Emerson AC8 user manual 7.5.4Change 4 mA Value, 7.5.5Change 20 mA Value, 7.5.6Change Offset Value

Models: AC8

1 128
Download 128 pages 38.48 Kb
Page 50
Image 50
7.5.4Change 4 mA Value

System and Control Options

7.5.4Change 4 mA Value

For the 4 mA value, enter the smallest value for the range of the sen- sor—for example, 50°F for a temperature sensor with a range of 50°F to 90°F.

The default value for each sensor is +045.0. Values that can be entered range from -999.9 to +999.9.

To enter a new value:

From the Setup Sensor Menu, choose 4 mA for the selected sensor and press Enter ↵ .

To change the 4 mA value:

Use the arrows ↑↓ to choose a character.

Press Enter ↵ to advance to the next character position.

When finished, press Enter ↵ again.

7.5.5Change 20 mA Value

For the 20 mA value, enter the largest value for the range of the sen- sor—for example, 90°F for a temperature sensor with a range of 50°F to 90°F.

The default value for each sensor is +096.0. Values that can be entered range from -999.9 to +999.9.

To enter a new value:

From the Setup Sensor Menu, choose 20 mA for the selected sen- sor and press Enter ↵ .

To change the 20 mA value:

Use the arrows ↑↓ to choose a character.

Press Enter ↵ to advance to the next character position.

When finished, press Enter ↵ again.

7.5.6Change Offset Value

For the Offset value, enter an adjustment factor—for example, if the sensor reading shows 70°F when the actual temperature is 75°F, the offset might be 5°F.

The default Offset value for each sensor is +000.0. Values that can be entered range from -999.9 to +999.9.

To enter a new value:

From the Setup Sensor Menu, choose Offset for the selected sensor and press Enter ↵ .

To change the Offset value:

Use the arrows ↑↓ to choose a character.

Press Enter ↵ to advance to the next character position.

When finished, press Enter ↵ again.

Setup Sensor Menu

SETUP SENSOR_1 CONNECTED: Y LABEL: ROOM_TMP ↑↓ =NEXT =SELECT

UNITS: DEG

>4 mA: +045.0

20 mA: +096.0

OFFSET: +000.0

ALARM/EVENT: AL

LATCHED: N

LOW SETPT: +0050.0

HIGH SETPT: +0090.0

SENSOR DELAY: 00:01

Change 4 mA Value

CHANGE 4 mA VALUE

4 mA: +050.0

↑↓ =SELECT =NEXT/END

Setup Sensor Menu

SETUP SENSOR_1 CONNECTED: Y LABEL: ROOM_TMP ↑↓ =NEXT =SELECT

UNITS: DEG

4 mA: +050.0

>20 mA: +096.0

OFFSET: +000.0

ALARM/EVENT: AL

LATCHED: N

LOW SETPT: +0050.0

HIGH SETPT: +0090.0

SENSOR DELAY: 00:01

Change 20 mA Value

CHANGE 20 mA VALUE

20 mA: +090.0

↑↓ =SELECT =NEXT/END

Setup Sensor Menu

SETUP SENSOR_1 CONNECTED: Y LABEL: ROOM_TMP ↑↓ =NEXT =SELECT

UNITS: DEG

4 mA: +050.0

20 mA: +090.0

>OFFSET: +000.0

ALARM/EVENT: AL

LATCHED: N

LOW SETPT: +0050.0

HIGH SETPT: +0090.0

SENSOR DELAY: 00:01

Change Offset Value

CHANGE OFFSET VALUE

OFFSET: +005.0

↑↓ =SELECT =NEXT/END

42

Page 50
Image 50
Emerson AC8 user manual 7.5.4Change 4 mA Value, 7.5.5Change 20 mA Value, 7.5.6Change Offset Value, Setup Sensor Menu