6.11 Troubleshooting
Displayed on LCD | Audible Alarm | Alarm Description | What You Should Do |
Output Overload | Two Beeps/sec | The UPS is overloaded (in | Remove loads from the UPS; least to |
|
| Line Mode). More power | most critical. If this solves the |
|
| required than the UPS can | problem, the UPS will return to |
|
| provide. The UPS operates | normal operation. |
|
| in bypass. |
|
|
|
|
|
Battery Test | No Beeps | Battery test active. | No action needed. |
|
|
| User Notification only. |
|
|
|
|
Constant Beep | Overcharged Batteries. | Turn off loads. Turn off UPS. | |
|
|
| Call service @ |
Low Battery | 2 Beeps/5 sec | UPS operating on Battery | The unit will restart |
|
| Power and will shut down | Automatically when acceptable |
|
| soon due to low battery | power returns. |
|
| voltage. |
|
1 Beep/5 sec | UPS operating on Battery | Save your data and perform a | |
|
| Power. | controlled shutdown. |
Charger Failure | Constant Beep | Failed Charger. | Call service @ |
|
|
|
|
Constant Beep | High ambient | Ensure that the UPS fans and | |
|
| Temperature. | vents are not blocked, and that |
|
|
| the ambient temp. is < 40° C. If |
|
|
| problem persists call service @ |
|
|
| |
Output Short | Constant Beep | Output short circuit. | Call service @ |
High output Voltage | Constant Beep | High output voltage. | Call service @ |
Low Output Voltage | Constant Beep | Low output voltage. | Call service @ |
|
|
|
|
Bus Fault | 2 Beeps/sec | High internal DC bus | Turn off loads. Turn off UPS. |
|
| Voltage. | Call service @ |
Site Wiring Fault | 1 Beep/sec | Voltage detected between | UPS main connector wrong |
|
| neutral and ground. | polarity. Rotate the connector |
|
|
| |
|
|
| installed to main supply without |
|
|
| ground. See section 4.4 for |
|
|
| information on how to disable |
|
|
| the Site wiring alarm. |
Line Abnormal | 1 Beep/sec | Wrong AC Line backed |
|
up during auto restart. |
| ||
|
|
|
22