Setup Menu

APPENDIX B - DEFAULT SETTINGS QUICK REFERENCE GUIDE

This appendix provides a quick reference to default settings for the AC8. These settings also appear throughout the manual.

Table 35 AC8 - default settings for inputs and outputs

DEFAULT SETTINGS - DIGITAL INPUTS (FROM Table 15)

Feature

Default

Other Options

 

 

 

LABEL

DEVICE_1 - DEVICE_8

Any name (up to eight characters)

NORM OPEN/CLOSE

NO (Normally open)

NC (Normally closed)

ALARM/EVENT

AL (Alarmable)

EV (Event)

LATCHED

L (Latched) / Y (Yes)*

NL (Unlatched) / N (No)*

DELAY

00:01 (1 second)

Any time (in minutes and seconds) from 00:00 to 99:59

* NOTE: Different abbreviations are used to designate a digital input as Latched (L/Y) or Unlatched (NL/N) in Select Input/Set Inputs screens.

DEFAULT SETTINGS - ANALOG SENSOR INPUTS (FROM TABLE 17)

Feature

Default

Other Options

CONNECTED*

N (Not connected)*

Y (Connected)**

LABEL

SENSOR_1 - SENSOR_4

Any name (up to eight characters)

UNITS

DEG

Any units (up to three characters)

4 mA

+045.0

Can define up to two decimal places—e.g., -99.99

20 mA

+096.0

Can define up to two decimal places—e.g., +99.99

OFFSET

+000.0

Can define up to two decimal places—e.g., +00.00

ALARM/EVENT

AL (Alarmable)

EV (Event)

LATCHED

N (Unlatched)

Y (Latched)

LOW SETPT

+0050.0

Can define up to two decimal places—e.g., -999.99

HIGH SETPT

+0090.0

Can define up to two decimal places—e.g., +999.99

SENSOR DELAY

00:01 (1 second)

Any time (in minutes and seconds) from 00:00 to 99:59

* If a sensor is configured as N (Not connected), the display will show an empty reading (blank spaces). ** If a sensor is configured as Y (Connected) and is functioning properly, the display will show a reading.

If the connected sensor is not functioning properly, the display will show dashes (------) indicating a problem.

DEFAULT MAPPINGS - DIGITAL INPUTS TO CONTROL RELAYS (FROM TABLE 30)

Digital input

Mapping to control relay:

Digital input

 

Mapping to control relay:

Device_1

(none)

Device_5

 

(none)

 

 

 

 

 

Device_2

(none)

Device_6

 

(none)

 

 

 

 

 

Device_3

(none)

Device_7

 

(none)

 

 

 

 

 

Device_4

(none)

Device_8

 

(none)

DEFAULT MAPPINGS -

ANALOG INPUTS TO CONTROL

RELAYS (FROM TABLE 31)

Analog input

Mapping to control relay:

Analog input

 

Mapping to control relay:

 

 

 

 

 

Sensor_1

(none)

Sensor_3

 

(none)

Sensor_2

(none)

Sensor_4

 

(none)

DEFAULT SETTINGS - DIGITAL OUTPUTS (FROM Table 19)

 

 

Feature

Default

 

Other Options

 

 

 

 

 

NORM OPEN/CLOSE

NO (Normally open)

NC (Normally closed)

 

 

 

Outputs 1-2: OP (Operating)

OP (Operating)

 

 

MODE*

Outputs 3-4: ST (Standby)

ST (Standby)

 

 

 

Outputs 5-8: NU (Not Used)

NU (Not Used)

 

 

IN ALARM

E (Enable)

D (Disable)

 

 

EMERG OP

E (Enable)

D (Disable)

 

 

117

Page 125
Image 125
Emerson user manual Appendix B Default Settings Quick Reference Guide, AC8 default settings for inputs and outputs