Inverter Drive Error Codes
Operation | Name | Description and NOTES | Check point | Corrective action | |
Panel | |||||
Indication |
|
|
|
|
|
| Inverter | If a current of more than 150% of the rated | Verify that the AC | Contact Alliance | |
| overload shut- | output current flows and overcurrent shut- | drive’s parameters are | Laundry Systems’ | |
| off (electronic | off does not occur (200% or less) inverse- | correct. | Customer Service | |
| overcurrent | time characteristics cause the electronic |
|
| department. |
| protection) | overcurrent protection to be activated to |
|
|
|
|
| stop the inverter output in order to protect |
|
|
|
|
| the output transistors. |
|
|
|
|
| Note: Resetting the inverter initializes |
|
|
|
|
| the internal heat integrating data of the |
|
|
|
|
| electronic overcurrent protection. |
|
|
|
|
|
|
|
|
|
| Fin overheat | If the cooling fin overheats, the overheat | ∙ | Check for too | Verify that the AC |
|
| sensor is actuated to stop the inverter | high ambient | drive’s parameters are | |
|
| output. | temperature. | correct. | |
|
|
| ∙ | Check for | Contact Alliance |
|
|
| cooling fin clogging | Laundry Systems’ | |
|
|
|
|
| Customer Service |
|
|
|
|
| department. |
|
|
|
|
|
|
| Brake transistor | Internal Circuit Error |
|
| Contact Alliance |
| alarm detection |
|
|
| Laundry Systems’ |
|
|
|
|
| Customer Service |
|
|
|
|
| department. |
|
|
|
|
| |
| Output side | This function stops the inverter output if a | Check the motor cable | Repair the wiring. | |
| ground fault | ground fault overcurrent flows due to a | insulation and |
| |
| overcurrent | ground fault which occurred in the | connection for output |
| |
| protection | inverter’s output (load) side. Use Pr. 249 |
| ||
|
| “ground fault detection at start” to set | fault. |
|
|
|
| whether the protective function is to be |
|
|
|
|
| activated or not. (In the 400V class, the |
|
|
|
|
| protective function is always active.) |
|
|
|
|
|
|
|
| |
| External thermal | If the external thermal relay designed for | Check for motor | Load the machine | |
| relay operation | motor overheat protection or the internally | overheating. | properly to distribute | |
|
| mounted temperature relay in the motor | Check to make sure | the load evenly. | |
|
| switches on (contacts open), the inverter | the machine is loaded |
| |
|
| output is stopped. If the relay contacts are | properly and that the |
| |
|
| reset automatically, the inverter will not | load is balanced. |
| |
|
| restart unless it is reset. |
|
|
|
|
|
|
|
| |
| Stall prevention | The running frequency has fallen to 0 with | Check the motor for a | Verify that the AC | |
|
| stall prevention activated. | “locked rotor” | drive’s parameters are | |
|
|
| condition. | correct. | |
|
|
|
|
| Contact Alliance |
|
|
|
|
| Laundry Systems’ |
|
|
|
|
| Customer Service |
|
|
|
|
| department. |
|
|
|
|
| |
| Output phase | This function stops the inverter output if | Check the wiring. | Tighten the wire | |
| failure | one of the three phases (U, V, W) on the | Check the motor for a | connections. | |
| protection | inverter’s output side (load side) results in | fault. |
| Replace the |
|
| open phase. |
|
| connectors as needed. |
|
|
|
|
| |
| Fan fault | For the inverter which contains a cooling | Check the cooling | Replace the fan as | |
|
| fan, FN appears on the operation panel | fan’s operation. | needed. | |
|
| when the cooling fan fails. |
|
|
|
|
|
|
|
|
|
9001889 | © Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT | 57 |