Liebert SERIES 300 UPS manual UPS System

Page 65

Table 8

Alarm Messages (continued)

 

 

Alarm

Meaning and

Message

Corrective Action in Brackets [ ]

UPS SYSTEM

 

 

 

 

UPS output not synchronized to input

UPS inverter output is not synchronized with the input power. Automatic

power

 

transfers to the Static Bypass Line are prohibited. This is usually a temporary

 

 

condition that is corrected automatically by the UPS internal control system.

 

 

Input power single phased

This message indicates an input power problem.

 

 

[Check all input power phases.]

 

 

Input voltage sensor failed

Each input voltage phase has two sensors. One of these sensors has failed.

 

 

[Contact Liebert Customer Service and Support at 1-800-543-2378.]

 

 

Inverter leg over current in X-phase

A fault has been detected in the inverter, caused by a UPS failure. The load

 

 

has been automatically transferred to the Static Bypass Line. Power to the load

 

 

is not being conditioned by the UPS.

 

 

[Contact Liebert Customer Service and Support at 1-800-543-2378.]

 

 

 

Output undervoltage

 

UPS output voltage is below a specified minimum. The load has been

 

 

automatically transferred to the Static Bypass Line. Power to the load is not

 

 

being conditioned by the UPS. An automatic retransfer will be attempted when

 

 

the output voltage is within tolerance.

 

 

[Contact Liebert Customer Service and Support if this condition persists.]

 

 

 

Output overvoltage

 

UPS output voltage is above a specified maximum. The load has been

 

 

automatically transferred to the Static Bypass Line. Power to the load is not

 

 

being conditioned by the UPS. An automatic retransfer will be attempted when

 

 

the output voltage is within tolerance.

 

 

[Contact Liebert Customer Service and Support if this condition persists.]

 

 

 

Output overcurrent

 

An output overcurrent surge has been detected. The load has been

 

 

automatically transferred to the Static Bypass Line. An automatic retransfer will

 

 

be attempted when the output current returns to nominal.

 

 

[Contact Liebert Customer Service and Support if this condition persists.]

 

 

System output overloaded

An overload condition is present. If the load is on the UPS inverter, the load will

 

 

be automatically transferred to the Static Bypass Line if the overload exceeds

 

 

the UPS Module capacity.

 

 

[Determine cause of the overload and reduce the load.]

 

 

Load transferred to bypass due to

The load has been automatically transferred to the Static Bypass Line because

overload

 

of an overload condition.

 

 

[Determine cause of the overload and reduce the load.]

 

 

System output overloaded

The overload condition is still present and must be reduced or it will soon

 

 

exceed the capacity of the Static Bypass Line, resulting in loss of all power to

 

 

the critical load. Power to the load is not being conditioned by the UPS.

 

 

[Determine cause of the overload and reduce the load.]

 

 

System shutdown due to overload

An overload condition has exceeded the capacity of the Static Bypass Line.

 

 

The UPS has been shut down, resulting in loss of power to the critical load.

 

 

[Perform a UPS shutdown procedure. Correct the overload condition and

 

 

perform a UPS start-up procedure.]

 

 

 

Control error

 

Automatic diagnostic testing has detected a failure (of hardware or software) in

 

 

the UPS internal control system. A second message may indicate internal test

 

 

or software timeout. The load has been automatically transferred to the Static

 

 

Bypass Line. Power to the load is not being conditioned by the UPS.

 

 

[Contact Liebert Customer Service and Support at 1-800-543-2378.]

 

 

Critical power supply failure

A failure has been detected in one of the low voltage power supplies. The load

 

 

has been automatically transferred to the Static Bypass Line. Power to the load

 

 

is not being conditioned by the UPS.

 

 

[Contact Liebert Customer Service and Support at 1-800-543-2378.]

 

 

Load transferred due to internal

A failure has been detected in the UPS. More specific information may be

protection

 

available in a separate Alarm Message. The load has been automatically

 

 

transferred to the Static Bypass Line (provided the power available on the

 

 

bypass line is within specifications). Power to the load is not being conditioned

 

 

by the UPS.

 

 

[Contact Liebert Customer Service and Support at 1-800-543-2378.]

 

 

 

Operation 59

Image 65
Contents Series 300 UPS Page Table of Contents Êïéïë ÊïéïìÊïèïì ÊïèïëÈïçïë ÈïçïìÈïçïê ÈïçïéLJXUHýë LJXUHýìLJXUHýê LJXUHýéPDLQWHQDQFHýRIý\RXUý6HULHVýêííý836ýDQGýEDWWHULHVï $ $51,1 Important Safety InstructionsPage PRVWýVLJQLILFDQWýFDXVHýRIýVWDUWðXSýSUREOHPVï $87,21$51,1 +$/ý92/7$*6ý,67ý,7+,1ý7+,6ý48,3017ý85,1*ýDefinitions Maintenance Bypass Line Static Transfer SwitchExternal Maintenance Bypass Cabinet Static Bypass LineThrough the UPS Module Modes of OperationVXSSRUWLQJýWKHýORDGï Safety PrecautionsHFHVVýPRLVWXUHñýRUýGHEULVï Site Planning Data, Series 300 UPS, 10 to 50 kVA Site Planning Data, Series 300 UPS, 65 to 125 kVA $ &$87,21 UPS InstallationInstallation Considerations Internal Inspection of the UPS System Unloading and External InspectionEquipment Location YHUWLFDOýDWýDOOýWLPHVïBattery Safety Precautions Battery InstallationIHHWýDQGýUHPRYHýVXSSRUWLQJýGHYLFHï Matching Battery CabinetsNon-Standard Batteries Power and Control Wiring Electrical WiringUPS Wire Size Guidelines WKHý%DWWHU\ý&DELQHWýWRýWKHýDVVRFLDWHGý836ï Battery WiringÕZKHQýQHHGHGôï UHVXOWïCopper Aluminum or Copper-Clad Aluminum Connection Type / Wire Size Range Wiring Inspection Wiring ConnectionsSingle Line Diagram 10-125 kVA Installation UPS Cabinet Installation Diagram 10-30 kVA UPS Cabinet Installation Diagram 40-50 kVA UPS Cabinet Installation Diagram 65-125 kVA Battery Cabinet Installation Diagram 22-inch Frame Battery Cabinet Installation Diagram 36-inch Frame Battery Cabinet Installation Diagram 36-inch Frame Control Wiring Diagram 10-30 kVA Control Wiring Diagram 40-50 kVA Control Wiring Diagram 65-125 kVA Field Wiring Terminations Field Wiring Terminations Digital Display Screen Operator Controls and IndicatorsBlock Diagram of the Series 300 UPS Selection Pads Power Status DiagramAdvisory Display Rotary Switch\SDVVý/LQHï RSHUDWLRQïMenu Selection Arrangement Display Screen MenuOn Maintenance Default Screen MessagesNormal Operation Load on UPS Load XXX%Fault System Shutdown Load on Static SwitchUPS on Battery Time Remaining XX MinutesOperator Response to an Alarm Alarm MessagesUPS Response to an Alarm System Status Screens Load XXX% a Phase XXX kVA B Phase XXX kVA C Phase XXX kVAVoltage 410 Amps Charging 60.0 HzDeutsche English Espanol Francais Italia Press To set Press Review System Options ConfigurationRating Output Voltage RatingNominal Low BatteryInput / Output Press To setPress To view or set Auto BatteryMON APR 15 Time and DateODWHUï Auto RestartLamp Test Alarm History Press To accessAlarm History Start-Up from Position Start-Up ProcedureStart-Up Testing charger PowerTesting inverter Press Button To start systemTesting battery Rotary switch toTesting static PositionSynchronization Testing InputSRZHUýWRýWKHýFULWLFDOýORDGï WKHýORDGïý7KHýIROORZLQJýGHIDXOWýPHVVDJHýZLOOýDSSHDUãýIýWKHýV\VWHPýGHWHFWVýDQýDEQRUPDOýFRQGLWLRQýGXULQJýVWDUWðXSã Abnormal Conditions During Start-UpResponse to an Incorrect Start-Up Sequence Improperly OperatedFULWLFDOýORDGï RLQJýVRýZLOOýFDXVHýDQýLPPHGLDWHýORVVýRIýSRZHUýWRýWKHýORDGïNormal Operation Please turn ShutdownCalculating Time Remaining Response to a Power FailureUPS Response VXSSO\ýSRZHUýWRýWKHýLQYHUWHUýZKLFKýVXSSRUWVýWKHýORDGïOperator Response As Battery Time Approaches ZeroResponse to a UPS Failure On Static Switch$QýDXGLEOHýDODUPýZLOOýVRXQGï WKHýFULWLFDOýORDGýWKURXJKýWKHý0DLQWHQDQFHý%\SDVVý/LQHïAlarm Messages UPS System Cooling Maintenance IýDQ\ýRIýWKHýDERYHýRFFXUã When To CallSteps To Take Maintaining an Operator’s Log Preventive MaintenanceChanging the Air Filter Periodic Restart of the UPSMaintaining the Battery 6ý3,&6ý6286ý$/,017$7,21ý65217ý/$,666ý6$16ý $957,660173527&7,21ý85$17ý&6ý352&856ýª1757,1ïý81ý 356211/ý48$/,,ý67ý548,6ý3285ý&785ý&6ýREVHUYpHVã Battery Voltage VDC Ìï HDUýIXOOýH\HýSURWHFWLRQýDQGýSURWHFWLYHýFORWKLQJï PDQXDOïý $ &$87,21Maintenance Agreements Liebert Customer Service and SupportProfessional Start-up TrainingInstallation Location Considerations Optional External Maintenance Bypass CabinetGeneral FDQQRWýEHýLQVWDOOHGýVHSDUDWHO\ýIURPýWKHý836ýPRGXOHï127 5HIHUýWRýëïéïì ðý836ýLUHý6LHý*XLGHOLQHVï Electrical Wiring7KHýWKUHHý5RWDU\ý6ZLWFKýSRVLWLRQVýDUHã Operation Control Rotary SwitchGLWLRQýRFFXUVï FRQGLWLRQýKDVýEHHQýFRUUHFWHGïShutdown to Maintenance Position Optional Remote Status Panel Optional Slim-Line DistributionOptional Remote Contact Board RSWLRQýZKHQýDýUHPRWHýVWDWXVýSDQHOýRSWLRQýLVýSURYLGHGïOptional RS-232 Interface Port Using a Terminal as a Remote StationKey Description Remote Front Panel Terminal ModePassword Setting the PasswordEmerson Standard Protocol ESP Remote Load ControlPHQWDWLRQýVXSSOLHGýVHSDUDWHO\ï Using an Snmp Adapter OptionalWXUQýWKHýORDGýRQýRUýRIIýDWýZLOOï Optional Internal Modem Modem Mode OFFOutgoing Calls Using the ModemIncoming Calls 000*000*000**?# Pager Disabled91000-000-0000 VLEOHýZKHQýLWýFDOOVýDýSDJHUýVHUYLFHýQXPEHUï Calling a ModemDQýHYHQWýRFFXUVïý WLRQã Editing the Phone NumbersÜýíýìýëýêýéýèýçýæýåýäýðýõýôýñýúýý5ý7ý3ý#ýóýâý Setting the Data Rate Testing the Dial-Out SetupDial Test OFF Last AttemptsOptional SiteScan /Sitemaster Interface Optional IBM AS/400 Signal Interface\RXýDUHýSUHSDUHGï ÌëííïOptional Battery Circuit Breaker Optional System/38 Power Warning SignalOptional DC Ground Fault Alarm Optional Contact Isolator BoardOptional IBM AS/400 Multi-Interface System Optional Multi-Computer Interface SystemOptional Maintenance Bypass Cabinet System Options Optional Slim-Line Distribution Optional Slim-Line Distribution Optional Remote Status Panel Optional Remote Contact Board Optional IBM AS/400 Signal Interface System Options Optional Battery Circuit Breaker 10-75 kVA Optional Battery Circuit Breaker 100-125 kVA Optional Computer Interface System Optional Multi-Computer Interface System Optional IBM AS/400 Multi-Interface System AC Inputs to UPS Electrical SpecificationsDXOWý&OHDULQJãý 6XEýF\FOHýFXUUHQWýRIýDWýOHDVWýêííø AC Output. UPS InverterMechanical Specifications Environmental SpecificationsRatings 7HPSHUDWXUHý5DQJHã ‡ 2SHUDWLQJãDWWHU\ý7\SHãý6HDOHGñýOHDGðDFLGñýLQýPDWFKLQJýFDELQHWýý BatterySpecifications 5HYLVHGãý-XO\ýìääæ SDFNDJHïXVWRPHUý5HVSRQVHý&HQWHUï