Siemens SED2 manual AOP Stored Parameter Sets, Editing AOP-Stored Parameter Sets

Page 23

Editing Parameters

6.Press to access the index value. Use and to scroll through the index values and to highlight the desired index value.

7.Press to confirm the new index value. The AOP returns to the parameter selection screen so you can select another parameter, if desired.

8.To edit another indexed parameter, repeat Steps 3 to 6.

NOTES:

1.Simultaneously press and , at any time, to return to the main menu.

2.Simultaneously press and , at any time, to display the parameter help screens.

AOP Stored Parameter Sets

The AOP contains a battery-backed storage facility for storing up to 10 parameter sets that are identified numerically from 00 to 09.

Only a parameter set containing parameter data can be edited. If the selected parameter set does not contain parameter data, the AOP asks if the default parameter set should be copied to the selected parameter set. When you confirm this request, the AOP copies only the editable parameters to the selected parameter set; read-only parameters are accessed from the original parameter location.

Editing AOP-Stored Parameter Sets

Use the following procedure to edit a parameter set:

1.From the main menu, use and to scroll through the list of options and to highlight the Mode item. Press to confirm the selection.

The AOP displays a mode menu so you can select the operating mode.

2.Use and to scroll through the list of mode options and to highlight the Internal item. Press to confirm the selection.

The AOP displays an internal mode menu so you can select the internal mode function.

3.Press again to confirm the selection and to return to the main menu.

4.Use and to scroll through the main menu and to highlight the Parameters item. Press to confirm the selection.

The AOP displays an internal edit parameter set menu so you can select the desired parameter set.

5.Use and to scroll through the list of parameter sets and to highlight the desired parameter set number.

You can now edit parameters associated with the selected parameter set.

Editing Internal AOP Parameter Set

1. Set P0003=3 (expert parameter access level).

Siemens Building Technologies, Inc.

15

Image 23
Contents SED2 Advanced Operator Panel AOP Page Rev , September SED2 AOP Operating InstructionsPage Service Statement Underwriters Laboratories European Low Voltage DirectiveEuropean Machinery Directive European EMC DirectiveTable of Contents AOP Faults & Warnings AOP Setup & ConfigurationManual Organization How to Use this ManualReference Documents Where To Send CommentsNotation Symbol Meaning Manual NotationsLocal 1 Drive AOP OverviewAOP Menu Structure Main Menu Local and Master ModesKey Function Functional Description Key FunctionsAOP Overview Important Notes Power-on and InitializationAOP Start-Up & Initialization To Delete a Language Language SelectionStart Help Memory LimitationDescription Quick CommissioningMenu Item AOP Start-Up & Initialization Stopped Running Fault Inhibit AOP Applications Single Drive Control Using the AOPNetwork Setup RS-485 with Panel Mounting Kit Network Setup PC Mode Editing Conventional Parameters Parameter Access LevelsEditing Parameters Editing Indexed Parameters TIP How to quickly change parameter values?Editing Internal AOP Parameter Set AOP Stored Parameter SetsEditing AOP-Stored Parameter Sets Parameter Parameter Upload UpreadUpload/Download Limitations Parameter Download Wait RequestSED2 AOP Operating Instructions AOP Operating Modes Selecting an Operating ModeOperating Mode Icon Description Operating in Local ModeOperating in Master Mode Individual Control of SED2 VFD Verifying Drive Type Operating in Master Mode Broadcast OperationCommunications Failure Displaying Drive StatusKey Timer FunctionSetting the AOP Timer Timer Function Backlighting AOP Setup & ConfigurationSetup Menu Cursor Type Screen ContrastLarge Number Display User Defined Text Welcome TextSet Time/Date Parameter Set Names$51,1 AOP ResetFault Indication/Fault Screen AOP Faults & WarningsMultiple Warnings Multiple FaultsSimultaneous Faults and Warnings SED2 VFD Fault/Warning Record P0947Siemens Building Technologies, Inc Siemens Building Technologies AG Siemens Building Technologies, Inc