Inverter Drive Error Codes
Operation | Name | Description and NOTES | Check point | Corrective action | |
Panel | |||||
Indication |
|
|
|
|
|
| Overcurrent | When the inverter output current reaches | ∙ | Check the motor | Repair the wiring. |
| or exceeds approximately 200% of the | cable insulation and |
| ||
| acceleration | rated current during acceleration, the | connection for output |
| |
|
| protective circuit is activated to stop the |
| ||
|
| inverter output. | fault. |
|
|
|
|
|
|
|
|
| Overcurrent | When the inverter output current reaches | ∙ | Check the motor | Repair the wiring. |
| or exceeds approximately 200% of the | cable insulation and |
| ||
| constant speed | rated current during constant speed, the | connection for output |
| |
|
| protective circuit is activated to stop the |
| ||
|
| inverter output. | fault. |
|
|
|
|
|
|
| |
| Overcurrent | When the inverter output current reaches | ∙Check for sudden | ∙Contact Alliance | |
| or exceeds approximately 200% of the | speed reduction. | Laundry Systems’ | ||
| deceleration | rated current during deceleration (other | ∙Check the motor | Customer Service | |
|
| than acceleration or constant speed), the | cable insulation and | department. | |
|
| protective circuit is activated to stop the | connection for | ∙Repair the wiring. | |
|
| inverter output. | output |
| |
|
|
| ground fault. |
| |
| Regenerative | If regenerative energy causes the | Check to make sure | Load the machine | |
| overvoltage | inverter’s internal main circuit DC voltage | the machine is loaded | properly to distribute | |
| to reach or exceed the specified value, the | properly and that the | the load evenly. | ||
| acceleration | protective circuit is activated to stop the | load is balanced. |
| |
|
| inverter output. It may also be activated |
|
|
|
|
| by a surge voltage generated in the power |
|
|
|
|
| supply system. |
|
|
|
|
|
|
|
| |
| Regenerative | If regenerative energy causes the | Check to make sure | Load the machine | |
| overvoltage | inverter’s internal main circuit DC voltage | the machine is loaded | properly to distribute | |
| to reach or exceed the specified value, the | properly and that the | the load evenly. | ||
| constant speed | protective circuit is activated to stop the | load is balanced. |
| |
|
| inverter output. It may also be activated |
|
|
|
|
| by a surge voltage generated in the power |
|
|
|
|
| supply system. |
|
|
|
|
|
|
|
| |
| Regenerative | If regenerative energy causes the | Check to make sure | Load the machine | |
| overvoltage | inverter’s internal main circuit DC voltage | the machine is loaded | properly to distribute | |
| to reach or exceed the specifed value, the | properly and that the | the load evenly. | ||
| deceleration or | protective circuit is activated to stop the | load is balanced. |
| |
| stop | inverter output. It may also be activated |
|
|
|
|
| by a surge voltage generated in the power |
|
|
|
|
| supply system. |
|
|
|
|
|
|
|
| |
| Motor overload | The electronic overcurrent protection in | Verify that the AC | Contact Alliance | |
| the inverter detects motor overheat due to | drive’s parameters are | Laundry Systems’ | ||
| (electronic | overload or reduced cooling capability | correct. | Customer Service | |
| overcurrent | due to overload or reduced cooling |
|
| department. |
| protection) | capability during |
|
|
|
|
| to stop the inverter output. When a multi- |
|
|
|
|
| pole motor or two or more motors are run, |
|
|
|
|
| provide a thermal relay in the output side |
|
|
|
|
| of the inverter. |
|
|
|
|
|
|
|
|
|
56 | © Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT | 9001889 |