Liebert SERIES 300 UPS manual Site Planning Data, Series 300 UPS, 10 to 50 kVA

Page 14

 

Table 2

Site Planning Data, Series 300 UPS, 10 to 50 kVA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rectifier

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AC Input

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rectifier

with Optional

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AC Input

Input Filter

Battery

 

AC Output

Mechanical Data

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heat

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Dis-

 

 

 

 

 

 

 

 

 

 

 

 

 

Max.

 

 

 

 

 

sipa-

 

 

 

 

 

 

 

 

 

 

 

 

 

Dis-

 

 

 

 

DFL

tion

Cooling

 

Power

 

 

 

Rec

 

 

Rec

Nominal

Full

charge

 

Rec

Dimen-

 

Lb./

BTU/

Air

Model

Rating

Voltage

Current

**

Current

**

Voltage

Load

Current

Current

**

sions

Weight

Ft.2

hr.

CFM

 

kVA

kW

VAC/Freq

Nom

Max

 

Nom

Max

 

 

kW

 

Nom

 

(WxDxH)

 

 

 

 

311

10

8

208/60Hz

35A

44A

60A

30A

37A

50A

204VDC

9.3

58A

28A

35A

36x28x72 in

1100 lbs

157

6000

600

*

 

 

240/60Hz

29A

36A

50A

26A

32A

40A

(102 cells)

 

 

24A

30A

91x72x183 cm

499 kg

 

 

 

 

 

 

480/60Hz

15A

19A

25A

13A

16A

20A

 

 

 

12A

15A

 

 

 

 

 

 

 

 

600/60Hz

12A

15A

20A

11A

14A

20A

 

 

 

10A

15A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

321

15

12

208/60Hz

50A

63A

80A

44A

55A

70A

204VDC

13.8

85A

42A

60A

36x28x72 in

1100 lbs

157

6000

600

*

 

 

240/60Hz

43A

54A

70A

38A

48A

60A

(102 cells)

 

 

36A

45A

91x72x183 cm

499 kg

 

 

 

 

 

 

480/60Hz

22A

28A

40A

19A

24A

30A

 

 

 

18A

25A

 

 

 

 

 

 

 

 

600/60Hz

18A

23A

30A

15A

19A

25A

 

 

 

14A

20A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

331

20

16

208/60Hz

65A

81A

100A

57A

72A

90A

360VDC

17.8

62A

56A

70A

36x28x72 in

1400 lbs

200

8900

800

*

 

 

240/60Hz

56A

70A

90A

50A

62A

80A

(180 cells)

 

 

48A

60A

91x72x183 cm

635 kg

 

 

 

 

 

 

480/60Hz

28A

35A

50A

25A

31A

40A

 

 

 

24A

30A

 

 

 

 

 

 

 

 

600/60Hz

23A

29A

40A

20A

25A

30A

 

 

 

20A

25A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

341

30

24

208/60Hz

96A

120A

150A

85A

108A

150A

360VDC

26.4

92A

83A

125A

36x28x72 in

1400 lbs

200

12300

1050

*

 

 

240/60Hz

83A

104A

125A

74A

92A

110A

(180 cells)

 

 

72A

90A

91x72x183 cm

635 kg

 

 

 

 

 

 

480/60Hz

42A

53A

70A

37A

46A

60A

 

 

 

36A

50A

 

 

 

 

 

 

 

 

600/60Hz

33A

41A

50A

29A

37A

50A

 

 

 

29A

40A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

346

40

32

208/60Hz

128A

160A

200A

113A

142A

175A

360VDC

35.2

122A

111A

150A

36x28x72 in

1900 lbs

271

16400

1050

*

 

 

240/60Hz

111A

139A

175A

98A

123A

150A

(180 cells)

 

 

96A

125A

91x72x183 cm

882 kg

 

 

 

 

 

 

480/60Hz

55A

69A

90A

49A

61A

80A

 

 

 

48A

60A

 

 

 

 

 

 

 

 

600/60Hz

44A

55A

70A

39A

49A

60A

 

 

 

39A

50A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

356

50

40

208/60Hz

158A

198A

250A

140A

175A

225A

360VDC

43.7

150A

139A

175A

36x28x72 in

1900 lbs

271

18700

1050

*

 

 

240/60Hz

137A

171A

225A

122A

152A

200A

(180 cells)

 

 

120A

150A

91x72x183 cm

882 kg

 

 

 

 

 

 

480/60Hz

68A

85A

110A

61A

76A

100A

 

 

 

60A

80A

 

 

 

 

 

 

 

 

600/60Hz

55A

69A

90A

49A

61A

80A

 

 

 

48A

60A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Applicable

 

1

2

3,4

1

2

3,4

5

4,6

1

4,7

12,13,15

15

15

Notes:

 

 

 

 

 

9,10

 

 

9,10

 

 

9

 

9

 

 

 

 

 

 

 

 

 

 

 

11

 

 

11

 

 

11

 

11

 

 

 

 

 

 

 

 

 

 

 

13

 

 

13

 

 

13

 

13

 

 

 

 

 

 

 

 

 

 

 

14

 

 

14

 

 

14

 

14

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

For explanation of Applicable Notes, see referenced numbers in Notes below.

*Field-upgradeable to next larger model

**Rec = Recommended External Overcurrent Protection

Notes

1.Nominal (NOM) current is based on full rated output load.

2.Maximum (MAX) current (125% of NOM) is short duration for battery recharge conditions.

3.UPS input and bypass cables must be run in separate conduit from output cables.

4.If the UPS module is to be upgraded in the future, it is recommended that the AC input, bypass AC input, battery, and AC output wiring and overcurrent protection be sized initially for the future upgraded size.

5.Nominal battery voltage is shown at 2.0 volts/cell per NEC 480-2.

6.Power cables from UPS DC link to batteries should be sized for a total maximum 2.0 volt line drop (measured at UPS) at maximum discharge current.

7.Recommended bypass AC input and AC output overcurrent protection represents 125% of nominal full load current (continuous) per NEC 220-2(a).

8.UPS output load cables must be run in separate conduit from input and bypass cables.

9.Minimum sized grounding conductors to be per NEC 250-95. Parity sized ground conductors are recommended. Neutral conductors to be sized for full capacity per NEC-16 Note 10.

10.Wiring requirements:

AC INPUT: 3-phase, 3-wire plus ground (unit supplied with input isolation transformer).

3-phase, 4-wire plus ground (unit supplied with input auto transformer). AC OUTPUT: 3-phase, 4-wire plus ground.

DC INPUT: 2-wire (positive and negative), plus ground.

11.All wiring is to be in accordance with national and local electrical codes.

12.Minimum access clearance is 3 feet front and 1 foot above UPS.

13.Top or bottom cable entry through removable access plates. Cut plate to suit conduit size, then replace.

14.Control wiring and power wiring must be run in separate conduit.

15.Battery cabinet not included.

Additional Notes

1.If site configuration includes a back-up emergency generator, it is recommended that the engine generator set be properly sized and equipped for a UPS application. Generator options would typically include an isochronous governor (generator frequency regulation) and a UPS compatible regulator (generator voltage regulation). Consult generator manufacturer for required generator options and sizing.

2.If site configuration includes an automatic transfer switch, refer to the Liebert Power Line titled “Criteria for Application of Automatic Transfer Switches (ATS) with Uninterruptible Power Supply (UPS) Systems.” 91K-PLT-48-02. It is also recommended that the transfer switch be equipped with auxiliary contacts for UPS “on generator” current limit. Consult transfer switch manufacturer for required transfer switch options and sizing.

3.If site configuration requires an external isolated maintenance bypass circuit, it should be noted that the Utility AC input is not in phase with the UPS AC output, with the optional delta-wye input isolation transformer. Consult with sales representative or UPS applications engineer.

8 Installation

Image 14
Contents Series 300 UPS Page Table of Contents Êïèïì ÊïéïìÊïéïë ÊïèïëÈïçïê ÈïçïìÈïçïë ÈïçïéLJXUHýê LJXUHýìLJXUHýë LJXUHýéImportant Safety Instructions PDLQWHQDQFHýRIý\RXUý6HULHVýêííý836ýDQGýEDWWHULHVï $ $51,1Page $51,1 $87,21PRVWýVLJQLILFDQWýFDXVHýRIýVWDUWðXSýSUREOHPVï +$/ý92/7$*6ý,67ý,7+,1ý7+,6ý48,3017ý85,1*ýDefinitions External Maintenance Bypass Cabinet Static Transfer SwitchMaintenance Bypass Line Static Bypass LineModes of Operation Through the UPS ModuleVXSSRUWLQJýWKHýORDGï Safety PrecautionsHFHVVýPRLVWXUHñýRUýGHEULVï Site Planning Data, Series 300 UPS, 10 to 50 kVA Site Planning Data, Series 300 UPS, 65 to 125 kVA $ &$87,21 UPS InstallationInstallation Considerations Equipment Location Unloading and External InspectionInternal Inspection of the UPS System YHUWLFDOýDWýDOOýWLPHVïBattery Installation Battery Safety PrecautionsMatching Battery Cabinets IHHWýDQGýUHPRYHýVXSSRUWLQJýGHYLFHïNon-Standard Batteries Power and Control Wiring Electrical WiringUPS Wire Size Guidelines ÕZKHQýQHHGHGôï Battery WiringWKHý%DWWHU\ý&DELQHWýWRýWKHýDVVRFLDWHGý836ï UHVXOWïCopper Aluminum or Copper-Clad Aluminum Connection Type / Wire Size Range Wiring Connections Wiring InspectionSingle Line Diagram 10-125 kVA Installation UPS Cabinet Installation Diagram 10-30 kVA UPS Cabinet Installation Diagram 40-50 kVA UPS Cabinet Installation Diagram 65-125 kVA Battery Cabinet Installation Diagram 22-inch Frame Battery Cabinet Installation Diagram 36-inch Frame Battery Cabinet Installation Diagram 36-inch Frame Control Wiring Diagram 10-30 kVA Control Wiring Diagram 40-50 kVA Control Wiring Diagram 65-125 kVA Field Wiring Terminations Field Wiring Terminations Operator Controls and Indicators Digital Display ScreenBlock Diagram of the Series 300 UPS Power Status Diagram Selection Pads\SDVVý/LQHï Rotary SwitchAdvisory Display RSHUDWLRQïDisplay Screen Menu Menu Selection ArrangementNormal Operation Default Screen MessagesOn Maintenance Load on UPS Load XXX%UPS on Battery Load on Static SwitchFault System Shutdown Time Remaining XX MinutesOperator Response to an Alarm Alarm MessagesUPS Response to an Alarm Voltage 410 Amps Charging Load XXX% a Phase XXX kVA B Phase XXX kVA C Phase XXX kVASystem Status Screens 60.0 HzRating Press Review System Options ConfigurationDeutsche English Espanol Francais Italia Press To set Output Voltage RatingInput / Output Low BatteryNominal Press To setMON APR 15 Auto BatteryPress To view or set Time and DateAuto Restart ODWHUïLamp Test Alarm History Press To accessAlarm History Start-Up from Position Start-Up ProcedureStart-Up Testing inverter PowerTesting charger Press Button To start systemTesting static Rotary switch toTesting battery PositionSRZHUýWRýWKHýFULWLFDOýORDGï Testing InputSynchronization WKHýORDGïý7KHýIROORZLQJýGHIDXOWýPHVVDJHýZLOOýDSSHDUãýAbnormal Conditions During Start-Up IýWKHýV\VWHPýGHWHFWVýDQýDEQRUPDOýFRQGLWLRQýGXULQJýVWDUWðXSãFULWLFDOýORDGï Improperly OperatedResponse to an Incorrect Start-Up Sequence RLQJýVRýZLOOýFDXVHýDQýLPPHGLDWHýORVVýRIýSRZHUýWRýWKHýORDGïNormal Operation Shutdown Please turnUPS Response Response to a Power FailureCalculating Time Remaining VXSSO\ýSRZHUýWRýWKHýLQYHUWHUýZKLFKýVXSSRUWVýWKHýORDGïAs Battery Time Approaches Zero Operator Response$QýDXGLEOHýDODUPýZLOOýVRXQGï On Static SwitchResponse to a UPS Failure WKHýFULWLFDOýORDGýWKURXJKýWKHý0DLQWHQDQFHý%\SDVVý/LQHïAlarm Messages UPS System Cooling Maintenance IýDQ\ýRIýWKHýDERYHýRFFXUã When To CallSteps To Take Changing the Air Filter Preventive MaintenanceMaintaining an Operator’s Log Periodic Restart of the UPSMaintaining the Battery 3527&7,21ý85$17ý&6ý352&856ýª1757,1ïý81ý $957,660176ý3,&6ý6286ý$/,017$7,21ý65217ý/$,666ý6$16ý 356211/ý48$/,,ý67ý548,6ý3285ý&785ý&6ýREVHUYpHVã Battery Voltage VDC PDQXDOïý $ &$87,21 Ìï HDUýIXOOýH\HýSURWHFWLRQýDQGýSURWHFWLYHýFORWKLQJïProfessional Start-up Liebert Customer Service and SupportMaintenance Agreements TrainingGeneral Optional External Maintenance Bypass CabinetInstallation Location Considerations FDQQRWýEHýLQVWDOOHGýVHSDUDWHO\ýIURPýWKHý836ýPRGXOHïElectrical Wiring 127 5HIHUýWRýëïéïì ðý836ýLUHý6LHý*XLGHOLQHVïOperation Control Rotary Switch 7KHýWKUHHý5RWDU\ý6ZLWFKýSRVLWLRQVýDUHãFRQGLWLRQýKDVýEHHQýFRUUHFWHGï GLWLRQýRFFXUVïShutdown to Maintenance Position Optional Remote Contact Board Optional Slim-Line DistributionOptional Remote Status Panel RSWLRQýZKHQýDýUHPRWHýVWDWXVýSDQHOýRSWLRQýLVýSURYLGHGïUsing a Terminal as a Remote Station Optional RS-232 Interface PortRemote Front Panel Terminal Mode Key DescriptionEmerson Standard Protocol ESP Setting the PasswordPassword Remote Load ControlPHQWDWLRQýVXSSOLHGýVHSDUDWHO\ï Using an Snmp Adapter OptionalWXUQýWKHýORDGýRQýRUýRIIýDWýZLOOï Modem Mode OFF Optional Internal ModemOutgoing Calls Using the ModemIncoming Calls 000*000*000**?# Pager Disabled91000-000-0000 VLEOHýZKHQýLWýFDOOVýDýSDJHUýVHUYLFHýQXPEHUï Calling a ModemDQýHYHQWýRFFXUVïý WLRQã Editing the Phone NumbersÜýíýìýëýêýéýèýçýæýåýäýðýõýôýñýúýý5ý7ý3ý#ýóýâý Dial Test OFF Testing the Dial-Out SetupSetting the Data Rate Last Attempts\RXýDUHýSUHSDUHGï Optional IBM AS/400 Signal InterfaceOptional SiteScan /Sitemaster Interface ÌëííïOptional DC Ground Fault Alarm Optional System/38 Power Warning SignalOptional Battery Circuit Breaker Optional Contact Isolator BoardOptional Multi-Computer Interface System Optional IBM AS/400 Multi-Interface SystemOptional Maintenance Bypass Cabinet System Options Optional Slim-Line Distribution Optional Slim-Line Distribution Optional Remote Status Panel Optional Remote Contact Board Optional IBM AS/400 Signal Interface System Options Optional Battery Circuit Breaker 10-75 kVA Optional Battery Circuit Breaker 100-125 kVA Optional Computer Interface System Optional Multi-Computer Interface System Optional IBM AS/400 Multi-Interface System Electrical Specifications AC Inputs to UPSAC Output. UPS Inverter DXOWý&OHDULQJãý 6XEýF\FOHýFXUUHQWýRIýDWýOHDVWýêííøRatings Environmental SpecificationsMechanical Specifications 7HPSHUDWXUHý5DQJHã ‡ 2SHUDWLQJãBattery DWWHU\ý7\SHãý6HDOHGñýOHDGðDFLGñýLQýPDWFKLQJýFDELQHWýýSpecifications 5HYLVHGãý-XO\ýìääæ SDFNDJHïXVWRPHUý5HVSRQVHý&HQWHUï