UNSUPERVISED, NORMALLY CLOSED
IN THIS CONFIGURATION, TRANSISTOR "S" (THE SWITCH) IS BIASED FOR CONDUCTION AND POINT "A" RESIDES CLOSE TO 0V. IF THE TRANSISTOR IS BIASED TO THE OFF STATE OR IF THE LINE IS CUT TO STOP CURRENT FLOW, POINT "A" RISES TOWARD 5V AND AN ALARM CONDITION.
NOTE: PIN NUMBERS REFER TO TYPICAL HEADER ALARM INPUT NUMBERS ON MATING PLUGS
NOTE: TIME DURATION OF THE INPUT CONTROL SIGNAL MUST
| +5V | INPUT |
| VOLTAGE | |
|
| A L A R M |
| 2.5V |
|
|
| |
POINT A | 0V | TIME |
|
|
BE 50ms OR MORE
_<50ms
HIGH =
ALARM WIRING SIDE
POINT A
PIN 1
PIN 2
S
EQUIPMENT SIDE
+5V
10K
100K
0.1uF 0.1uF
Processor
CIRCUITRY
10K
GNDGND
EXTERNAL
CONTROL
GND
| NORMAL | |
GND | CURRENT FL0W | |
NO ALARM | ||
|
UNSUPERVISED, NORMALLY OPEN
IN THIS CONFIGURATION, TRANSISTOR "S" (THE SWITCH) IS BIASED FOR NON- CONDUCTION AND POINT "A" RESIDES CLOSE TO 5V. IF AN INPUT CONTROL SIGNAL OF SUFFICIENT DURATION TURNS ON THE TRANSISTOR FOR ALARM ACTIVATION OR IF THE LINE IS SHORTED, POINT "A" WILL FALL TOWARD 0V AND AN ALARM CONDITION.
NOTE: PIN NUMBERS REFER TO TYPICAL HEADER ALARM INPUT NUMBERS ON MATING PLUGS
NOTE: TIME DURATION OF THE INPUT CONTROL SIGNAL MUST
+5V | INPUT |
VOLTAGE | |
POINT A |
|
| |
2.5V |
|
| A L A R M |
0V | TIME |
|
BE 50ms OR MORE
_<50ms
HIGH = ALARM
LOW = STAND-BY MODE
ALARM WIRING SIDE
POINT A
PIN 1
PIN 2
S
EQUIPMENT SIDE
+5V
10K
100K
0.1uF 0.1uF
Processor
CIRCUITRY
10K
GNDGND
EXTERNAL
CONTROL
GND
| NORMAL | |
GND | CURRENT FL0W | |
NO ALARM | ||
|
Figure 8b. Unsupervised Alarm Operation
Pelco Manual | 23 |