Using the Firmware Upgrade Utility
This Firmware Upgrade Utility is part of the firmware upgrade package available on the APC Web site. (Never use an Upgrade Utility designated for one product to upgrade the firmware of another product).
Using the Utility for upgrades on Windows systems. On any supported Windows operating system, the Firmware Upgrade Utility automates the transferring of the firmware modules, in the correct module order. The utility only works with a Rack PDU that has an IPv4 address.
Unzip the downloaded firmware upgrade file and
Using the Utility for manual upgrades, primarily on Linux. On
To extract the firmware files:
1.After extracting files from the downloaded firmware upgrade file, run the Firmware Upgrade Utility (the .exe file).
2.At the prompts, click Next>, and then specify the directory location to which the files will be extracted.
3.When the Extraction Complete message displays, close the dialog box.
Use FTP or SCP to upgrade one Rack PDU
FTP. To use FTP to upgrade a Rack PDU over the network:
•The Rack PDU must be on the network, with its system IP, subnet mask, and default gateway configured.
•The FTP server must be enabled at the Rack PDU, see “FTP Server” on page 68.
To transfer the files (this procedure assumes bootmon does not need upgrading, it is always necessary to upgrade the other two though):
1.The firmware module files must be extracted, see “To extract the firmware files:” .
2.At a computer on the network, open a command prompt window. Go to the directory that contains the firmware files, and list the files:
C:\>cd apc C:\apc>dir
For file information, see “Firmware module files (Rack PDU)” on page 86.
3.Open an FTP client session:
C:\apc>ftp
4.Type open with the IP address of the Rack PDU, and press ENTER. If the port setting for the FTP Server has changed from its default of 21, you must use the
•For Windows FTP clients, separate a
ftp> open 150.250.6.10 21000
•Some FTP clients require a colon instead before the port number.
5.Log on as Administrator (apc is the default user name and password).
6.Upgrade the AOS. (Always upgrade the AOS before the application module). ftp> bin
ftp> put apc_hw05_aos_nnn.bin (where nnn is the firmware version number)
7.When FTP confirms the transfer, type quit to close the session.
8.After 20 seconds, repeat step 3 through step 7, using the application module file name at step 6, .