System and Control Options
7.3.4Set Up Alarmable Inputs in Latched or Unlatched Mode
Alarmable input points may be set up in Latched mode (Y), which requires the user to clear the AC8 alarms after an alarm has occurred, or Unlatched mode (N), in which alarms will automatically clear after a
Any input defined as an event is automatically Unlatched.
A digital input defined as Latched does not reset automatically after an alarm. It will remain in the triggered position even after the moni- tored device returns to normal. After an alarm, the user must manu- ally reset Latched inputs, as described in 7.13.1 - Clear Active Alarms. This also means that any digital outputs linked to a Latched digital input will remain triggered until the input is manually reset.
A digital input defined as Unlatched will automatically track the sta- tus of the monitored device. No action by the user is required.
•From the Setup Inputs Menu, choose Latched, as shown above right, and press Enter ↵ .
• To change this feature, use the arrows ↑↓ to choose Y (Yes - Latched) or N (No - Unlatched), then press Enter ↵ .
NOTE: Only alarmable input points may be set up as Latched. Once an input is defined as an event, the Latched entry displays N/A. If you attempt to set up an event as Latched, the message shown at right appears. Press the ESC key to return to the previous screen to con- tinue configuring the digital input.
The only way to reset latched alarms is by clearing active alarms. This step is required to return latched points to their normal state. For details, see 7.13.1 - Clear Active Alarms.
Setup Inputs Menu
SETUP DEVICE_1
LABEL: DEVICE_1
NORM OPEN/CLOSE: NO | |
ALARM/EVENT: AL | |
↑↓ =NEXT | ↵ =SELECT |
>LATCHED: Y
DELAY: 00:01
Latched / Unlatched
IS ALARM
LATCHED? N
↑↓ =Y/N | ↵ =END |
Message (if input has been defined as an event)
LATCH NOT ALLOWED WHEN IN EVENT MODE
ESC=BACK
7.3.5Set Up Delay Time
Each input may be set up with a specified time delay between the occurrence of an alarm or
This delay is the amount of time that must elapse before the AC8 acknowledges the change of state in the monitored device and takes any further action, such as dialing configured pagers. The default time delay is 1 second (displayed as 00 MIN : 01 SEC).
The time delay applies only when a monitored device changes from its normal
When the monitored device returns to its normal state, the AC8 acknowledges the change of state immediately.
•From the Setup Inputs Menu, choose Delay, as shown at right, and press Enter ↵ .
Setup Inputs Menu
SETUP DEVICE_1
LABEL: DEVICE_1 | |
NORM OPEN/CLOSE: NO | |
ALARM/EVENT: AL | |
↑↓ =NEXT | ↵ =SELECT |
LATCHED: N
DELAY: 00:01
Delay Time
DELAY TIME BEFORE TRIGGER?
00 MIN : 01 SEC ↑↓ =SELECT ↵ =NEXT/END
• To change the time delay in minutes and seconds (in the range of 00:00 to 99:59):
• For minutes (MIN), press and hold one of the arrow keys ↑↓ scroll through the numbers
• Press Enter ↵ to advance to seconds (SEC).
• For seconds (SEC), press and hold one of the arrow keys ↑↓ scroll through the numbers
• When finished, press Enter ↵ again.