Configuring the MES1A/B
•the Serial Interface type and communications parameters
Figure 17. Serial & Mode Settings Menu
To configure Serial and Mode Settings, type 2 at the Select Command or parameter set (1..4) to change: prompt. The Attached Device
prompt appears.
Protocol
Protocol parameters must be set to match the type of Modbus device (master or slave) connected to the serial side of the MES1A/B device, and the type of Modbus protocol (ASCII or RTU) that will be used.
Attached Device
Modbus devices operate as either Masters (polling Slaves) or Slaves (responding to polls from Masters). An example of a Modbus master is a computer running HMI (human machine interface) software. Examples of Modbus slaves are controllers, remote terminal units (RTU) or programmable logic controllers (PLC).
To configure the type of Attached Device:
25.At the Attached Device (1=Slave 2=Master)(1) prompt
o To keep the current setting, press Enter o To select Slave, type 1
o To select Master, type 2
26.To accept changes, press Enter
Note: When Master mode is selected a fifth item (Unit ID
Serial Protocol
Modbus devices communicate in either of two Serial Protocols: ASCII or RTU. Modbus/ASCII protocol is slower and uses two ASCII characters to represent each 8 bit data byte. Modbus/RTU uses 8 bit binary data characters.
Manual Documentation Number: |
B&B Electronics Mfg Co Inc – 707 Dayton Rd - PO Box 1040 - Ottawa IL 61350 - Ph
B&B Electronics Ltd – Westlink Commercial Park – Oranmore, Galway, Ireland – Ph +353
25