Configuring the MES1A/B
•If you configure this field for 0 it hold a single socket open to the last remote Modbus TCP slave accessed
•If you configure this field for any value between 3 and 60 seconds, it will close the last socket after the configured length of idle time.
Redundant Entry Retries After
The Redundant Entry Retries After field allows you to disable redundant retries or set a maximum length of time for retries.
•If you configure this field for 0 is disables the feature.
•If you configure this field for any value between 15 seconds and 60 seconds it will set the retry period to the configure time.
Add, Delete, Exit - Select Function
The Add, Delete, Exit - Select Function field is the starting point for managing entries in the IP Address Table.
•Type A to add an entry. The Modbus addr from prompt appears.
•Type D to delete an entry. The Delete entry number prompt appears.
•Type E to exit.
Modbus Address From/To
Configuring these fields sets up the range of Modbus slave addresses that will be forwarded to the IP address (that you will configure in the next step).
The prompt: Modbus addr from (1) indicates that no slave addresses have been added to the list so far. If other slave addresses have already been configured, the number will reflect the first available slave address number.
37.Press Enter to accept (1) as the first slave address number, or type in the number you prefer. After you press Enter, the Modbus Address To prompt appears.
38.Type in an slave address number that reflects the range of slaves that will be found at the IP address that will be entered in the next step. When you press Enter the Slave IP address prompt appears.