Siemens SED2 manual AOP Start-Up & Initialization

Page 17

AOP Start-Up & Initialization

4.Use and to scroll through the parameters and to highlight Command Source P0700. Press to confirm the selection and the cursor advances to the parameter index.

Use and to scroll through the indexes for P0700 and to highlight P0700[1] (index 1). Press to confirm the selection and the cursor advances to the parameter value.

Use and to set P0700[1]=4 (USS on BOP/AOP local link). Press to confirm the setting and the cursor returns to the parameter.

5.Use and to scroll through the parameters and to highlight Selection of Frequency Setpoint P1000. Press to confirm the selection and the cursor advances to the parameter index.

Use and to scroll through the indexes for P1000 and to highlight P1000[1] (index 1). Press to confirm the selection and the cursor advances to the parameter value.

Use and to set P1000[1]=1 (motor potentiometer [MOP] setpoint). Press to confirm the setting and the cursor returns to the parameter.

6.Use and to scroll through the parameters and to highlight Commissioning parameter P0010. Press to confirm the selection and the cursor advances to the parameter value.

Use and to set P0010[0]=0 (Ready) to exit the quick commissioning mode. Press to confirm the setting and the cursor returns to the parameter.

7.Use and to scroll through the parameters and to highlight USS Telegram Off Time P2014. Press to confirm the selection and the cursor advances to the parameter index.

Use and to scroll through the indexes for P2014 and to highlight P2014[1] (index 1, Serial Interface BOP Link). Press to confirm the selection and the cursor advances to the parameter value.

Use and to set P2014[1]=5000 (USS on BOP/AOP local link) to prevent unexpected drive operation. In this mode, removal of the AOP from the SED2 VFD causes a timeout to occur in 5 seconds. Press to confirm the setting and the cursor returns to the parameter.

8.Press to return to r0000. Press to display the standard (operate) screen.

9.Press to switch the SED2 to hand mode.

10.Press to start the SED2.

11.Use to increase the output; Use to decrease the output.

Siemens Building Technologies, Inc.

9

Image 17
Contents SED2 Advanced Operator Panel AOP Page Rev , September SED2 AOP Operating InstructionsPage Service Statement European Machinery Directive European Low Voltage DirectiveEuropean EMC Directive Underwriters LaboratoriesTable of Contents AOP Faults & Warnings AOP Setup & ConfigurationManual Organization How to Use this ManualNotation Symbol Meaning Where To Send CommentsManual Notations Reference DocumentsAOP Menu Structure AOP OverviewMain Menu Local and Master Modes Local 1 DriveKey Function Functional Description Key FunctionsAOP Overview Important Notes Power-on and InitializationAOP Start-Up & Initialization Start Help Language SelectionMemory Limitation To Delete a LanguageDescription Quick CommissioningMenu Item AOP Start-Up & Initialization Stopped Running Fault Inhibit AOP Applications Single Drive Control Using the AOPNetwork Setup RS-485 with Panel Mounting Kit Network Setup PC Mode Editing Conventional Parameters Parameter Access LevelsEditing Parameters Editing Indexed Parameters TIP How to quickly change parameter values?Editing Internal AOP Parameter Set AOP Stored Parameter SetsEditing AOP-Stored Parameter Sets Parameter Parameter Upload UpreadUpload/Download Limitations Parameter Download Wait RequestSED2 AOP Operating Instructions AOP Operating Modes Selecting an Operating ModeOperating Mode Icon Description Operating in Local ModeOperating in Master Mode Individual Control of SED2 VFD Communications Failure Operating in Master Mode Broadcast OperationDisplaying Drive Status Verifying Drive TypeKey Timer FunctionSetting the AOP Timer Timer Function Backlighting AOP Setup & ConfigurationSetup Menu Cursor Type Screen ContrastLarge Number Display User Defined Text Welcome TextSet Time/Date Parameter Set Names$51,1 AOP ResetFault Indication/Fault Screen AOP Faults & WarningsSimultaneous Faults and Warnings Multiple FaultsSED2 VFD Fault/Warning Record P0947 Multiple WarningsSiemens Building Technologies, Inc Siemens Building Technologies AG Siemens Building Technologies, Inc