Silence Alarm & Backup Log Files (Service Terminal Interface)
6.0SILENCE ALARM & BACKUP LOG FILES (SERVICE TERMINAL INTERFACE)
This section describes two features that are available in the Service Terminal Interface:
•Silence Alarm
•Backup Log Files
6.1Silence Alarm (Service Terminal Interface)
The Silence Alarm menu item allows you to silence the audible alarm and reset the Common Alarm Relay output if the common alarm is configured to reset with silence.
This menu item is available only through the Service Terminal Interface and SiteScan Web connec- tion.
NOTE
An alarm may also be silenced by pressing any key on the LCD keypad on the front of the AC8. The LCD does not offer Silence Alarm as a menu item.
To silence the alarm remotely through the Service Terminal Interface:
•Connect to the AC8 either from a remote computer or through the RS232 port (see A.2 - Connecting to the Service Terminal Interface).
•At the Main Menu, enter 8 (Silence Alarm).
•At the Silence Alarm menu, shown below, enter 1 to silence the audible alarm immediately. (To exit without silencing the alarm, enter 2 or press the Escape key.)
Silence Alarm | (Service Terminal Interface only) |
SILENCE ALARM
Silence alarm and reset common alarm relay if common alarm relay is configured to reset with silence alarm
1=SILENCE ALARM 2=RETURN TO MAIN MENU
SELECT A NUMBER:1
>ALARM HAS BEEN SILENCED
• A confirmation message appears: “Alarm has been silenced.”
NOTE
Through SiteScan Web, this option is available via the AC8 Graphic
Screen.
31