SED2 AOP Operating Instructions
2.Press to confirm the selected operating mode (press to return to the main menu.)
NOTE: To exit an operating mode, either follow the
Operating in Local Mode
On initial
Operating in Master Mode
(Individual Control of SED2 VFD)
In Master mode, the AOP can control up to 31 SED2 drives that connect in a
Control of the SED2 drives can be individually or by broadcast method.
1.In master mode, selecting Operate from the main menu displays an operation screen.
2.Use and to select a slave SED2 VFD. A
NOTE: To configure SED2 VFDs for network operation, set Command Source P0700[1]=5 (USS on Com link), set USS Telegram Off Time for Serial Interface Com Link P2014[0]=5000, and USS Address for Serial Interface Com Link P2011[0]=a unique number for each drive on the network.
Icon
Description
F
A
U
Indicates the SED2 VFD is active and communicating.
Indicates no active slave (icon is blank).
Indicates a SED2 VFD fault has been recorded and the SED2 VFD has tripped.
Indicates a SED2 VFD with active warnings.
Indicates a SED2 VFD with communications problems.
Indicates a