Inverter Drive Error Codes
Operation | Name | Description and NOTES | Check point | Corrective action | ||||
Panel | ||||||||
Indication |
|
|
|
|
|
|
|
|
| Stall prevention | During | ∙Check to make sure | ∙Load the machine | ||||
| (overcurrent) | than 150% of the rated inverter current | the machine is | properly to | ||||
|
| flows in the motor this function stops the | loaded properly and | distribute the load | ||||
|
| increase in frequency until the overload | that the load is | evenly. | ||||
|
| current reduces to prevent the inverter | balanced. | ∙Contact Alliance | ||||
|
| from resulting in overcurrent | ∙Verify that the AC | Laundry Systems’ | ||||
|
| When the overload current has reduces | drive’s parameters | Customer Service | ||||
|
| are correct. | department. | |||||
|
| below 150%, this function increases the | ||||||
|
|
|
|
|
| |||
|
| frequency again. |
|
|
|
| ||
|
| During |
|
|
|
| ||
|
| current of more than 150%, this function |
|
|
|
| ||
|
| lowers the frequency again. |
|
|
|
| ||
|
| When the overload current has reduces |
|
|
|
| ||
|
| below 150%, this function increases the |
|
|
|
| ||
|
| frequency again. |
|
|
|
| ||
|
| During |
|
|
|
| ||
|
| than 150% of the rated inverter current |
|
|
|
| ||
|
| flows in the motor, this function stops the |
|
|
|
| ||
|
| decrease in frequency until the overload |
|
|
|
| ||
|
| current reduces to prevent the inverter |
|
|
|
| ||
|
| from resulting in overcurrent |
|
|
|
| ||
|
| When the overload current has reduced |
|
|
|
| ||
|
| below 150%, this function decreases the |
|
|
|
| ||
|
| frequency again. |
|
|
|
| ||
|
|
|
|
|
|
|
|
|
| Stall prevention | During | Check to make sure | Load the machine | ||||
| (overvoltage) | energy of the motor exceeds the brake | the machine is loaded | properly to distribute | ||||
|
| capability, this function stops the decrease | properly and that the | the load evenly. | ||||
|
| in frequency to prevent overvoltage | load is balanced. |
| ||||
|
| shutoff. As soon as the regenerative |
|
|
|
| ||
|
| energy has reduced, deceleration resumes. |
|
|
|
| ||
|
|
|
|
|
|
|
|
|
| PU stop | A stop made by pressing the | STOP | key of | Check for a stop made | Perform operation | ||
| RESET | |||||||
|
| the PU has been set in Pr. 75 “PU stop | by pressing the | STOP |
| correctly. | ||
|
| RESET | ||||||
|
| selection”. | key of the operation |
| ||||
|
|
|
|
| panel during external |
| ||
|
|
|
|
| operation. |
| ||
|
|
|
|
|
|
|
|
|
|
| This alarm appears if: |
|
|
| Perform operation | ||
|
| ∙The RES signal is on; |
|
|
| correctly. | ||
|
| ∙You attempted to set any parameter |
|
|
|
| ||
|
| value in the external operation mode; |
|
|
|
| ||
|
| ∙You attempted to change the operation |
|
|
|
| ||
|
| mode during operation; |
|
|
|
| ||
|
| ∙You attempted to set any parameter |
|
|
|
| ||
|
| value outside its setting range. |
|
|
|
| ||
|
| ∙You attempted to set any parameter |
|
|
|
| ||
|
| value during operation (while signal |
|
|
|
| ||
|
| STF or STR is ON). |
|
|
|
| ||
|
| ∙You attempted to set any parameter |
|
|
|
| ||
|
| value while parameter write is being |
|
|
|
| ||
|
| inhibited in Pr. 77 “parameter write |
|
|
|
| ||
|
| inhibit selection”. |
|
|
|
|
58 | © Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT | 9001889 |