

 

 

representative.

 

 

Battery damaged or

 

Battery

 

something wrong in the

Contact your Toshiba

problem

 

battery circuit (battery may

service representative.

 

 

not be connected)

 

Output

 

Capacity of load

Review UPS rating

overload

 

equipment to high

or reduce load

 

 

 

equipment.

7 - 1

Image 26
Contents Series Page Toshiba Contents Section Preventive Maintenance/Parts Replacement Contents ContdTroubleshooting Procedures External Dimensions/Panel Layout/Shipping WeightsIntroduction General Safety Instructions Important Safety Instructions Model Capacity Manufacturer Type QuantityWhen working with batteries ViiInstructions Importantes Concernant LA Sécurité ViiiTheory of Operation Power BackupPower Conditioning Application and UseStorage of UPS equipment Inspection of the new UPS equipmentAfter Uncrating AvoidInstallation Precautions General Prestart Precautions Operating Precautions CautionSpecifications Standard Series Specifications Model NumberSpecifications Standard Series Specifications Contd UE1A1A012C6UE1A1A006C6T UE1A1A008C6T UE1A1A010C6T Battery Backup Mode Operation Modes AC Input Mode normal operationPower flow in AC input mode Power flow in battery backup modeSystem Protection Features Operation Modes Circuit-bypass modePower flow in circuit-bypass mode Visual and Audible Indicator Function Chart Condition Cause Operation Monitoring Visual Indicator FunctionsAudible Alarm Functions Indicators Operation PatternUPS On-Line Mode Display Front Panel LayoutBattery Recharging Rated battery voltagesBattery Check Function Battery Backup TimeBattery Low Voltage Tolerances System ResetDB25 Connector Pinout Pin Symbol DescriptionDry Contact Interface RS-232C Serial Communication InterfaceUPS Shutdown via RS-232C Non-Fatal Fault Mode Non-Fatal Fault Mode Display ChartFatal Fault Mode Fatal Fault Mode Display ChartPreventive and Scheduled Maintenance/Parts Replacement Preventive MaintenanceFuse Rating Chart Fuse ratingExternal Dimensions/Shipping Weights/Panel Layout External DimensionsPounds Kilograms Panel Layout Shipping WeightsShipping Weight Toshiba International Corporation