Siemens SED2 manual AOP Start-Up & Initialization, Important Notes, Power-on and Initialization

Page 14

SED2 AOP Operating Instructions

AOP Start-Up & Initialization

Important Notes

CAUTION:

You can mount or remove the AOP while power is applied to the SED2 VFD.

You must set Command Source P0700[1]=4 (USS on BOP link or AOP) before the AOP can start or stop an attached SED2 VFD.

On setting the AOP as the command source, you must set USS Telegram Off Time for Serial Interface BOP Link P2014[1]=5000 (5 seconds) to prevent unexpected drive operation. In this mode, removal of the AOP from the SED2 VFD causes a timeout to occur in 5 seconds.

On setting the AOP as the command source, the drive control buttons (, , , and ) can control the drive at all times.

NOTES:

Parameter editing (bit field indicator) — When editing a bit-field type parameter, the AOP increments the display value as a binary number.

Inhibit — When the AOP displays ‘Inhibit’, the SED2 VFD is in an inhibit mode of operation as reported by the USS message. This inhibit status clears when the SED2 VFD receives a valid start/stop command from the AOP. On first power-up, send an OFF1 command to the SED2 before trying to run the VFD; this must also be done when the VFD is under Automatic Timer Control.

Power-on and Initialization

1.On initial power-up, the AOP performs internal self tests and displays a welcome screen.

2.After establishing initial AOP-to-SED2 VFD communications, the Start Help screen(s) appear. If the current AOP display language is acceptable, continue with the Start Help section.

If you need to change the current AOP display language, continue with the Language Selection section.

6

Siemens Building Technologies

Image 14
Contents SED2 Advanced Operator Panel AOP Page SED2 AOP Operating Instructions Rev , SeptemberPage Service Statement European EMC Directive European Low Voltage DirectiveEuropean Machinery Directive Underwriters LaboratoriesTable of Contents AOP Setup & Configuration AOP Faults & WarningsHow to Use this Manual Manual OrganizationManual Notations Where To Send CommentsNotation Symbol Meaning Reference DocumentsMain Menu Local and Master Modes AOP OverviewAOP Menu Structure Local 1 DriveKey Functions Key Function Functional DescriptionAOP Overview Important Notes Power-on and InitializationAOP Start-Up & Initialization Memory Limitation Language SelectionStart Help To Delete a LanguageDescription Quick CommissioningMenu Item AOP Start-Up & Initialization Stopped Running Fault Inhibit AOP Applications Single Drive Control Using the AOPNetwork Setup RS-485 with Panel Mounting Kit Network Setup PC Mode Editing Conventional Parameters Parameter Access LevelsEditing Parameters TIP How to quickly change parameter values? Editing Indexed ParametersEditing Internal AOP Parameter Set AOP Stored Parameter SetsEditing AOP-Stored Parameter Sets Parameter Parameter Upload UpreadUpload/Download Limitations Wait Request Parameter DownloadSED2 AOP Operating Instructions AOP Operating Modes Selecting an Operating ModeOperating Mode Icon Description Operating in Local ModeOperating in Master Mode Individual Control of SED2 VFD Displaying Drive Status Operating in Master Mode Broadcast OperationCommunications Failure Verifying Drive TypeKey Timer FunctionSetting the AOP Timer Timer Function Backlighting AOP Setup & ConfigurationSetup Menu Cursor Type Screen ContrastLarge Number Display Welcome Text User Defined TextParameter Set Names Set Time/DateAOP Reset $51,1AOP Faults & Warnings Fault Indication/Fault ScreenSED2 VFD Fault/Warning Record P0947 Multiple FaultsSimultaneous Faults and Warnings Multiple WarningsSiemens Building Technologies, Inc Siemens Building Technologies, Inc Siemens Building Technologies AG