Liebert SERIES 300 UPS manual Copper Aluminum or Copper-Clad Aluminum

Page 23

Table 4 Table 310-16

Allowable Ampacities of Insulated Conductors Rated 0-2000 Volts, 60° to 90°C (140° to 194°F) 1

Not More than Three Conductors in Raceway or Cable or Earth (Directly Buried), based on Ambient Temperature of 30° (86°F)

Size

 

 

Temperature Rating of Conductor. See Table 310-13.

 

Size

 

 

 

 

 

 

 

 

 

 

 

60°C

75°C

90°C

60°C

75°C

90°C

 

 

 

(140°F)

(167°F)

(194°F)

(140°F)

(167°F)

(194°F)

 

 

 

 

 

 

 

 

 

 

 

 

Types

Types

Types

Types

Types

Types

 

 

 

TW†

FEPW+,

TBS, SA,

TW†

RH†, RHW†,

TBS,

 

 

 

UF†

RH,RHW†,

SIS,FEP†,

UF†

THHW†,

SA,SIS,

 

AWG

 

THHW†,

FEPB†,MI,

 

THW†,

THHN†,

AWG

 

THW†,

RHH†, RHW-2

 

THWN†,

THHW†,

kcmil

 

 

kcmil

 

THWN†,

THHN†,THHW†,

 

XHHW†,

THW-2, THWN-2,

 

 

 

XHHW†,

THW-2,THWN-2,

 

USE†

RHH†, RHW-2,

 

 

 

 

USE†, ZW†

USE-2, XHH,

 

 

USE-2,

 

 

 

 

 

XHHW†

 

 

XHH, XHHW†,

 

 

 

 

 

XHHW-2,ZW-2

 

 

XHHW-2, ZW-2

 

 

 

 

 

 

 

 

 

 

 

 

Copper

 

Aluminum or Copper-Clad Aluminum

 

 

 

 

 

 

 

 

 

 

18

.......

.......

 

14

.......

.......

.......

.......

16

.......

.......

 

18

.......

.......

.......

.......

14

20†

20†

 

25†

.......

.......

.......

.......

12

25†

25†

 

30†

20†

20†

25†

12

10

30

35†

 

40†

25

30†

35†

10

8

40

50

 

55

30

40

45

8

 

 

 

 

 

 

 

 

 

6

55

65

 

75

40

50

60

6

4

70

85

 

95

55

65

75

4

3

85

100

 

110

65

75

85

3

2

95

115

 

130

75

90

100

2

1

110

130

 

150

85

100

115

1

 

 

 

 

 

 

 

 

 

1/0

125

150

 

170

100

120

135

1/0

2/0

145

175

 

195

115

135

150

2/0

3/0

165

200

 

225

130

155

175

3/0

4/0

195

230

 

260

150

180

205

4/0

 

 

 

 

 

 

 

 

 

250

215

255

 

290

170

205

230

250

300

240

285

 

320

190

230

255

300

350

260

310

 

350

210

250

280

350

400

280

335

 

380

225

270

305

400

500

320

380

 

430

260

310

350

500

 

 

 

 

 

 

 

 

 

600

355

420

 

475

285

340

385

600

700

385

460

 

520

310

375

420

700

750

400

475

 

535

320

385

435

750

800

410

490

 

555

330

395

450

800

900

435

520

 

585

355

425

480

900

 

 

 

 

 

 

 

 

 

1000

455

545

 

615

375

445

500

1000

1250

495

590

 

665

405

485

545

1250

1500

520

625

 

705

435

520

585

1500

1750

545

650

 

735

455

545

615

1750

2000

560

665

 

750

470

560

630

2000

 

 

 

 

 

 

 

 

 

Correction Factors

Ambient

For ambient temperatures other than 30°C (86°F), multiply the allowable ampacities shown

Ambient

Temp °C

 

 

above by the appropriate factor shown below.

 

Temp °F

 

 

 

 

 

 

 

 

 

21-25

1.08

1.05

 

1.04

1.08

1.05

1.04

70-77

26-30

1.00

1.00

 

1.00

1.00

1.00

1.00

78-86

31-35

.91

.94

 

.96

.91

.94

.96

87-95

36-40

.82

.88

 

.91

.82

.88

.91

96-104

41-45

.71

.82

 

.87

.71

.82

.87

105-113

46-50

.58

.75

 

.82

.58

.75

.82

114-122

51-55

.41

.67

 

.76

.41

.67

.76

123-131

56-60

.......

.58

 

.71

.......

.58

.71

132-140

61-70

.......

.33

 

.58

.......

.33

.58

141-158

71-80

.......

.......

 

.41

.......

.......

.41

159-176

 

 

 

 

 

 

 

 

 

† Unless otherwise specifically permitted elsewhere in this Code, the overcurrent protection for conductor types marked with an obelisk (†) shall not exceed 15 amperes for No. 14, 20 amperes for No. 12, and 30 amperes for No. 10 copper; or 15 amperes for No. 12 and 25 amperes for No. 10 aluminum and copper-clad aluminum after any correction factors for ambient temperature and number of conductors have been applied.

1 Reprinted with permission from NFPA 70-1993, the National Electrical Code®, Copyright 1996, National Fire Protection Association, Quincy, MA 02269. This reprinted material is not the complete and official position of the National Fire Protection Association, on the referenced subject which is represented only by the standard in its entirety.

Installation 17

Image 23
Contents Series 300 UPS Page Table of Contents Êïèïë ÊïéïìÊïéïë ÊïèïìÈïçïé ÈïçïìÈïçïë ÈïçïêLJXUHýé LJXUHýìLJXUHýë LJXUHýêPDLQWHQDQFHýRIý\RXUý6HULHVýêííý836ýDQGýEDWWHULHVï $ $51,1 Important Safety InstructionsPage +$/ý92/7$*6ý,67ý,7+,1ý7+,6ý48,3017ý85,1*ý $87,21PRVWýVLJQLILFDQWýFDXVHýRIýVWDUWðXSýSUREOHPVï $51,1Definitions Static Bypass Line Static Transfer SwitchMaintenance Bypass Line External Maintenance Bypass CabinetThrough the UPS Module Modes of OperationVXSSRUWLQJýWKHýORDGï Safety PrecautionsHFHVVýPRLVWXUHñýRUýGHEULVï Site Planning Data, Series 300 UPS, 10 to 50 kVA Site Planning Data, Series 300 UPS, 65 to 125 kVA $ &$87,21 UPS InstallationInstallation Considerations YHUWLFDOýDWýDOOýWLPHVï Unloading and External InspectionInternal Inspection of the UPS System Equipment LocationBattery Safety Precautions Battery InstallationIHHWýDQGýUHPRYHýVXSSRUWLQJýGHYLFHï Matching Battery CabinetsNon-Standard Batteries Power and Control Wiring Electrical WiringUPS Wire Size Guidelines UHVXOWï Battery WiringWKHý%DWWHU\ý&DELQHWýWRýWKHýDVVRFLDWHGý836ï ÕZKHQýQHHGHGôïCopper Aluminum or Copper-Clad Aluminum Connection Type / Wire Size Range Wiring Inspection Wiring ConnectionsSingle Line Diagram 10-125 kVA Installation UPS Cabinet Installation Diagram 10-30 kVA UPS Cabinet Installation Diagram 40-50 kVA UPS Cabinet Installation Diagram 65-125 kVA Battery Cabinet Installation Diagram 22-inch Frame Battery Cabinet Installation Diagram 36-inch Frame Battery Cabinet Installation Diagram 36-inch Frame Control Wiring Diagram 10-30 kVA Control Wiring Diagram 40-50 kVA Control Wiring Diagram 65-125 kVA Field Wiring Terminations Field Wiring Terminations Digital Display Screen Operator Controls and IndicatorsBlock Diagram of the Series 300 UPS Selection Pads Power Status DiagramRSHUDWLRQï Rotary SwitchAdvisory Display \SDVVý/LQHïMenu Selection Arrangement Display Screen MenuLoad on UPS Load XXX% Default Screen MessagesOn Maintenance Normal OperationTime Remaining XX Minutes Load on Static SwitchFault System Shutdown UPS on BatteryOperator Response to an Alarm Alarm MessagesUPS Response to an Alarm 60.0 Hz Load XXX% a Phase XXX kVA B Phase XXX kVA C Phase XXX kVASystem Status Screens Voltage 410 Amps ChargingOutput Voltage Rating Press Review System Options ConfigurationDeutsche English Espanol Francais Italia Press To set RatingPress To set Low BatteryNominal Input / OutputTime and Date Auto BatteryPress To view or set MON APR 15ODWHUï Auto RestartLamp Test Alarm History Press To accessAlarm History Start-Up from Position Start-Up ProcedureStart-Up Press Button To start system PowerTesting charger Testing inverterPosition Rotary switch toTesting battery Testing staticWKHýORDGïý7KHýIROORZLQJýGHIDXOWýPHVVDJHýZLOOýDSSHDUãý Testing InputSynchronization SRZHUýWRýWKHýFULWLFDOýORDGïIýWKHýV\VWHPýGHWHFWVýDQýDEQRUPDOýFRQGLWLRQýGXULQJýVWDUWðXSã Abnormal Conditions During Start-UpRLQJýVRýZLOOýFDXVHýDQýLPPHGLDWHýORVVýRIýSRZHUýWRýWKHýORDGï Improperly OperatedResponse to an Incorrect Start-Up Sequence FULWLFDOýORDGïNormal Operation Please turn ShutdownVXSSO\ýSRZHUýWRýWKHýLQYHUWHUýZKLFKýVXSSRUWVýWKHýORDGï Response to a Power FailureCalculating Time Remaining UPS ResponseOperator Response As Battery Time Approaches ZeroWKHýFULWLFDOýORDGýWKURXJKýWKHý0DLQWHQDQFHý%\SDVVý/LQHï On Static SwitchResponse to a UPS Failure $QýDXGLEOHýDODUPýZLOOýVRXQGïAlarm Messages UPS System Cooling Maintenance IýDQ\ýRIýWKHýDERYHýRFFXUã When To CallSteps To Take Periodic Restart of the UPS Preventive MaintenanceMaintaining an Operator’s Log Changing the Air FilterMaintaining the Battery 356211/ý48$/,,ý67ý548,6ý3285ý&785ý&6ý $957,660176ý3,&6ý6286ý$/,017$7,21ý65217ý/$,666ý6$16ý 3527&7,21ý85$17ý&6ý352&856ýª1757,1ïý81ýREVHUYpHVã Battery Voltage VDC Ìï HDUýIXOOýH\HýSURWHFWLRQýDQGýSURWHFWLYHýFORWKLQJï PDQXDOïý $ &$87,21Training Liebert Customer Service and SupportMaintenance Agreements Professional Start-upFDQQRWýEHýLQVWDOOHGýVHSDUDWHO\ýIURPýWKHý836ýPRGXOHï Optional External Maintenance Bypass CabinetInstallation Location Considerations General127 5HIHUýWRýëïéïì ðý836ýLUHý6LHý*XLGHOLQHVï Electrical Wiring7KHýWKUHHý5RWDU\ý6ZLWFKýSRVLWLRQVýDUHã Operation Control Rotary SwitchGLWLRQýRFFXUVï FRQGLWLRQýKDVýEHHQýFRUUHFWHGïShutdown to Maintenance Position RSWLRQýZKHQýDýUHPRWHýVWDWXVýSDQHOýRSWLRQýLVýSURYLGHGï Optional Slim-Line DistributionOptional Remote Status Panel Optional Remote Contact BoardOptional RS-232 Interface Port Using a Terminal as a Remote StationKey Description Remote Front Panel Terminal ModeRemote Load Control Setting the PasswordPassword Emerson Standard Protocol ESPPHQWDWLRQýVXSSOLHGýVHSDUDWHO\ï Using an Snmp Adapter OptionalWXUQýWKHýORDGýRQýRUýRIIýDWýZLOOï Optional Internal Modem Modem Mode OFFOutgoing Calls Using the ModemIncoming Calls 000*000*000**?# Pager Disabled91000-000-0000 VLEOHýZKHQýLWýFDOOVýDýSDJHUýVHUYLFHýQXPEHUï Calling a ModemDQýHYHQWýRFFXUVïý WLRQã Editing the Phone NumbersÜýíýìýëýêýéýèýçýæýåýäýðýõýôýñýúýý5ý7ý3ý#ýóýâý Last Attempts Testing the Dial-Out SetupSetting the Data Rate Dial Test OFFÌëííï Optional IBM AS/400 Signal InterfaceOptional SiteScan /Sitemaster Interface \RXýDUHýSUHSDUHGïOptional Contact Isolator Board Optional System/38 Power Warning SignalOptional Battery Circuit Breaker Optional DC Ground Fault AlarmOptional IBM AS/400 Multi-Interface System Optional Multi-Computer Interface SystemOptional Maintenance Bypass Cabinet System Options Optional Slim-Line Distribution Optional Slim-Line Distribution Optional Remote Status Panel Optional Remote Contact Board Optional IBM AS/400 Signal Interface System Options Optional Battery Circuit Breaker 10-75 kVA Optional Battery Circuit Breaker 100-125 kVA Optional Computer Interface System Optional Multi-Computer Interface System Optional IBM AS/400 Multi-Interface System AC Inputs to UPS Electrical SpecificationsDXOWý&OHDULQJãý 6XEýF\FOHýFXUUHQWýRIýDWýOHDVWýêííø AC Output. UPS Inverter7HPSHUDWXUHý5DQJHã ‡ 2SHUDWLQJã Environmental SpecificationsMechanical Specifications RatingsDWWHU\ý7\SHãý6HDOHGñýOHDGðDFLGñýLQýPDWFKLQJýFDELQHWýý BatterySpecifications 5HYLVHGãý-XO\ýìääæ SDFNDJHïXVWRPHUý5HVSRQVHý&HQWHUï