6.7UPS Manual Test
Manual UPS and Battery tests may be performed from the UPS configuration screen. Tests may be performed when the battery is not being charged.
To run the battery test scroll to the “Manual Bat Test” parameter press the Enter button twice.
**Note: In order for the UPS to operate normally, Manual Bypass should always be set to OFF because the load will not be protected by the unit when Manual Bypass is ON.
***Note: Turn off the UPS and keep the AC power on to use the Generator function. (go to normal mode for \Generator\OFF).
6.8Interpreting UPS Messages
Troubleshooting procedures described here provide instructions to be used to isolate UPS malfunctions.
Start the troubleshooting procedure in the event of a control panel alarm.
6.9Audible Alarms
•While operating on battery power (ON BAT LED is on) the UPS will beep once at
•While operating on battery power and the battery power is low (ON BAT LED is flashing) the UPS will beep twice at
•In the event of an internal fault with an active alarm (ALARM LED is on), the UPS will provide a constant audible alarm and display an error message on the LCD display.
•While operating in the Bypass mode (BYPASS LED is on) the UPS will not beep.
6.10 Silencing an Alarm
With the exception of a LOW BATTERY Alarm, pressing any of the front panel buttons will turn off the alarm. Select Silent Alarm Mode to disable all audible alarms.
21