Emerson AC8 user manual 7.11.1Set Up Mapping for a Digital Input, Log In and Choose Setup System

Models: AC8

1 128
Download 128 pages 38.48 Kb
Page 81
Image 81
Select Setup I/O Matrix

System and Control Options

7.11Setup System - Setup I/O Matrix

The Setup I/O Matrix menu allows you to configure the AC8’s digital and analog inputs to trigger var- ious actions in either or both of the two control relays. Each relay can be set up to respond to more than one digital or analog input.

Almost any mapping combination can be used. For example, you may decide to trigger an action in Control Relay 1 when Device_1 goes into alarm, or you might want to generate an action in Control Relay 2 when Sensor_1 High Setpoint goes into alarm.

To set up the mapping of inputs to relays:

Log In and Choose Setup System

• From the Main Menu, use the arrows ↑↓ to choose System and Control, then press Enter ↵ (see 7.1 - Login for help).

• Enter your password at the Login screen.

• From the System and Control Menu, use the arrows ↑↓ to choose Setup System, then press Enter ↵ .

Select Setup I/O Matrix

• From the Setup System Menu, shown at right, use the arrows ↑↓ to choose Setup I/O Matrix and press Enter ↵ .

Setup System Menu

SETUP INPUTS SETUP COMMON ALARM SETUP SENSOR

↑↓ =NEXT =SELECT

SETUP ZONES SETUP OUTPUTS SETUP MODEM&PAGERS SETUP SYSTEM INFO SETUP OPERATION

> SETUP I/O MATRIX

Use the following instructions to set up the mapping of each digital input or analog sensor input to each relay.

7.11.1Set Up Mapping for a Digital Input

Use the arrows ↑↓ to choose Map Input To Relay from the Map Input/Sensor Menu, and press Enter ↵ .

From the Select Input Menu, choose the input you want—for exam- ple, Device_1—and press Enter ↵ .

On the Input-to-Relay Map screen, you may map the selected input to either or both of the control relays (1-2). The example at right shows Device_1 mapped to Control Relay 1.

To make changes to the mapping:

If needed, press Enter ↵ to advance to the position directly below the relay.

Use the arrows ↑↓ to choose Y (Yes - Mapped to this relay) or N (No - Not mapped), then press Enter ↵ .

Press Enter ↵ to advance to the next position where you want to make a change.

Use the arrows ↑↓ to choose Y (Yes - Mapped to this relay) or N (No - Not mapped), then press Enter ↵ .

When finished, press Enter ↵ again.

Default Mappings - Digital Inputs to Control Relays

By default, digital inputs are not mapped to any control relay, as shown in Table 30.

Table 30 Default mapping of digital inputs to relays

Digital input

By default, mapped to control relay:

Device_1

(none)

Device_2

(none)

Device_3

(none)

Device_4

(none)

Device_5

(none)

Device_6

(none)

Device_7

(none)

Device_8

(none)

Map Input/Sensor Menu

>MAP INPUT TO RELAY MAP SENSOR TO RELAY

↑↓ =NEXT =SELECT

Select Input

SELECT INPUT

> DEVICE_1

 

 

DEVICE_2

=SELECT

 

↑↓ =NEXT

 

 

 

 

DEVICE_3

 

 

DEVICE_4

 

 

DEVICE_5

 

 

DEVICE_6

 

 

DEVICE_7

 

 

DEVICE_8

 

Input-to-Relay Map

1 CONTROL RELAY

1 2 Y N

↑↓ =Y/N =NEXT/END

73

Page 81
Image 81
Emerson AC8 user manual 7.11.1Set Up Mapping for a Digital Input, Log In and Choose Setup System, Select Setup I/O Matrix