Table 8 | Alarm Messages (continued) | |
|
| |
Alarm | Meaning and | |
Message | Corrective Action in Brackets [ ] | |
UPS SYSTEM |
|
|
|
| |
UPS output not synchronized to input | UPS inverter output is not synchronized with the input power. Automatic | |
power |
| transfers to the Static Bypass Line are prohibited. This is usually a temporary |
|
| condition that is corrected automatically by the UPS internal control system. |
|
| |
Input power single phased | This message indicates an input power problem. | |
|
| [Check all input power phases.] |
|
| |
Input voltage sensor failed | Each input voltage phase has two sensors. One of these sensors has failed. | |
|
| [Contact Liebert Customer Service and Support at |
|
| |
Inverter leg over current in | A fault has been detected in the inverter, caused by a UPS failure. The load | |
|
| has been automatically transferred to the Static Bypass Line. Power to the load |
|
| is not being conditioned by the UPS. |
|
| [Contact Liebert Customer Service and Support at |
|
|
|
Output undervoltage |
| UPS output voltage is below a specified minimum. The load has been |
|
| automatically transferred to the Static Bypass Line. Power to the load is not |
|
| being conditioned by the UPS. An automatic retransfer will be attempted when |
|
| the output voltage is within tolerance. |
|
| [Contact Liebert Customer Service and Support if this condition persists.] |
|
|
|
Output overvoltage |
| UPS output voltage is above a specified maximum. The load has been |
|
| automatically transferred to the Static Bypass Line. Power to the load is not |
|
| being conditioned by the UPS. An automatic retransfer will be attempted when |
|
| the output voltage is within tolerance. |
|
| [Contact Liebert Customer Service and Support if this condition persists.] |
|
|
|
Output overcurrent |
| An output overcurrent surge has been detected. The load has been |
|
| automatically transferred to the Static Bypass Line. An automatic retransfer will |
|
| be attempted when the output current returns to nominal. |
|
| [Contact Liebert Customer Service and Support if this condition persists.] |
|
| |
System output overloaded | An overload condition is present. If the load is on the UPS inverter, the load will | |
|
| be automatically transferred to the Static Bypass Line if the overload exceeds |
|
| the UPS Module capacity. |
|
| [Determine cause of the overload and reduce the load.] |
|
| |
Load transferred to bypass due to | The load has been automatically transferred to the Static Bypass Line because | |
overload |
| of an overload condition. |
|
| [Determine cause of the overload and reduce the load.] |
|
| |
System output overloaded | The overload condition is still present and must be reduced or it will soon | |
|
| exceed the capacity of the Static Bypass Line, resulting in loss of all power to |
|
| the critical load. Power to the load is not being conditioned by the UPS. |
|
| [Determine cause of the overload and reduce the load.] |
|
| |
System shutdown due to overload | An overload condition has exceeded the capacity of the Static Bypass Line. | |
|
| The UPS has been shut down, resulting in loss of power to the critical load. |
|
| [Perform a UPS shutdown procedure. Correct the overload condition and |
|
| perform a UPS |
|
|
|
Control error |
| Automatic diagnostic testing has detected a failure (of hardware or software) in |
|
| the UPS internal control system. A second message may indicate internal test |
|
| or software timeout. The load has been automatically transferred to the Static |
|
| Bypass Line. Power to the load is not being conditioned by the UPS. |
|
| [Contact Liebert Customer Service and Support at |
|
| |
Critical power supply failure | A failure has been detected in one of the low voltage power supplies. The load | |
|
| has been automatically transferred to the Static Bypass Line. Power to the load |
|
| is not being conditioned by the UPS. |
|
| [Contact Liebert Customer Service and Support at |
|
| |
Load transferred due to internal | A failure has been detected in the UPS. More specific information may be | |
protection |
| available in a separate Alarm Message. The load has been automatically |
|
| transferred to the Static Bypass Line (provided the power available on the |
|
| bypass line is within specifications). Power to the load is not being conditioned |
|
| by the UPS. |
|
| [Contact Liebert Customer Service and Support at |
|
|
|