Siemens SED2 manual Parameter Upload Upread, Upload/Download Limitations

Page 24

SED2 AOP Operating Instructions

2.In the Internal mode, scroll through the list of parameter sets until the AOP parameter set appears. Press to confirm the selection.

3.Press again to select All parameters.

4.Use to access the internal AOP parameters. Internal parameters that display AOP information include:

Parameter

P0964

P8552

P8553

P8564

P8560

P8561

Description

Software Version Information

Base slave address

Default baud rate

Enable Autobaud

Battery level

Enable Backlight

Parameter

P8562

P8563

P8564

P8565

P8566

P8567

Description

Free Memory

Enable Text Scrolling

RS-232 Error count

RS-485 Error count

Null USS Responses

USS Timeouts

Parameter Upload (Upread)

CAUTION:

Upload/Download Limitations:

The AOP will normally only upload and download parameters up to and including Level 3. When copying parameter sets between VFDs, you must again complete the quick commissioning to re-adjust the motor parameters. Exit quick commissioning with P3900=3 (for only motor data).

Do not exit quick commissioning with P3900=1 or all downloaded parameters are reset to their default values.

Memory Limitation:

The delivered AOP supports five European languages: English, German, French, Spanish, and Italian. Due to internal memory limitations, you should delete one of these languages in order to upload the specified ten parameter sets that can be held on the AOP.

To Delete a Language:

Select Language from the main menu, highlight the language you want to delete, and then press and .

NOTE: Once a language has been removed, it cannot be restored.

The upload/upread procedure reads a parameter set from a SED2 VFD and stores that parameter set in the internal memory of the AOP. The AOP can read from a single SED2 VFD in local mode or from one specific SED2 VFD on a network of SED2 VFDs in master mode.

Use the following procedure to upload/upread a parameter set from a SED2 to the AOP:

16

Siemens Building Technologies

Image 24
Contents SED2 Advanced Operator Panel AOP Page SED2 AOP Operating Instructions Rev , SeptemberPage Service Statement European Low Voltage Directive European Machinery DirectiveEuropean EMC Directive Underwriters LaboratoriesTable of Contents AOP Setup & Configuration AOP Faults & WarningsHow to Use this Manual Manual OrganizationWhere To Send Comments Notation Symbol MeaningManual Notations Reference DocumentsAOP Overview AOP Menu StructureMain Menu Local and Master Modes Local 1 DriveKey Functions Key Function Functional DescriptionAOP Overview Power-on and Initialization AOP Start-Up & InitializationImportant Notes Language Selection Start HelpMemory Limitation To Delete a LanguageQuick Commissioning Menu ItemDescription AOP Start-Up & Initialization Stopped Running Fault Inhibit Single Drive Control Using the AOP Network Setup RS-485 with Panel Mounting KitAOP Applications Network Setup PC Mode Parameter Access Levels Editing ParametersEditing Conventional Parameters TIP How to quickly change parameter values? Editing Indexed ParametersAOP Stored Parameter Sets Editing AOP-Stored Parameter SetsEditing Internal AOP Parameter Set Parameter Upload Upread Upload/Download LimitationsParameter Wait Request Parameter DownloadSED2 AOP Operating Instructions Selecting an Operating Mode Operating ModeAOP Operating Modes Operating in Local Mode Operating in Master Mode Individual Control of SED2 VFDIcon Description Operating in Master Mode Broadcast Operation Communications FailureDisplaying Drive Status Verifying Drive TypeTimer Function Setting the AOP TimerKey Timer Function AOP Setup & Configuration Setup MenuBacklighting Screen Contrast Large Number DisplayCursor Type Welcome Text User Defined TextParameter Set Names Set Time/DateAOP Reset $51,1AOP Faults & Warnings Fault Indication/Fault ScreenMultiple Faults Simultaneous Faults and WarningsSED2 VFD Fault/Warning Record P0947 Multiple WarningsSiemens Building Technologies, Inc Siemens Building Technologies, Inc Siemens Building Technologies AG