APC Utilizing the IP Configuration Wizard for Devices to Export Configuration Settings

Page 90

How to Export Configuration Settings

Retrieving and Exporting the .ini File

Summary of the procedure

An Administrator can retrieve the .ini file of a Rack PDU and export it to another Rack PDU or to multiple Rack PDUs.

1.Configure a Rack PDU to have the settings you want to export.

2.Retrieve the .ini file from that Rack PDU.

3.Customize the file to change at least the TCP/IP settings.

4.Use a file transfer protocol supported by the Rack PDU to transfer a copy to one or more other Rack PDUs. For a transfer to multiple Rack PDUs, use an FTP or SCP script or the .ini file utility.

Each receiving Rack PDU uses the file to reconfigure its own settings and then deletes it.

Contents of the .ini file

The config.ini file you retrieve from a Rack PDU contains the following:

section headings and keywords (only those supported for the device from which you retrieve the file): Section headings are category names enclosed in brackets ([ ]). Keywords, under each section heading, are labels describing specific Rack PDU settings. Each keyword is followed by an equals sign and a value (either the default or a configured value).

The Override keyword: With its default value, this keyword prevents the exporting of one or more keywords and their device-specific values. For example, in the [NetworkTCP/IP] section, the default value for Override (the MAC address of the Rack PDU) blocks the exporting of values for the SystemIP, SubnetMask, DefaultGateway, and BootMode.

INI and Network Port Sharing

The INI configuration utility is able to get and set values for all Rack PDUs in a group. In order to be backwards compatible, the host Rack PDU will always be designated as first, "PDU_A". Any guest Rack PDUs are then designated "PDU_B", "PDU_C", and "PDU_D" based on their Display ID in ascending order. Therefore, "PDU_A" will not necessarily correlate to Display ID 1, and so on.

Note: Because of the large number of configuration values possible in a Rack PDU group, it may take a very long time to process an INI file set. For example, a Rack PDU group of 4 units with all values changing may take 30 minutes to complete processing.

Metered Rack PDU User Guide

82

Image 90
Contents User Guide Contents Log on to the Command Line Interface Web Interface Logs Administration Notification Device IP Configuration Wizard Troubleshooting Product Features IntroductionAccess Priorities for Logging on Types of User AccountsWatchdog Features Network Port SharingGetting Started Dhcp and Bootp configuration Establish Network SettingsTCP/IP configuration methods INI file utilityOption 43 = 01 04 31 41 50 Command Line Interface Recovering from a Lost Password Rack PDU Front Panel FunctionFunction Display Tree Example Display Tree Example Condition Description Load indicator LEDNetwork Status LED 10/100 LEDLog on to the Command Line Interface Command Line InterfaceAbout the Command Line Interface Remote access to the command line interfaceLocal access to the command line interface About the Main ScreenUsing the Command Line Interface IPv4 IPv6 Description OnlyCommand Syntax DescriptionCommand Response Codes Code MessageAbout Network Management Card Command DescriptionsAlarmcount Option Arguments DescriptionBoot Option Argument DescriptionClrrst Console Argument Description DateDelete DirExit DnsEventlog FormatNetstat Option Argument DefinitionHelp NtpPrompt PingPortSpeed QuitReboot RadiusResetToDef Snmp, snmpv3System Tcpip Tcpip6User WebXferINI XferStatusBkLowLoad Device Command DescriptionsNetwork Port Sharing Commands BkNearOverBkOverLoad BkReadingDevLowLoad DevReading DevNearOverDevOverLoad Argument DefinitionHumLow HumMinHumReading PhLowLoad PhNearOverPhOverLoad PhReading ProdInfo SensorNameTempHigh TempMaxTempReading Whoami Web Interface Supported Web BrowsersLogging On to the Web Interface Error Message Browser Cause of the Error URL address formatsTabs Web Interface FeaturesSymbol Description Device status iconsOther Web interface features Quick LinksGroup Control using Network Port Sharing Network Port Sharing on the Web InterfaceMetered Rack PDU User Guide Alarm Status view About the Home TabOverview view About the Device Manager Tab Configuring Load ThresholdsDevice Management Viewing the Load Status and Peak LoadConfigure the Name and Location of the Rack PDU Resetting Peak Load and kWhConfigure Temperature and Humidity Sensors EnvironmentLogs Use the Event and Data LogsEvent log Example event log Rack PDU 4 Device low load Data log Path Logs Data optionsParameter Description How to use FTP or SCP to retrieve log files Scp username@hostnameoripaddressdata.txt ./data.txtAuthentication Administration SecuritySetting user access Local UsersRadius Setting Definition RadiusConfiguring a Radius server on Unix with shadow passwords Configure the Radius ServerSummary of the configuration procedure Supported Radius serversInactivity Timeout TCP/IP settings Administration Network FeaturesTCP/IP and Communication Settings Setting DescriptionDhcp response options APC Cookie. Tag 1, Len 4, Data 1APCPort Speed Ping ResponseDNS Query Type Selected Query Question to UseWeb Option DescriptionStatus Console Telnet 152.214.12.1145000 telnet 152.214.12.114Snmp SNMPv1 SNMPv3 FTP Server Event Actions Administration NotificationConfiguring event actions Types of notificationMetered Rack PDU User Guide Active, Automatic, Direct Notification Mail notificationSend a test message to a configured recipient Snmp traps Snmp Trap TestRemote Monitoring Service Setting DefinitionSyslog Informational is mapped to Info Set the Date and Time Administration General OptionsIdentification ModeUse an .ini File Daylight savingChange the default temperature scale Event Log and Temperature UnitsReset the Rack PDU Color-code event log text Configure Links About the Rack PDUDevice IP Configuration Wizard Capabilities, Requirements, and InstallationUse the Wizard Configure or reconfigure the TCP/IP settings locally Select Remotely over the network, and click NextSelect Locally through the serial port, and click Next Contents of the .ini file How to Export Configuration SettingsSummary of the procedure Retrieving and Exporting the .ini FileDetailed procedures Ftp open ipaddress Messages in config.ini Upload Event and Error MessagesEvent and its error messages Errors generated by overridden valuesFirmware File Transfer Methods How to Upgrade FirmwareFile Transfers Benefits of upgrading firmwareUsing the Firmware Upgrade Utility Use FTP or SCP to upgrade one Rack PDUUse Xmodem to upgrade one Rack PDU How to upgrade multiple Rack PDUs Using the Firmware Upgrade Utility for multiple upgradesUsing a USB flash drive to upgrade one Rack PDU Firmware Module Binary File Verify the success or failure of the transfer Verifying Upgrades and UpdatesVerify the version numbers of installed firmware Last Transfer Result codesTroubleshooting Rack PDU Access ProblemsProblem Solution Appendix a List of Supported Commands Network Management Card Command DescriptionsSets manual IPv6 address Device Command Descriptions APC Worldwide Customer Support 990-3429D-001 10/2012