System and Control Options

7.5.4Change 4 mA Value

For the 4 mA value, enter the smallest value for the range of the sen- sor—for example, 50°F for a temperature sensor with a range of 50°F to 90°F.

The default value for each sensor is +045.0. Values that can be entered range from -999.9 to +999.9.

To enter a new value:

From the Setup Sensor Menu, choose 4 mA for the selected sensor and press Enter .

To change the 4 mA value:

Use the arrows ↑↓ to choose a character.

Press Enter to advance to the next character position.

When finished, press Enter again.

7.5.5Change 20 mA Value

For the 20 mA value, enter the largest value for the range of the sen- sor—for example, 90°F for a temperature sensor with a range of 50°F to 90°F.

The default value for each sensor is +096.0. Values that can be entered range from -999.9 to +999.9.

To enter a new value:

From the Setup Sensor Menu, choose 20 mA for the selected sen- sor and press Enter .

To change the 20 mA value:

Use the arrows ↑↓ to choose a character.

Press Enter to advance to the next character position.

When finished, press Enter again.

7.5.6Change Offset Value

For the Offset value, enter an adjustment factor—for example, if the sensor reading shows 70°F when the actual temperature is 75°F, the offset might be 5°F.

The default Offset value for each sensor is +000.0. Values that can be entered range from -999.9 to +999.9.

To enter a new value:

From the Setup Sensor Menu, choose Offset for the selected sensor and press Enter .

To change the Offset value:

Use the arrows ↑↓ to choose a character.

Press Enter to advance to the next character position.

When finished, press Enter again.

Setup Sensor Menu

SETUP SENSOR_1 CONNECTED: Y LABEL: ROOM_TMP ↑↓ =NEXT =SELECT

UNITS: DEG

>4 mA: +045.0

20 mA: +096.0

OFFSET: +000.0

ALARM/EVENT: AL

LATCHED: N

LOW SETPT: +0050.0

HIGH SETPT: +0090.0

SENSOR DELAY: 00:01

Change 4 mA Value

CHANGE 4 mA VALUE

4 mA: +050.0

↑↓ =SELECT =NEXT/END

Setup Sensor Menu

SETUP SENSOR_1 CONNECTED: Y LABEL: ROOM_TMP ↑↓ =NEXT =SELECT

UNITS: DEG

4 mA: +050.0

>20 mA: +096.0

OFFSET: +000.0

ALARM/EVENT: AL

LATCHED: N

LOW SETPT: +0050.0

HIGH SETPT: +0090.0

SENSOR DELAY: 00:01

Change 20 mA Value

CHANGE 20 mA VALUE

20 mA: +090.0

↑↓ =SELECT =NEXT/END

Setup Sensor Menu

SETUP SENSOR_1 CONNECTED: Y LABEL: ROOM_TMP ↑↓ =NEXT =SELECT

UNITS: DEG

4 mA: +050.0

20 mA: +090.0

>OFFSET: +000.0

ALARM/EVENT: AL

LATCHED: N

LOW SETPT: +0050.0

HIGH SETPT: +0090.0

SENSOR DELAY: 00:01

Change Offset Value

CHANGE OFFSET VALUE

OFFSET: +005.0

↑↓ =SELECT =NEXT/END

42

Page 50
Image 50
Emerson AC8 user manual Change 4 mA Value, Change 20 mA Value, Change Offset Value