ADC EMU-830 Configure EMU Autoconfiguration through Bootp, Network Parameters, Option Function

Page 42

Chapter 3: Provisioning

September 25, 2006

Configure SNMP Operation Over SLIP

To configure the EMU-830 for basic SNMP operation over SLIP:

Step

Action

1In the Network Parameters menu (Figure 3-5 on page 3-9), enter the Local SLIP IP Address (see Table 3-5 on page 3-10).

2Enter the Local SLIP Subnet Mask.

3Use the SPACEBAR to select the SLIP Port Baud Rate.

4Press ENTER to confirm all network settings.

5Follow the EMU console prompt to reset the EMU.

Configure EMU Autoconfiguration through BOOTP

To use BOOTP capability of the EMU-830 (see Table 3-5):

Step

Action

1

In the Network Parameters menu, enter the BOOTP Server IP Address.

 

 

2

Enter the BOOTP Gateway IP Address.

 

 

3

Toggle the Boot Mode from NVRAM to Network.

 

 

4

Press ENTER to confirm all network settings.

 

 

5

Follow the EMU console prompt to reset the EMU.

 

 

 

Table 3-5. Network Parameters

Option

 

Function

 

 

 

Ethernet Address

 

Reflects the hardware Ethernet (MAC) address for

 

 

the EMU-830. This field cannot be changed.

 

 

 

Ethernet Connection

 

The Ethernet connection type is 10BASE-T. This

 

 

field cannot be changed.

 

 

 

Local IP Address

 

Must be configured for the EMU-830 Ethernet port to

 

 

respond to the local management station.

 

 

192.168.0.1 is the default setting using Telnet or

 

 

SNMP.

 

 

 

Local IP Subnet Mask

 

Allows the EMU-830 to determine if a host (TFTP

 

 

server, SNMP management station, or trap receiver)

 

 

is on the same local subnet. If it is, the EMU-830 can

 

 

communicate directly with the host; if it is not,

 

 

messages must be sent through a default router.

 

 

255.255.255.0 is the default setting

 

 

 

Default Gateway IP

 

Enter the IP address of the default gateway the

Address

 

EMU-830 will use if the EMU-830 and the host are

 

 

not on the same network. 0.0.0.0 is the default

 

 

setting.

 

 

 

Local SLIP IP Address

 

Must be configured for the EMU-830 SLIP port to

 

 

respond to the local management station. 0.0.0.0 is

 

 

the default setting, which means SLIP port is not

 

 

used.

 

 

 

Image 42
Contents WorldDSLTM Exchange Office Management Unit Revision History Table of Contents Table of ContentsSeptember 25 LTPE-UM-3159-02List of Figures 21.Xmodem Transfer Message List of FiguresSeptember 25List of Tables LTPE-UM-3159-02 ViiList of Tables September 25 Viii LTPE-UM-3159-02 Intended Audience IntroductionOrganization ConventionsAbout This Manual September 25 EU ComplianceInspecting Your Shipment Reader Alert MeaningNEW Features Standard FeaturesName Mode Function Front PanelEMU-830 List 4A and 6A Front Panel Components Major Components Multishelf TAOSeptember 25 Overview Local Management of a Single Shelf Using RS-232/Telnet Multishelf TAO Network Screen Snmp Snmp Management Information Base Ethernet NetworkTraps WorldDSL TrapsTraps Definition Bootp and Tftp Protocols Xmodem ProtocolAlarms Autonomous DIAL-OUT Alarm ReportingExternal Shelf Clock Backup Circuit External Shelf Clock and EMU-830 List 6A Backup CircuitOverview September 25 LTPE-UM-3159-02 EMU Jumper Settings Location of the Slip Header Connector P6 on the EMU-830EMU Installation Installation September 25September 25 Installation Installing the EMU-830 into Slot 17 of EMS-830Multishelf Cable Connections BASE-T Multishelf Cable ConnectionsEMU-830 Console Port Pinouts to DB-9 or DB-25 Connector Local Terminal ConnectionsConsole port Remote Terminal and Local Shelf Modem Connections Local Shelf Modem for Multishelf TAOAT&F Shelf Modem for Slip Operation Modem to EMU Serial Cable PinoutsModem to Slip Port Cable Pinouts Console Menu Navigation Keys Console Menu NavigationConsole Menu Options Press this Key To Perform this FunctionProvisioning September 25 Logon, Network, and Main Menu Screen SelectionsScreens and Selections Displays and Functions Multishelf Configuration September 25 ProvisioningLogging On Network Screen Logging in to the Main menu To log in to the Main menuMain Menu HDSL/G.SHDSL Line Unit Status Shelf AlarmsDSL/G.SHDSL Alarm Reporting Logging in to an HDSL/G.SHDSL CircuitDSL Line Unit Status Conditions State Indicator Description DSL Circuit Alarms in Order of Severity PriorityLogging into DSL Circuits Enabling or Disabling Alarm Reporting To enable or disable alarm reporting for DSL circuitsConfig Menu Configure Network Parameters for Multishelf TAO and Snmp Configure EMU Autoconfiguration through Bootp Network ParametersOption Function Snmp Parameters Menu Configure System Identification Provisioning September 25 Configure Snmp Community StringsConfigure Snmp Trap Receivers Snmp Parameters Menu Option FunctionOption Function Modem Parameters Configure and Test Dial-out Alarm Reporting Modem Parameters MenuLOSW* and LOSW1 Alarm Reporting Screen 10. Shelf Alarms Menu Remote Alarm Reporting 11. Remote Alarm Reporting Menu Item Set Date and Time12. Set Date/Time Dialog Box Change Password Provisioning September 25 To set the date and time13. Change Password Dialog Box Set Shelf ID Terminal Settings Provisioning September 25 To set the shelf IDSet to Factory Defaults 16. Restore To Factory Defaults Warning PromptReset EMU Inventory Information ScreenData in Inventory Information Screen Field DescriptionManaging Firmware Through the Upload Menu Upload to a Local or Remote Line UnitScreen -2 on 19. Upload Line Unit Menu Item 21. Xmodem Transfer Message September 25 Provisioning Upload Local EMU 23. Upload EMU Menu Item 25. Tftp Upload EMU Prompt 27. Boot Loader Prompt Upload Remote EMU29. Remote EMU Upload Message Provisioning September 25 LTPE-UM-3159-02 Regulatory Approvals Power RequirementsEnvironmental CompatibilityAppendix a Specifications September 25 LTPE-UM-3159-02 ADC Technical Assistance Center Sales AssistanceSystems Integration 800.366.3891Appendix B Product Support September 25 LTPE-UM-3159-02 Glossary LTPE-UM-3159-02 GL-1Glossary September 25 GL-2 LTPE-UM-3159-02September 25 Glossary LTPE-UM-3159-02 GL-3Glossary September 25 GL-4 LTPE-UM-3159-02 Certification and Warranty World Headquarters For Technical Assistance