Mitsubishi Electronics AJ65SBT-64AD user manual Data Link Cable Wiring, Wiring precautions

Page 39

4SETUP AND PREPARATION BEFORE OPERATION

4.7 Data Link Cable Wiring

MELSEC-A

This section explains the wiring of the CC-Link dedicated cable used for connection of the AJ65SBT-64AD and master module.

4.7.1 Instructions for handling the CC-Link dedicated cables

Do not handle the CC-Link dedicated cables roughly as described below. Doing so can damage the cables.

Compact with a sharp object.

Twist the cable excessively.

Pull the cable hard. (more than the permitted elasticity.)

Step on the cable.

Place an object on the top. Scratch the cable's protective layer.

4.7.2 Connection of the CC-Link dedicated cables

Connect the CC-Link dedicated cable between the AJ65SBT-64AD and master module as shown below.

Master module side

AJ65SBT-64AD

I/O module or like

Termination resistor

DA

 

DB

 

DG

 

SLD

CC-Link dedicated

FG

cable

DA

 

 

 

 

 

 

 

 

 

 

DA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DB

 

 

 

 

 

 

 

 

 

 

DB

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DG

 

 

 

 

 

 

 

 

 

 

DG

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SLD

 

CC-Link dedicated

 

 

 

SLD

FG

 

cable

 

 

 

FG

 

 

 

 

 

 

 

 

 

 

 

 

Termination resistor

4.8 Wiring

This section provides the instructions for wiring the AJ65SBT-64AD and its wiring with external equipment.

4.8.1 Wiring precautions

To obtain maximum performance from the functions of AJ65SBT-64AD and improve the system reliability, an external wiring with high durability against noise is required. The precautions when performing external wiring are as follows:

(1)Use separate cables for the AC and AJ65SBT-64AD external input signals, in order not to be affected by the AC side surge or conductivity.

(2)Do not bundle or place with load carrying wires other than the main circuit line, high voltage line or PLC. Noises, surges, or conductivity may affect the system.

(3)Place a one-point grounding on the PLC side for the shielded line or shielded cable. However, depending on the external noise conditions, it may be better have a grounding externally.

4 - 8

Image 39
Contents User,s Manual Safety Precautions Installation Precautions Starting and Maintenance Precautions Manual number is given on the bottom left of the back cover RevisionsOverview Programming Procedure Program Examples Setup and Preparation Before OperationIB-66251 Model CodeIB-66721 13J872Gppw Product components This product consists of the following Memo Overview MELSEC-A Overall Configuration MELSEC-A System ConfigurationApplicable System Applicable master modulesRestrictions on use of CC-Link dedicated instructions General Specification SpecificationPerformance Specification I/O Conversion Characteristics Voltage Input Characteristic Voltage input characteristicsCurrent input characteristics 0mA4mA Accuracy ResolutionCurrent Input Characteristic Accuracy Conversion speed AJ65SBT-64AD function list Function ListStored second time Stored third time Sampling processingMoving average processing Sampling time 4000 2000Remote I/O Signals Remote I/O signal listRemote I/O Signals List Remote I/O Signal Details 1/2 Functions of the remote I/O signalsFlag RYn+1A Error reset request flag Remote I/O Signal Details 2/2Device No Signal Name RXn+1A Initial data setting requestRemote register allocation Remote Register2 A/D conversion enable/prohibit specification Address RWwm B15 B12 b11 B8 b7 B4 b3 CH.4 CH.3 CH.2 CH.1 Input range setting Address RWwm+1Times Moving average processing count setting Address RWwm+25 CH. Digital output value Address RWrn to RWrn+3 B15 B14 B13 B12 B11 B10 CH.4 CH.3 CH.2 CH.1Create a program When making offset/gain setting, set all MELSEC-A Setup and Preparation Before OperationPre-Operation Procedure Precautions When HandlingDIN rail DIN rail hook Name of Each Part Switches Setting switchesSet Value Setting Switches Transmission Speed Speed setting Start Offset/Gain SettingPoint Facing Direction of the Module Installation Station Number SettingInstructions for handling the CC-Link dedicated cables Data Link Cable WiringWiring Wiring precautionsFor current input Maintenance and InspectionModule connection example For voltage inputMemo MELSEC-A Programming Programming ProcedureProgram Examples Program example for power-on MELSEC-A Program example for initial data changing MELSEC-A Initial settings Program example for power-on Setting of automatic refresh parameters Checking Program example for initial data changing MELSEC-A Program examples for use of the QnACPU Automatic refresh parameter setting Program example for initial data changing Program examples for use of the Qcpu Q mode Program for power-on Setting results Setting results of 1 to 8 are shown below Program for initial data changing Error status flag TroubleshootingUsing the Remote Input Signals to Check Errors Error flag RXnC has turned onTo enter the test mode? Terminals across Using the LED Indications to Check ErrorsSet the voltage value to within the range 20.4 to Specified value? 26.4VPower on again Operation?If the L ERR. LED has begun flickering though When the digital output value cannot be read Revise the parameter settings Is the L RUN LED lit? AJ65SBT-64AD AJ65BT-64AD AppendixMELSEC-A Appendix2 External dimension diagram Memo Ind ERR.LED of the master station flickers Memo Warranty User,s Manual