Xantrex Technology XADC Connecting the AC to the Panel, To connect the AC input

Page 22

Xantrex AC to DC Converter

Connecting the AC to the Panel

See “Connection Types for AC and DC” on page 18 if you are not familiar with the connections used on the breakers.

When following the procedure, see Table 2 on page 24 for wire lengths and Table 1 on page 24 for torque values.

See Figure 4 on page 8 for panel electrical connection diagrams.

WARNING: Shock hazard

Ensure that the AC disconnect or breaker is open on the AC line before attempting any installation.

To connect the AC input:

1.Install a UL/CSA approved strain relief on the AC input cables.

2.Route the AC input cables through the knockouts in the back of the panel.

3.Install breaker(s) for your AC input source. See the documentation for your breaker to determine how it installs.

CAUTION

Breakers can be damaged if forced onto the AC “stab-lok” bus bar. Breakers should slide easily into position without excess force.

Important: The following breakers are suitable for each circuit:

MAIN: Cutler Hammer/Bryant/Westinghouse Type BR Series and ITE Gould QP Series. The maximum current rating for the main breaker is not to exceed the rating of the panelboard.

BRANCH: Cutler Hammer/Bryant/Westinghouse Type BR, BD Series and ITE Gould QP, QT Series. The maximum current rating for the branch breaker is not to exceed 20A. WIRE GAUGE: In order to remain within the manufacturer’s specifications for the above breakers, the gauge of wire used must be selected based on 75°C ratings from your local electrical code. Wiring with temperature ratings higher than 75°C may be used, however, the gauge must align with that of 75°C wire.

4.Connect the AC input ground (bare copper) cable from the AC input source to the front AC bus on the panel, marked “Equipment Grounding Terminal”.

5.Connect the AC input neutral (white) cable from the AC input source to the rear AC bus on the panel, marked “AC Neutral Terminal”.

6.Connect the AC line (black cable) to the top breaker (30A panel) or breaker 4+5 (50A panel). See Figure 4 on page 8.

Important: Main AC line must go into breaker location 1 (top breaker) for the 30A panel and into breaker location 4 and 5 for the 50A panel, where breakers 4 and 5 must employ a ganging mechanism. Bus bars have a protective tab to prevent non-certified breakers from being installed.

22

975-0301-01-01

Image 22
Contents Xantrex AC to DC Converter Installation Instructions Audience PurposeConventions Used Important Safety Instructions Explosive Gas Precautions Precautions When Working With BatteriesFCC Information to the User Installation Main ComponentsAC/DC Distribution Panel Xadc Internal ComponentsAC/DC Distribution Panel Components AC/DC Distribution Panel and Xadc Internal Components Installation Codes Installation Tools and MaterialsInstallation Configurations Choosing a LocationPreparing to Install Installing the Xadc stand-alone unitTo prepare the Xadc for installation To prepare the Xadc mounting location Connecting the DC BatteryPreparing the Mounting Location for the Xadc To connect the DCConnecting the AC Input To connect the AC inputTo mount the Xadc using the mounting plates Installing Xadc with the AC/DC Distribution PanelConfigurations To prepare the panel for installationTo prepare the Xadc for remote installation To prepare the Xadc for connected installationConnecting the Xadc and Panel Together To connect the Xadc and panel togetherPreparing the Mounting Location for the Xadc and Panel Connecting the DC to the PanelConnection Types for AC and DC DC PCB Removal Connecting the Panel to the Xadc DC Side To connect the panel to the Xadc DC sideConnecting the Panel to the Xadc AC Side To connect the panel to the Xadc AC sideConnecting the AC to the Panel To install the AC loads Mounting the Xadc and Panel when ConnectedTo mount the Xadc and panel when connected Mounting the Xadc and Panel Remotely DC Wire Size and Torque ValuesTo mount the Xadc and panel remotely Mechanical Specifications Electrical PerformanceDate and Revision