7.2Setup System - Overview

System and Control Options

7.2Setup System - Overview

The Setup System screen displays seven options that allow you to configure input and output devices and their relationships, the common alarm, the modem, pagers to be dialed when alarms occur, and a variety of system details, such as login password and system date and time:

Setup Inputs

Setup Common Alarm

Setup Sensor

Setup Zones

Setup Outputs

Setup Modem & Pagers

Setup System Info

Setup Operation

Setup I/O Matrix

Setup System Menu

>SETUP INPUTS SETUP COMMON ALARM

SETUP SENSOR

↑↓ =NEXT =SELECT

SETUP ZONES SETUP OUTPUTS SETUP MODEM&PAGERS SETUP SYSTEM INFO SETUP OPERATION SETUP I/O MATRIX

7.3

Setup System - Setup Inputs

 

 

 

 

 

Select Input Menu

 

The AC8 has eight digital input points that may be configured

 

 

SELECT

INPUT

 

individually. These inputs may have a wide variety of Liebert or other

 

 

> DEVICE_1

NO-AL-L

 

manufacturers’ equipment connected for monitoring.

 

DEVICE_2

NO-AL-L

 

To configure a digital input:

 

↑↓ =NEXT

=SELECT

 

 

DEVICE_3

NO-AL-L

 

 

 

 

 

Log In and Choose Setup System

 

DEVICE_4

NO-AL-L

 

 

DEVICE_5

NO-AL-L

 

• From the Main Menu, use the arrows ↑↓ to choose System and

 

 

 

DEVICE_6

NO-AL-L

 

Control, then press Enter ↵ (see 7.1 - Login for help).

 

DEVICE_7

NO-AL-L

 

• Enter your password at the Login screen.

 

DEVICE_8

NO-AL-L

 

 

 

 

 

 

 

• From the System and Control Menu, use the arrows ↑↓ to choose

 

 

 

 

 

 

Setup System, then press Enter ↵ .

 

 

 

 

 

 

Select a Digital Input to Configure

 

 

 

 

 

 

• From the Setup System Menu, shown at right, use the arrows ↑↓ to choose Setup Inputs and

 

press Enter ↵ .

 

 

 

 

 

From the Select Input Menu, choose the input you want—for example, Device_1—and press Enter ↵ .

Table 15 shows the digital input features you may change, along with the default settings: you may change the name of the input, define it as Normally Open or Normally Closed, and specify it as alarm- able or as an event.

Alarmable inputs may be defined as either Unlatched or Latched.

Event status allows you to monitor a digital input’s state—and use a change in state to initiate an action through an output, if desired—without triggering an alarm. Events are always Unlatched.

You may also specify a time delay before the AC8 responds to an alarm or event.

Use the steps following Table 15 to change the default settings for any digital input.

Table 15 Default settings - digital inputs

Feature

Default

Other Options

LABEL

DEVICE_1

Any name (up to eight characters)

NORM OPEN/CLOSE

NO (Normally Open)

NC (Normally Closed)

ALARM/EVENT

AL (Alarmable)

EV (Event)

LATCHED

L (Latched) / Y (Yes)*

NL (Unlatched) / N (No)*

DELAY

00:01 (1 second)

Any time (in minutes and seconds) from 00:00 to 99:59

* NOTE: Different abbreviations are used to designate a digital input as Latched or Unlatched as shown below.

 

Settings - Select Input

When configuring an input

 

Menu (see Section 7.3)

(see Section 7.3.4)

Unlatched

NL (Not Latched)

N (No, not latched)

Latched

L (Latched)

Y (Yes, latched)

36

Page 44
Image 44